05000373/FIN-2016004-03
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Perform Preventive Maintenance Resulting in Two Subsequent Unit 1 RCIC Turbine Trips During Surveillance Testing |
Description | A finding of very low safety significance with an associated NCV of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, was self-revealed when the licensee failed to perform preventive maintenance on the Unit 1 reactor core isolation cooling (RCIC) electronic governor-remote (EGR) actuator. Specifically, from June 4, 1993, to November 17, 2016, the licensees processes for the control and administration of preventive maintenance failed to ensure that the Unit 1 RCIC EGR actuator was replaced or refurbished on an interval that would prevent internal fouling of the EGR actuator from adversely affecting governor performance. As a result, contaminates and degradation accumulated in the EGR actuator from January 16, 2004, to November 17, 2016, ultimately causing the RCIC turbine to trip during quarterly surveillance testing on October 18, 2016, and again on November 17, 2016. The licensee entered this issue into the CAP as ARs 02729757 and 02742254. Corrective actions planned and completed included replacing the Unit 1 and Unit 2 RCIC EGRs and performing a root cause evaluation of the degraded condition. The performance deficiency was more than minor, and thus a finding because it was associated with the Mitigating Systems cornerstone attribute of equipment performance and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences (i.e., core damage). Specifically, the failure to perform preventive maintenance on the Unit 1 RCIC EGR resulted in a degraded condition which adversely affected the reliability of the system to respond to an initiating event. A detailed risk evaluation determined that the finding screened as having very low safety significance (Green). This finding did not have a cross-cutting aspect because the performance deficiency was not indicative of current licensee performance. |
Site: | LaSalle |
---|---|
Report | IR 05000373/2016004 Section 4OA2 |
Date counted | Dec 31, 2016 (2016Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Self-revealing |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | B Palagi C Hunt G Hansen J Neurauter K Stoedter R Ng R Ruiz R Zuffa T Ospino V Meghani W Schaupr Ruizc Phillips C Hunt J Wojewoda W Schaup I Hafeez D Sargis J Cassidy R Zuffa K Stoedter |
Violation of: | 10 CFR 50 Appendix B 10 CFR 50 Appendix B Criterion V |