Finding | |
|---|---|
| Title | Failure to Implement and Maintain Surveillance Procedures Associated with Fire Barrier and Penetration Seal Inspections |
| Description | The inspectors identified a non-cited violation (NCV) of Calvert Cliffs Renewed Facility Operating License Numbers DPR-53 and DPR-54, License Condition 2. E, because Constellation did not adequately implement and maintain surveillance procedures associated with fire barrier and penetration seal inspections. As a result, Constellation did not identify degraded conditions associated with one fire barrier and three penetration seals. Immediate actions taken included entering the appropriate Technical Requirement Manual (TRM) action statement, establishing an hourly fire tour until temporary repairs were completed, and entering each issue into their corrective action program (CAP) for resolution. The finding is more than minor because it was associated with the external factors attribute (i.e. fire) of the Mitigating Systems cornerstone and affected the cornerstone objective to ensure availability, reliability, and capability of systems that respond to initiation events to prevent undesirable consequences. Specifically, the degraded conditions had to be repaired or evaluated to ensure that the barriers/penetrations would meet their design function. In addition, if left uncorrected, the finding could result in a more significant safety concern in that that the condition could continue to degrade such that the barriers/penetrations could no longer perform their specified function and/or result in the inability of Constellation to recognize additional degraded fire barriers/penetrations. The inspectors determined that the finding is of very low safety significance because there was a non-degraded automatic full area water based fire suppression system in the exposing fire area. This finding has a crosscutting aspect in the area of human performance because Constellation did not define and effectively communicate expectations regarding procedural compliance and personnel following procedures for fire penetration seal inspections (H.4.b of IMC 0310) |
| Site: | Calvert Cliffs |
|---|---|
| Report | IR 05000317/2010002 Section 1R05 |
| Date counted | Mar 31, 2010 (2010Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | M Davis M Modes J Schoppy D Johnson G Dentel S Kennedy R Rolph J Montgomery J Hawkins |
| CCA | H.8, Procedure Adherence |
| INPO aspect | WP.4 |
| ' | |