05000373/FIN-2017004-04
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure of Offsite Power Backfeed Procedure to be Appropriate to the Circumstances Caused Unit 1 Scram |
| Description | A finding of very low safety significance and an associated NCV of LaSalle Technical Specification (TS) 5.4.1, Procedures, occurred on February 13, 2017, for the stations failure to maintain instructions of a type appropriate to the circumstances for energizing offsite electrical systems during a Unit 2 backfeed evolution (an activity affecting quality per Regulatory Guide 1.33). Specifically, the steps of backfeed procedure, LOPAP01, Revision 35, led to a Unit 1 scram because the prescribed switchyard configuration left both units connected to the 345 kilovolt (kv) ring bus, leaving the operating unit susceptible to the large in-rush current induced by the backfeed energization of the Unit 2 main power transformer. As a corrective action from Action Request (AR) 03973724, the licensee revised the backfeed procedure to eliminate the tie between the units on the ring bus when main power transformers are energized. This performance deficiency was more than minor because it was associated with the Procedure Quality attribute of the Initiating Events Cornerstone, and adversely affected the Cornerstone objective of limiting the likelihood of events that upset plant stability because it resulted in a Unit 1 Scram. In accordance with IMC 0609.04, Initial Characterization of Findings, and Exhibit 1 of IMC 0609, Appendix A, The Significance Determination Process for Findings At Power, issued June 19, 2012, the inspectors determined that this finding was of very low safety significance because, although the performance deficiency caused a reactor scram, it did not result in the loss of mitigation equipment relied upon to transition the plant from the onset of the scram to a stable shutdown condition. The inspectors determined there was no cross-cutting aspect because the performance deficiency was not indicative of licensees current performance since the design modification occurred greater than 3 years before the event. This inspection report will also bring to closure the associated Licensee Event Report, (LER) 05000373/201700300. |
| Site: | LaSalle |
|---|---|
| Report | IR 05000373/2017004 Section 4OA3 |
| Date counted | Dec 31, 2017 (2017Q4) |
| Type: | NCV: Green |
| cornerstone | Initiating Events |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71153 |
| Inspectors (proximate) | R Ruiz J Havertape J Bozga J Neurauter L Smith C Zoia M Bielby G Hansen R Zuffa B Dickson |
| Violation of: | Technical Specification - Procedures |
| INPO aspect | |
| ' | |