Finding | |
|---|---|
| Title | Failure to Identify and Perform Testing to Demonstrate Local Manual Operation Action on SAFETY-RELATED AIR-OPERATED Valves |
| Description | The inspectors identified a NCV of 10 CFR Part 50, Appendix B, Criterion XI, Test Control, because the licensee failed to identify and perform testing on safety-related components to demonstrate that they would perform satisfactorily in service in accordance with requirements contained in applicable design documents. Specifically, the licensee did not identify and perform testing on several safetyrelated air-operated valves to demonstrate local manual operation in the event their safety-related nitrogen accumulators were exhausted. As a result, the licensee could not demonstrate that the safety-related valves would perform satisfactorily in service in accordance with requirements contained in the updated final safety analysis report (UFSAR) and design calculations. The licensee entered this issue into their corrective action program as CR-WF3-2012-6703. The immediate corrective actions taken to restore compliance included developing a test for the local manual operation for some valves and the installation of a backup air supply to recharge the accumulators for other valves. The failure to identify and perform testing to demonstrate that safety-related airoperated valves would perform satisfactorily in service in accordance with requirements contained in applicable design documents was a performance deficiency. The performance deficiency was more than minor because it was associated with the equipment performance attribute of the Mitigating Systems Cornerstone and adversely affects the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The inspectors used the NRC Inspection Manual Chapter 0609, Attachment 4, Initial Characterization of Findings, to evaluate this issue. The finding required a detailed analysis because it involved a potential loss of a system function of safety related equipment. Therefore, the senior reactor analyst performed a bounding detailed risk evaluation. The analyst determined that the finding was of very low safety significance (Green). The bounding change to the core damage frequency was less than 4E-8/year. The finding was not significant with respect to the large early release frequency. The dominant core damage sequences included losses of offsite power, which result in an early loss of the instrument air compressors. The fact the accumulators would allow continued air operated valve operation for ten or more hours helped to reduce the risk. The inspectors concluded that the finding reflected current licensee performance and involved a cross-cutting aspect in the corrective action program component of the problem identification and resolution area in that the licensee did not thoroughly evaluate problems such that the resolutions address causes and extent of conditions, as necessary |
| Site: | Waterford |
|---|---|
| Report | IR 05000382/2013002 Section 1R22 |
| Date counted | Mar 31, 2013 (2013Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.22 |
| Inspectors (proximate) | M Davis D Allen J Melfi J Laughlin M Baquera |
| Violation of: | 10 CFR 50 Appendix B Criterion XI |
| CCA | P.2, Evaluation |
| INPO aspect | PI.2 |
| ' | |