( SMU2 SACRAMENTO MUNICIPAL UTILITY DISTRICT O 6201 S Street, Box 15830, Sacramento, California 95813; (916) 452-3211 August 17, 1981

~

i

?

- l0 gQ

' r!

R H ENGELKEN, DIRECTOR REGION V 0FFICE OF INSPECTION & ENFORCEMENT 4* W, iQ:,

i[i U S NUCLEAR REGULATOP,Y COMMISSION 1990 N CALIFORNIA BLVD h

% j

.Np WALNUT CREEK PLAZA, SUITE 202 g

A WALNt'T CREEK CA 94596 j

(F Q

!?

's M'

Y DOCKET NO. 50-312

'Q g

s Ll CENSE NO. DPR-54 g-REPORTABLE OCCURRENCE 81-35, REVISION 1 O

in accordance with Technical Specification Section 6.9.4.2.b, and in response to a request from H. Canter, the Sacramento Municipal Utility District hereby submits Revision 1 of the thirty-day report of Reportable Occurrence 81-35 On June 25, performance of SP 206.03A, Diesel Generator A Synchronization Test, on Diesel Generator G886A, re.vealed unstable operation caused by low governor oil level. Oil was added and the generator operated p rope rl y.

The low oil level was apparent'y caused by a slow leak, as no significant spilled oil was found.

Operations has added an item to their shift surveil ?ance to check the governor oil level. The gove rnor, a Woodward model EG-B 13C, will be replaced by the end of the next refueling.

is a General Motors Electromotive Division, model 645E4.

The generator There were nc transients or power reductions associated with this event.