05000271/LER-2007-002, High Pressure Coolant Injection (HPCI) System Valve Failed to Open

From kanterella
(Redirected from 05000271/LER-2007-002)
Jump to navigation Jump to search
High Pressure Coolant Injection (HPCI) System Valve Failed to Open
ML072250028
Person / Time
Site: Vermont Yankee File:NorthStar Vermont Yankee icon.png
(DPR-028)
Issue date: 08/06/2007
From: Ted Sullivan
Entergy Nuclear Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
BVY 07-048 LER 07-002-00
Download: ML072250028 (5)


LER-2007-002, High Pressure Coolant Injection (HPCI) System Valve Failed to Open
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
2712007002R00 - NRC Website

text

Enter~gy Entergy Nuclear Operations, Inc.

Vermont Yankee P.O. Box 0500 185 Old Ferry Road Brattleboro, VT 05302-0500 Tel 802 257 5271 August 6, 2007 BVY 07-048 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555

Subject:

Vermont Yankee Nuclear Power Station License No. DPR-28 Docket Number: 05000271 Reportable Occurrence Number: LER 2007-002-00

Dear Sir or Madam,

As defined by 10 CFR 50.73(a)(2)(v)(D), we are submitting the attached Licensee Event Report, LER 2007-002-00, for a Reportable Occurrence that was discovered on June 8, 2007.

There are no regulatory commitments contained within this correspondence.

Sincerely,siden Vermont Yankee Nuclear Power Station cc:

USNRC Region I Administrator USNRC Resident Inspector - VYNPS USNRC Project Manager - VYNPS Vermont Department of Public Service

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPIRES: 06/30/2007 (6-2004)

, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

3. PAGE VERMONT YANKEE NUCLEAR POWER STATION (VY) 05000 271 1 OF 4
4. TITLE High Pressure Coolant Injection (HPCI) System Valve Failed to Open
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED FACILITY NAME DOCKET NUMBER SEQUENTIAL REV MONTH DAY YEAR N/A NUMBER NO.

FACILITY NAME DOCKET NUMBER 06 08 2007 2007 002 00 08 02 2007 N/A

9. OPERATING MODE
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §: (Check all that apply) o 20.2201(b) 5 20.2203(a)(3)(i)

[]

50.73(a)(2)(i)(C)

E] 50.73(a)(2)(vii)

N 5 20.2201(d) 5 20.2203(a)(3)(ii)

E] 50.73(a)(2)(ii)(A)

[]

50.73(a)(2)(viii)(A)

El 20.2203(a)(1) 5 20.2203(a)(4) 5 50.73(a)(2)(ii)(B)

E] 50.73(a)(2)(viii)(B)

[]

20.2203(a)(2)(i) 5 50.36(c)(1)(i)(A) 5 50.73(a)(2)(iii) 5 50.73(a)(2)(ix)(A)

10. POWER LEVEL jJ 20.2203(a)(2)(ii) 5 50.36(c)(1)(ii)(A) 5 50.73(a)(2)(iv)(A) 5 50.73(a)(2)(x)

EO 20.2203(a)(2)(iii)

E] 50.36(c)(2) 5 50.73(a)(2)(v)(A)

E] 73.71 (a)(4) 81 5 20.2203(a)(2)(iv)

C] 50.46(a)(3)(ii) 5] 50,73(a)(2)(v)(B)

E] 73.71(a)(5)

O 20.2203(a)(2)(v) 5 50.73(a)(2)(i)(A) 5 50.73(a)(2)(v)(C) 5 OTHER E] 20.2203(a)(2)(vi) 1] 50.73(a)(2)(i)(B) 2] 50.73(a)(2)(v)(D)

Specify in Abstract below or in It was determined that the V23-19 Close Contactor failed at the last closure evolution performed by Operations during the valve lineup. The 72/C contacts close to power the valve motor in the shut direction. When the valve is fully closed, a torque switch removes power from the contactor relay, allowing the contactor to spring back to its normally open position. The contactor had not fully returned to the normal de-energized position because its contacts had excessively arced and were fused together. The Close Contactor does not energize during an open signal to the valve. The Close Contactor failed in a manner such that the interlock prevented the Open Contactor from actuating. This is part of the MOV design to prevent both contactors from closing at the same time.

Prior to implementing the corrective actions developed by the Root Cause Analysis Team, the contactors were inspected at 6 year intervals and replaced when signs of degradation such as pitting were present. The contactors will continue to be inspected at 6 year intervals and as a result of corrective actions created to prevent recurrence of this event, the contactors will be replaced, regardless of condition, at 18 year intervals (during the third 6 year inspection interval).

CAUSE

Root Cause:

The Root Cause Team identified that the Preventative Maintenance required to be performed on the V23-19 valve's motor operator control circuitry was not fully effective for the application. A time-based replacement of these contactors would have prevented this event. No Human Performance items for this event were identified by the Root Cause Team.

Additionally, it was determined that procedural guidance for the V23-19 control circuitry inspection requires enhancement. Specifically, the inspection procedure did not contain adequate guidance for determining contact wear.

ASSESSMENT OF SAFETY CONSEQUENCES

The HPCI system is designed to supply high pressure coolant to the reactor core, to prevent excessive fuel clad temperatures, in the event of a small-break loss of coolant accident (LOCA) that does not result in a rapid depressurization of the reactor vessel and can supply reactor makeup during periods when the Feedwater System is isolated or otherwise unavailable. The failure of V23-19 to open would have prevented the HPCI system from performing the design safety functions listed above.

During the period of HPCI system unavailability, the Reactor Core Isolation Cooling System (RCIC), the Automatic Depressurization System (ADS), Core Spray System, and the Low Pressure Coolant Injection Systems (LPCI) were verified operable as required by Technical Specification 3.5.E.2. The Technical Specification HPCI LCO period of 14 days was not exceeded from the date that the valve was successfully operated to that date when repairs were complete. Technical Specification 3.5.E.1 requires the HPCI system to be operable whenever irradiated fuel is in the vessel (RPV) and reactor steam pressure is greater than 150 psig.

An evaluation has determined that this event did not constitute a significant increase in risk. It is conservatively assumed that HPCI was out of service at the time during reactor startup when RPV pressure reached 150 psig on 06/06/07 0243, and was returned to service on 06/12/07 at 1626 following successful Preventative Maintenance Testing. The interval of time that HPCI was unavailable while RPV pressure was above 150 psig was therefore 158 hours0.00183 days <br />0.0439 hours <br />2.612434e-4 weeks <br />6.0119e-5 months <br />. The Core Damage Frequency (CDF) with HPCI unavailable is 2.93E-5/Ry (Ry = Reactor Year), and the base CDF (zero-maintenance) is 3.03E-6/Ry. The Incremental Core Damage Probability (ICDP) associated with this event is 4.73E-7/Ry, which is lower than the ICDP significance threshold of 1.OE-06/Ry.

CORRECTIVE ACTIONS

Immediate Actions

1) Plant Operators entered 14 day HPCI System LCO and verified that the RCIC, ADS, Core Spray, and LPCI Systems were available.
2) Notified the NRC per per 10 CFR 50.72(b)(3)(v)(D) and performed a risk assessment using ORAM-Sentinel.
3) Electrical Maintenance and Engineering commenced trouble-shooting activities, V23-19 control circuitry was repaired and the HPCI system was returned to a fully operable status.

Corrective Actions to Prevent Recurrence (CAPR)

1) A Preventative Maintenance Change Request (PMCR) was initiated and assigned to System Engineering to enhance the Preventative Maintenance Basis by increasing the frequency for the replacement of MOV Heavy Loaded DC contactors to an 18 year interval.
2) On a priority basis, replace contactors in DC MOVs with highly loaded (current) contactors that are greater than 18 years old.
3) Develop a preventative maintenance schedule, based upon contactor size and safety significance for inspection and evaluation of the condition of DC contactors.

Long Term Corrective Actions

1) Revise procedure OP-5210, "MCC Inspections", to provide criteria for determining contact wear and replacement.

ADDITIONAL INFORMATION

No similar events have occurred at VY within the past ten years.

N