05000335/FIN-2013007-04
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Penetration Seals Outside Appendix R Requirements |
Description | On October 17, 2007, during the course of walkdowns being performed to evaluate internal conduit fire seals, the licensee identified three cable spreading room (CSR) floor penetrations which had not been installed or evaluated in accordance with 3-hour fire rating design details. The licensee generated AR 00479446 to track resolution of this issue in its CAP and submitted LER 05000335/2007-003-00. Region II fire protection inspectors performed a detailed review of the information related to this LER. The inspectors performed in-office reviews of licensee documents and analyses, performed onsite walkdowns, and discussed the event with plant personnel to verify the qualification of the fire penetration seals installed in the CSR. The inspectors assessed the licensees compensatory measures and corrective actions to ensure that they adequately restored compliance. The inspectors also evaluated the significance of degraded fire barriers that contained penetration seal configurations that did not meet regulatory requirements. The following finding was identified by the licensee and is a violation of NRC requirements. This finding has been screened and determined to warrant enforcement discretion per the Interim Enforcement Policy Regarding Enforcement Discretion for Certain Fire Protection Issues (10 CFR 50.48). This LER is closed. |
Site: | Saint Lucie |
---|---|
Report | IR 05000335/2013007 Section 4OA3 |
Date counted | Mar 31, 2013 (2013Q1) |
Type: | Violation: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71153 |
Inspectors (proximate) | M King M Thomas G Wiseman K Ellis T Fanelli M Singletary |
Violation of: | 10 CFR 50.48 |
INPO aspect | |
' | |
Finding - Saint Lucie - IR 05000335/2013007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Saint Lucie) @ 2013Q1