04-14-2017 | On February 13, 2017, LaSalle County Station Unit 1 was in Mode 1 at 100 percent power and Unit 2 shut down for a planned refueling outage. At 2309 CST, a reactor scram signal was received on Unit 1 due to turbine control valves fast closure while the station was aligning back-feed operation to the Unit 2 main power transformer (MPT). The Unit 1 turbine trip was due to the main generator trip on differential current. The plant was placed in a stable condition with reactor pressure maintained by the turbine bypass valves and reactor water level controlled using feedwater. Unit 2 was unaffected by the event.
The root cause of the Unit 1 trip on differential current was a marginal generator differential relay design that was prone to responding to faults outside its zone of protection. Both units' 345 kV ring buses were connected together through the cross-tie bus, which allowed the Unit 1 generator to supply some of the electrical current that resulted in its differential circuit to create an unbalanced current that actuated the differential relay.
This event is reportable in accordance with 10 CFR 50.73(a)(2)(iv)(A) as an event or condition that resulted in manual or automatic actuation of the reactor protection system ( RPS), including reactor scram. There were no safety consequences associated with the event since RPS and other emergency safety systems functioned as designed. |
---|
|
---|
Category:Letter
MONTHYEARIR 05000373/20243012024-10-31031 October 2024 Initial License Examination Report 05000373/2024301 05000374/2024301 IR 05000373/20244042024-10-23023 October 2024 County Station – Security Baseline Inspection Report 05000373/2024404 and 05000374/2024404 RS-24-093, Response to Request for Additional Information - Alternative Request to Utilize Code Case OMN-32, Alternative Requirements for Range and Accuracy of Pressure, Flow, and Differential Pressure Instruments Used in Pump Tests2024-10-10010 October 2024 Response to Request for Additional Information - Alternative Request to Utilize Code Case OMN-32, Alternative Requirements for Range and Accuracy of Pressure, Flow, and Differential Pressure Instruments Used in Pump Tests 05000373/LER-2023-001-01, Air Circuit Breaker (Acb) Mechanically Operated Contacts (MOC) Switch Failed to Actuate2024-10-0909 October 2024 Air Circuit Breaker (Acb) Mechanically Operated Contacts (MOC) Switch Failed to Actuate ML24275A2442024-10-0303 October 2024 Reassignment of the U.S. Nuclear Regulatory Commission Branch Chief, Division of Operating Reactor Licensing IR 05000373/20244012024-09-27027 September 2024 County Station – Security Baseline Inspection Report 05000373/2024401 and 05000374/2024401 ML24263A2062024-09-19019 September 2024 Request for Exemption from Certain Requirements of 10 CFR 72.212 and 10 CFR 72.214 for LaSalle County Station - Holtec MPC-68MCBS ML24260A0492024-09-16016 September 2024 Operator Licensing Examination Approval - Lasalle County Station, Unit 1 and 2, September 2024 RS-24-090, Response to Request for Additional Information - Relief Request Concerning Extension of Permanent Relief from Ultrasonic Examination of Reactor Pressure Vessel Circumferential Shell Welds2024-09-12012 September 2024 Response to Request for Additional Information - Relief Request Concerning Extension of Permanent Relief from Ultrasonic Examination of Reactor Pressure Vessel Circumferential Shell Welds ML24255A8642024-09-0606 September 2024 Rscc Wire & Cable LLC Dba Marmon Industrial Energy & Infrastructure - Part 21 Retraction of Final Notification ML24249A1362024-09-0404 September 2024 EN 57304 - Westinghouse Electric Company, LLC, Final Report - No Embedded Files. Notification of the Potential Existence of Defects Pursuant to 10 CFR Part 21 IR 05000373/20240052024-08-29029 August 2024 Updated Inspection Plan and Assessment Follow-Up Letter for Lasalle County Station (Report 05000373/2024005; 05000374/2024005) IR 05000373/20244022024-08-28028 August 2024 County Station - Cyber Security Inspection Report 05000373/2024402 and 05000374/2024402 ML24239A3972024-08-23023 August 2024 Rssc Wire & Cable LLC Dba Marmon - Part 21 Final Notification - 57243-EN 57243 05000373/LER-2024-004-01, Emergency Diesel Generator Auto-Start and Load Due to Loss of System Auxiliary Transformer2024-08-22022 August 2024 Emergency Diesel Generator Auto-Start and Load Due to Loss of System Auxiliary Transformer IR 05000373/20240022024-08-13013 August 2024 County Station - Integrated Inspection Report 05000373/2024002 and 05000374/2024002 ML24222A6772024-08-0909 August 2024 Response to Request for Additional Information for Application to Revise Technical Specifications to Adopt TSTF-591-A, Revise Risk Informed Completion Time (RICT) Program Revision 0 and Revise 10 CFR 50.69 License Condition IR 05000373/20244202024-08-0505 August 2024 County Station - Security Baseline Inspection Report 05000373 2024420 and 05000374 2024420 05000373/LER-2024-003-01, Supplement to Technical Specification (TS) Limiting Condition for Operation (LCO) 3.6.1.3 Completion Time Exceeded2024-07-31031 July 2024 Supplement to Technical Specification (TS) Limiting Condition for Operation (LCO) 3.6.1.3 Completion Time Exceeded ML24208A0962024-07-25025 July 2024 57243-EN 57243 - Rssc Wire & Cable LLC, Dba Marmon - Part 21 Notification RS-24-064, Nuclear Radiological Emergency Plan Document Revisions2024-06-28028 June 2024 Nuclear Radiological Emergency Plan Document Revisions ML24178A2522024-06-27027 June 2024 County Station – Acknowledgement of Response to NRC Inspection Report 05000373/2024001 and 05000374/2024001 and Disputed Non-Cited Violation 05000373/LER-2024-004, Emergency Diesel Generator Auto-Start and Load Due to Loss of Station Auxiliary Transformer2024-06-19019 June 2024 Emergency Diesel Generator Auto-Start and Load Due to Loss of Station Auxiliary Transformer RS-24-061, Constellation Energy Generation, LLC, Response to NRC Regulatory Issue Summary 2024-01, Preparation and Scheduling of Operator Licensing Examinations2024-06-14014 June 2024 Constellation Energy Generation, LLC, Response to NRC Regulatory Issue Summary 2024-01, Preparation and Scheduling of Operator Licensing Examinations 05000373/LER-2024-003, Technical Specification (TS) Limiting Condition for Operation (LCO) 3.6.1.3 Completion Time Exceeded2024-06-0606 June 2024 Technical Specification (TS) Limiting Condition for Operation (LCO) 3.6.1.3 Completion Time Exceeded IR 05000373/20240102024-05-29029 May 2024 County Station - Commercial Grade Dedication Inspection Report 05000373/2024010 and 05000374/2024010 ML24079A0762024-05-23023 May 2024 Issuance of Amendments to Adopt TSTF 264 ML24142A3352024-05-21021 May 2024 Quad Cities—Information Request to Support the NRC Annual Baseline Emergency Action Level and Emergency Plan Changes RS-24-055, 2023 Corporate Regulatory Commitment Change Summary Report2024-05-17017 May 2024 2023 Corporate Regulatory Commitment Change Summary Report 05000373/LER-2024-002, Reactor Protection System Half Scram Due to Motor Generator Set Electric Power Monitoring Assembly Output Breaker Trip2024-05-17017 May 2024 Reactor Protection System Half Scram Due to Motor Generator Set Electric Power Monitoring Assembly Output Breaker Trip ML24131A1512024-05-13013 May 2024 County Station - Integrated Report 05000373/2024001 and 05000374/2024001 IR 05000373/20240012024-05-13013 May 2024 County Station - Integrated Report 05000373/2024001 and 05000374/2024001 RS-24-038, Relief Request Concerning Extension of Permanent Relief from Ultrasonic Examination of Reactor Pressure Vessel Circumferential Shell Welds2024-05-0202 May 2024 Relief Request Concerning Extension of Permanent Relief from Ultrasonic Examination of Reactor Pressure Vessel Circumferential Shell Welds RS-24-041, Alternative Request to Utilize Code Case OMN-32, Alternative Requirements for Range and Accuracy of Pressure, Flow, and Differential Pressure Instruments Used in Pump Tests2024-04-30030 April 2024 Alternative Request to Utilize Code Case OMN-32, Alternative Requirements for Range and Accuracy of Pressure, Flow, and Differential Pressure Instruments Used in Pump Tests 05000373/LER-2024-001, Core Operating Limits Report Thermal Limits Exceeded2024-04-26026 April 2024 Core Operating Limits Report Thermal Limits Exceeded ML24108A1562024-04-15015 April 2024 Updated Final Safety Analysis Report (Ufsar), Revision 26 and Fire Protection Report (Fpr), Revision 11 ML24103A2042024-04-12012 April 2024 Constellation Energy Generation, LLC, Application to Revise Technical Specifications to Adopt TSTF-591-A, Revise Risk Informed Completion Time (RICT) Program Revision 0 and Revise 10 CFR 50.69 License Condition RS-24-002, Constellation Energy Generation, LLC - Annual Property Insurance Status Report2024-04-0101 April 2024 Constellation Energy Generation, LLC - Annual Property Insurance Status Report ML24071A2122024-03-12012 March 2024 County Station - Information Request for the Cyber-Security Baseline Inspection, Notification to Perform Inspection IR 05000373/20230062024-02-28028 February 2024 Annual Assessment Letter for Lasalle County Station, Units 1 and 2 (Report 05000373/2023006; 05000374/2023006) RS-24-014, Annual 10 CFR 50.46 Report of Emergency Core Cooling System Evaluation Model Changes and Errors2024-02-22022 February 2024 Annual 10 CFR 50.46 Report of Emergency Core Cooling System Evaluation Model Changes and Errors ML24018A0682024-02-0909 February 2024 Issuance of Amendment Nos. 262 and 247 Revised Design Bases of Lower Downcomer Braces IR 05000373/20230042024-01-24024 January 2024 County Station - Integrated Inspection Report 05000373/2023004 and 05000374/2023004 ML24024A1332024-01-24024 January 2024 Confirmation of Initial License Examination IR 05000373/20230122024-01-18018 January 2024 County Station - Biennial Problem Identification and Resolution Inspection Report 05000373/2023012 and 05000374/2023012 ML23354A2902024-01-0505 January 2024 Exemption from Select Requirements of 10 CFR Part 73 (EPID L-2023-LLE-0028 (Security Notifications, Reports, and Recordkeeping and Suspicious Activity Reporting)) ML23360A6082023-12-27027 December 2023 County Station Request for Information for NRC Commercial Grade Dedication Inspection: Inspection Report 05000373/2024010 and 05000374/2024010 ML23278A1292023-12-14014 December 2023 Units 1 & 2; Limerick, Units 1 & 2; Nine Mile Point, Units 1 & 2; and Peach Bottom, Units 2 & 3 -Revision to Approved Alternatives to Use Boiling Water Reactor Vessel and Internals Project Guidelines ML23305A1402023-12-13013 December 2023 Units 1 & 2; Nine Mile Point, Unit 2; Peach Bottom, Units 2 & 3; and Quad Cities, Units 1 and 2 - Issuance of Amendments to Adopt Traveler TSTF-580 05000373/LER-2023-002, Turbine Stop Valve Limit Switch Failure Due to Lubricant Degradation2023-12-0404 December 2023 Turbine Stop Valve Limit Switch Failure Due to Lubricant Degradation 2024-09-06
[Table view] Category:Licensee Event Report (LER)
MONTHYEAR05000373/LER-2023-001-01, Air Circuit Breaker (Acb) Mechanically Operated Contacts (MOC) Switch Failed to Actuate2024-10-0909 October 2024 Air Circuit Breaker (Acb) Mechanically Operated Contacts (MOC) Switch Failed to Actuate 05000373/LER-2024-004-01, Emergency Diesel Generator Auto-Start and Load Due to Loss of System Auxiliary Transformer2024-08-22022 August 2024 Emergency Diesel Generator Auto-Start and Load Due to Loss of System Auxiliary Transformer 05000373/LER-2024-003-01, Supplement to Technical Specification (TS) Limiting Condition for Operation (LCO) 3.6.1.3 Completion Time Exceeded2024-07-31031 July 2024 Supplement to Technical Specification (TS) Limiting Condition for Operation (LCO) 3.6.1.3 Completion Time Exceeded 05000373/LER-2024-004, Emergency Diesel Generator Auto-Start and Load Due to Loss of Station Auxiliary Transformer2024-06-19019 June 2024 Emergency Diesel Generator Auto-Start and Load Due to Loss of Station Auxiliary Transformer 05000373/LER-2024-003, Technical Specification (TS) Limiting Condition for Operation (LCO) 3.6.1.3 Completion Time Exceeded2024-06-0606 June 2024 Technical Specification (TS) Limiting Condition for Operation (LCO) 3.6.1.3 Completion Time Exceeded 05000373/LER-2024-002, Reactor Protection System Half Scram Due to Motor Generator Set Electric Power Monitoring Assembly Output Breaker Trip2024-05-17017 May 2024 Reactor Protection System Half Scram Due to Motor Generator Set Electric Power Monitoring Assembly Output Breaker Trip 05000373/LER-2024-001, Core Operating Limits Report Thermal Limits Exceeded2024-04-26026 April 2024 Core Operating Limits Report Thermal Limits Exceeded 05000373/LER-2023-002, Turbine Stop Valve Limit Switch Failure Due to Lubricant Degradation2023-12-0404 December 2023 Turbine Stop Valve Limit Switch Failure Due to Lubricant Degradation 05000374/LER-2022-003-02, Manual Scram Due to Lsophase Bus Duct Fire Followed by 2A RPS Normal Power Supply Trip2023-06-16016 June 2023 Manual Scram Due to Lsophase Bus Duct Fire Followed by 2A RPS Normal Power Supply Trip 05000373/LER-2023-001, Low Pressure Core Spray Inoperable Due to Minimum Flow Valve Flow Pressure Switch Failure2023-06-16016 June 2023 Low Pressure Core Spray Inoperable Due to Minimum Flow Valve Flow Pressure Switch Failure 05000374/LER-2021-002-02, Supplement to Reactor Protection System Half Scram Due to Motor Generator Set Output Breaker Trip2023-05-25025 May 2023 Supplement to Reactor Protection System Half Scram Due to Motor Generator Set Output Breaker Trip 05000374/LER-2023-003, Automatic Actuation of Reactor Protection System (RPS) During Restoration from Hydrostatic Test Conditions I2023-05-0202 May 2023 Automatic Actuation of Reactor Protection System (RPS) During Restoration from Hydrostatic Test Conditions I 05000374/LER-2023-001, Standby Liquid Control Valve Inoperable Due to Failed Motor Starter Contactor2023-04-17017 April 2023 Standby Liquid Control Valve Inoperable Due to Failed Motor Starter Contactor 05000374/LER-1922-003-01, Manual Scram Due to Lsophase Bus Duct Fire Followed by 2A RPS Normal Power Supply Trip2023-02-0909 February 2023 Manual Scram Due to Lsophase Bus Duct Fire Followed by 2A RPS Normal Power Supply Trip 05000373/LER-2022-004, Both Trains of Main Control Room and Auxiliary Electric Room HVAC Declared Inoperable Due to Compressor Trips2022-12-28028 December 2022 Both Trains of Main Control Room and Auxiliary Electric Room HVAC Declared Inoperable Due to Compressor Trips 05000373/LER-2022-003-02, Supplement to Main Control Room and Auxiliary Electric Room HVAC Declared Inoperable Due to Multiple Component Failures2022-12-28028 December 2022 Supplement to Main Control Room and Auxiliary Electric Room HVAC Declared Inoperable Due to Multiple Component Failures 05000374/LER-2022-003, Manual Scram Due to Lsophase Bus Duct Fire and 2A RPS Normal Power Supply Trip2022-11-15015 November 2022 Manual Scram Due to Lsophase Bus Duct Fire and 2A RPS Normal Power Supply Trip 05000373/LER-2022-003-01, Main Control Room and Auxiliary Electric Room HVAC Declared Inoperable Due to Multiple Component Failures2022-09-23023 September 2022 Main Control Room and Auxiliary Electric Room HVAC Declared Inoperable Due to Multiple Component Failures 05000373/LER-2022-003, Main Control Room and Auxiliary Electric Room HVAC Declared Inoperable Due to Multiple Component Failures2022-07-18018 July 2022 Main Control Room and Auxiliary Electric Room HVAC Declared Inoperable Due to Multiple Component Failures 05000374/LER-2022-002, Turbine Stop Valve Limit Switch Failure Due to Lubricant Degradation2022-05-27027 May 2022 Turbine Stop Valve Limit Switch Failure Due to Lubricant Degradation 05000373/LER-2022-001, Turbine Stop Valve Limit Switch Failure Due to Lubricant Degradation2022-05-27027 May 2022 Turbine Stop Valve Limit Switch Failure Due to Lubricant Degradation 05000373/LER-2017-0072017-08-18018 August 2017 Low Pressure Core Spray System Inoperable due to Loss of Cooling, LER 17-007-00 for LaSalle County Station, Unit 1, Regarding Low Pressure Core Spray System Inoperable due to Loss of Cooling 05000374/LER-2017-0032017-08-0909 August 2017 High Pressure Core Spray System Inoperable due to Injection Valve Stem-Disc Separation, LER 17-003-01 for LaSalle County Station, Unit 2 Regarding High Pressure Core Spray System Inoperable due to Injection Valve Stem-Disc Separation 05000373/LER-2017-0062017-07-14014 July 2017 Low Pressure Core Spray Inoperable due to Minimum Flow Valve Failure in Closed Position, LER 17-006-00 for LaSalle, Unit 1, Regarding Low Pressure Core Spray Inoperable due to Minimum Flow Valve Failure in Closed Position 05000374/LER-2017-0042017-07-14014 July 2017 Two Main Steam Safety Relief Valves Failed Inservice Lift Inspection Pressure Test, LER 17-004-01 for LaSalle, Unit 2, Regarding Two Main Steam Safety Relief Valves Failed Inservice Lift Inspection Pressure Test 05000373/LER-2017-0052017-04-18018 April 2017 Manual Reactor Scram Resulting From Feedwater Regulating Valve Failure Causing High Reactor Water Level, LER 17-005-00 for LaSalle County, Unit 1, Regarding Manual Reactor Scram Resulting From Feedwater Regulating Valve Failure Causing High Reactor Water Level 05000373/LER-2017-0042017-04-17017 April 2017 Secondary Containment Inoperable Due to Interlock Doors Open, LER 17-004-00 for LaSalle County, Unit 1, Regarding Secondary Containment Inoperable Due to Interlock Doors Open 05000373/LER-2017-0032017-04-14014 April 2017 Automatic Reactor Scram due to Main Generator Trip on Differential Current During Back-Feed Operations, LER 17-003-00 for LaSalle County Station, Unit 1, Regarding Automatic Reactor Scram due to Main Generator Trip on Differential Current During Back-Feed Operations 05000374/LER-2017-0022017-03-30030 March 2017 High Pressure Core Spray System Declared Inoperable due to Cooling Water Strainer Backwash Valve Stem-Disc Separation, LER 17-002-00 for LaSalle, Unit 2, Regarding High Pressure Core Spray System Declared Inoperable due to Cooling Water Strainer Backwash Valve Stem-Disc Separation 05000374/LER-2017-0012017-03-24024 March 2017 Manual Reactor Scram due to Turbine-Generator Run-Back Caused by Stem-Disc Separation in Stator Water Cooling Heat Exchanger Inlet Valve, LER 17-001-00 for LaSalle County, Unit 2 Regarding Manual Reactor Scram due to Turbine-Generator Run-Back Caused by Stem-Disc Separation in Stator Water Cooling Heat Exchanger Inlet Valve 05000373/LER-2017-0012017-02-0808 February 2017 Reactor Core Isolation Cooling System Inoperable Longer than Allowed by the Technical Specifications due to Low Suction Pressure Trips, LER 17-001-00 for LaSalle County, Unit 1, Regarding Reactor Core Isolation Cooling System Inoperable Longer than Allowed by the Technical Specifications due to Low Suction Pressure Trips 05000374/LER-2016-0012016-04-18018 April 2016 Secondary Containment Inoperable Due to Interlock Doors Open, LER 16-001-00 for LaSalle County, Unit 2, Regarding Secondary Containment Inoperable Due to Door Interlock Doors Open 05000373/LER-2016-0012016-04-11011 April 2016 Secondary Containment Inoperable due to Reactor Building Ventilation Damper Failure, LER 16-001-00 for LaSalle County, Unit 1 & 2, Regarding Secondary Containment Inoperable Due to Reactor Building Ventilation Damper Failure 2024-08-22
[Table view] |
comments regarding burden estimate to the Information Services Branch (T-2 F43), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by e-mail to used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
- 00
PLANT AND SYSTEM IDENTIFICATION
LaSalle County Station Unit 1 is a General Electric Boiling Water Reactor with 3546 Megawatts Thermal Rated Core Power.
The affected system is the 345 kV switchyard. The switchyard consists of a ring-bus arrangement for each unit and a cross-tie bus that interconnects the units' ring buses. Each unit has a main power transformer (MPT), system auxiliary transformer (SAT), and a unit auxiliary transformer (UAT). Each of the two main generators is connected to two half-size main transformers and a UAT through isolated phase electrical bus ducts. The main power transformers step up the voltage, where power is delivered to the switchyard. The main generator and associated isolated phase bus duct is protected from electrical faults by several relaying features that will trip the generator to protect it from damage.
CONDITION PRIOR TO EVENT
Unit(s): 1 Reactor Mode(s): 1 Event Date: February 13, 2017 Event Time: 2309 CST Mode(s) Name: Power Operation Power Level: 100 percent
DESCRIPTION OF EVENT
On February 13, 2017, LaSalle County Station Unit 1 was in Mode 1 at 100 percent power, while Unit 2 was in a planned refueling outage. Unit 2 switchyard switching activities were in progress necessary to establish electrical back-feed power supply to the Unit 2 MPT. Switching activities included closing a main generator output breaker on Unit 2.
At 2309 hours0.0267 days <br />0.641 hours <br />0.00382 weeks <br />8.785745e-4 months <br /> CST, the Unit Imain generator received a trip on the 'B' phase differential current relay and subsequent main generator lock-out, which resulted in a Unit 1 automatic main turbine trip and subsequent Unit 1 automatic reactor scram due to fast closure of the turbine stop valves. In response to the event, one of the safety relief valves actuated in the relief mode upon the turbine trip and subsequently reset with tailpipe temperature returning to normal. The plant was in a stable condition with reactor pressure maintained by the turbine bypass valves. Reactor water level was controlled with feedwater, and all control rods fully inserted for the scram.
CAUSE OF EVENT
The root cause of the Unit 1 trip on differential current was a marginal generator differential relay design prone to responding to faults outside its zone of protection. Since both units' 345 kV ring buses are connected together through a cross-tie bus, this allowed the Unit 1 generator, which is the closest and strongest source, to supply some of the current and resulted in its differential circuit creating an unbalanced current that actuated the differential relay.
Contributing to this event was the current switchyard alignment methodology used for MPT back-feed operations. The current methodology challenges the margin of electro-mechanical differential current protective relays. An additional contributing cause was the use of larger transformers in place of the existing MPT, which changed the nature of the in-rush transient and introduced different current transformers into the differential relay scheme.
There has been operating experience regarding similar consequences related to similar differential relay scheme designs and related to transformer in-rush transients. Although some of this experience was recognized by the station and the corporate organization, the opportunity to change the back-feed switching scheme to mitigate the in-rush transient was missed.
0500073 2017
3. LER NUMBER
003 comments regarcing burden estimate to the Information Services Branch (T-2 F43), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by e-mail to used to impose an information collection does not dsplay a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
3. LER NUMBER 2. DOCKET NUMBER 0500073 - 00
REPORTABILITY AND SAFETY ANALYSIS
This event is reportable in accordance with 10 CFR 50.73(a)(2)(iv)(A) as an event or condition that resulted in manual or automatic actuation of the reactor protection system (RPS), including reactor scram. There were no safety consequences associated with the event since the RPS and other emergency safety systems functioned as designed.
CORRECTIVE ACTIONS
The immediate corrective action was to revise future switching orders to break the tie between the Unit 1 and Unit 2 345 kV ring buses when performing a back-feed to the MPT. The station also revised switching orders to isolate the Unit 1 and Unit 2 345 kV ring buses for energizing the SAT for each unit and performing generator synchronization operations.
The corrective action to prevent recurrence of a unit scram during back-feed operations is to install a more robust generator differential relay protection scheme. In addition, the switching scheme will be revised to break the tie between the Unit 1 and Unit 2 ring buses when the MPTs are energized.
PREVIOUS OCCURRENCES
A review of station Licensee Event Reports for the past three years related to reactor trips identified instances where a reactor manual or automatic scram was inserted. However, there were no previous occurrences related directly to main generator operation at the station. One event was identified related to turbine-generator run-back as follows.
- LER 374-2017-001-00, Manual Reactor Scram due to Turbine-Generator Run-Back Caused by Stem-Disc Separation in Stator Water Cooling Heat Exchanger Inlet Valve On January 23, 2017, operators initiated a manual scram of the Unit 2 reactor as a result of observing a generator run-back due to a generator stator winding cooling (GC) system malfunction. Inspections of the GC components were performed while the unit was shut down for a planned refueling outage. The cause of the GC system failure was stem-disc separation in the 'A' GC heat exchanger inlet valve. This event was reportable in accordance with 10 CFR 50.73(a)(2)(iv)(A) as an event or condition that resulted in manual or automatic actuation of the RPS. There were no safety consequences associated with the event since there was no loss of safety function, and the RPS functioned as designed.
COMPONENT FAILURE DATA
Manufacturer: General Electric Company [G080] Device: Main Generator Differential Current (CFD) Relay Trip Component ID: GE Model CFD Differential Relay 1687-MP010B 2017 003