Abstract
OnSeptember14,2022,withUnit2inMode5(ColdShutdown)duringcooldownforamaintenanceoutage, OperationscommencedperformanceofOI342,Section6.8/AppendixJ,BypassingSIASandSIASBlockSensor ModulesinMode5,6,orDefueled,insupportofOP052,PlantShutdownfromHotStandbytoColdShutdown.During performanceoftheOI342evolution,anunplannedSafetyInjectionActuationSignal(SIAS)occurredduetoOperator failuretocomplywithstationprocedureuseandadherencestandards.TheunplannedSIASresultedintheautomatic startofthesites2ADieselGenerator(DG)and2BDG.TheunplannedSIASdidnotresultinsafetyinjectionintothe reactorcoolantsystemnordiditadverselyimpactshutdowncoolingoperations.
(See Page 3 for required number of digits/characters for each block)
(See NUREG-1022, R.3 for instruction and guidance for completing this form http://www.nrc.gov/reading-rm/doc-collections/nuregs/staff/sr1022/r3/)
Page 5 of 5 SafetyImpact
Thesafetysignificanceofthiseventwasminimal.Atthetimeoftheevent,Unit2wasinMode5andtheHPSILTOP tagoutwasinplace,preventingtheinjectionofhighpressuremakeupintothereactorcoolantsystemwhileinalow temperaturecondition.BothLPSIPumpswerealreadyinoperationprovidingcoolingflowviatheSDCsystem.SDC operationwasnotadverselyimpactedbytheunplannedSIAS.AlthoughbothUnit2dieselgenerators,the2ADGand 2BDG,receivedautomaticstartsignalsfromtheunplannedSIASAandB,sincetherewasnolossofeitherthe214KV Bus(safetyrelatedZAtrainbussupportedbythe2ADG)orthe244KVBus(safetyrelatedZBtrainbussupportedby the2BDG),neitherofthedieselgeneratorsloadedontotheirrespectivebus.Followingtheautomaticstartofthe2A DGand2BDG,bothdieselgeneratorsoperatedsatisfactorilyuntilsecured.
F.CORRECTIVEACTIONS
TheCAPproductperformedunderIR4522477identifiedthefollowingcorrectiveactionsthatareplannedtobetaken toaddresscauseandextentofconditionfromtheeventinvestigation:
(1)PerformedaCorrectiveActionProgramevaluation.
(2)AddressedpersonnelaccountabilityactionsinaccordancewithHumanResourcepolicies.
(3)ReviseapplicableESFAS/AuxiliaryFeedwaterActuationSystem(AFAS)procedurestoclearlydelineate supervisoryoversightwhileperformingthetasks.
G.PREVIOUSOCCURRENCES
AreviewofCalvertCliffsreportableeventsbacktoJanuary2012wasperformed.TherewerenoLERsthatinvolved unplannedESFASactuationsastheresultofpersonnelerrors.
LER3182021004,Unit2ManualReactorTripDuetoLoweringSteamGeneratorLevels,doesdocumentaUnit2 manualreactortripthatwasinitiatedbyapersonnelerrorwhenbreakerstabcoverswerenotremovedpriorto attemptingtoenergizethe12SpentFuelPoolCoolingPump(SFPCP).Uponattemptingtoenergizethe12SFPCP,an arcflasheventoccurredthatresultedinthelossofthe24A480VLoadCenterthatledultimatelytotheneedfor OperationstomanuallytriptheUnit2reactor.
H.COMPONENTFAILUREDATA
Therewerenocomponentfailuresidentifiedthatcontributedtothiseventoroccurredasaresultofthisevent.