05000260/LER-2005-006, Re Low Voltage on Shutdown Battery Cells Results in Condition Prohibited by Technical Specifications

From kanterella
(Redirected from 05000260/LER-2005-006)
Jump to navigation Jump to search
Re Low Voltage on Shutdown Battery Cells Results in Condition Prohibited by Technical Specifications
ML052630154
Person / Time
Site: Browns Ferry Tennessee Valley Authority icon.png
Issue date: 09/19/2005
From: O'Grady B
Tennessee Valley Authority
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
LER 05-006-00
Download: ML052630154 (9)


LER-2005-006, Re Low Voltage on Shutdown Battery Cells Results in Condition Prohibited by Technical Specifications
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications

10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function
2602005006R00 - NRC Website

text

September 19, 2005 U.S. Nuclear Regulatory Commission 10 CFR 50.73 ATTN: Document Control Desk Mail Stop OWFN, P1-35 Washington, D. C. 20555-0001

Dear Sir:

TENNESSEE VALLEY AUTHORITY - BROWNS FERRY NUCLEAR PLANT (BFN) -

UNIT 2 - DOCKET 50-260 - FACILITY OPERATING LICENSE DPR LICENSEE EVENT REPORT 50-260/2005-006-00 The enclosed report provides details of a plant condition which involved low voltage readings measured during the conduct of a surveillance test on two battery cells on a 4-kV Shutdown Board Battery. At the time, a second direct current subsystem was inoperable due to scheduled maintenance activities. This resulted in an entry into Limiting Condition for Operation 3.0.3 for a short period of time.

In accordance with 10 CFR 50.73(a)(2)(i)(B), TVA is reporting this event as condition prohibited by Technical Specifications.

There are no commitments contained in this letter.

Sincerely, Original signed by:

Brian OGrady cc: See page 2

U.S. Nuclear Regulatory Commission Page 2 September 19, 2005 Enclosure cc (Enclosure):

Ms. Eva Brown, Project Manager U.S. Nuclear Regulatory Commission (MS 08G9)

One White Flint, North 11555 Rockville Pike Rockville, Maryland 20852-2739 Mr. Stephen J. Cahill, Branch Chief U.S. Nuclear Regulatory Commission Region II Sam Nunn Atlanta Federal Center 61 Forsyth Street, SW, Suite 23T85 Atlanta, Georgia 30303-8931 NRC Resident Inspector Browns Ferry Nuclear Plant 10833 Shaw Road Athens, Alabama 35611-6970

U.S. Nuclear Regulatory Commission Page 3 September 19, 2005 WDC:DTL:BCM:BAB Enclosure cc (Enclosure):

B. M. Aukland, POB 2C-BFN A. S. Bhatnagar, LP 6A-C J. C. Fornicola, LP 6A-C R. G. Jones, NAB 1A-BFN R. F. Marks, PAB 1C-BFN G. W. Morris, BR 4X-C N. M. Moon, LP 6A-C J. R. Rupert, NAB 1A-BFN K. W. Singer, LP 6A-C E. J. Vigluicci, ET 11A-K LEREvents@inpo.org NSRB Support, LP 5M-C EDMS WT CA - K S:lic/submit/lers/260/2005-006 battery.doc

NRC FORM 366 (2004)

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION (6-2004)

LICENSEE EVENT REPORT (LER)

(See reverse for required number of digits/characters for each block)

APPROVED BY OMB NO. 3150-0104 EXPIRES 06/30/2007

, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

1. FACILITY NAME Browns Ferry Unit 2
2. DOCKET NUMBER 05000260
3. PAGE 1 OF 6
4. TITLE Low Voltage on Shutdown Battery Cells Results in Condition Prohibited By Technical Specifications
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED MONTH DAY YEAR YEAR SEQUENTIAL NUMBER REV NO.

MONTH DAY YEAR FACILITY NAME U3 DOCKET NUMBER 05000296 07 22 2005 2005-006-00 09 19 2005 FACILITY NAME none DOCKET NUMBER N/A

11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §:(Check all that apply)
9. OPERATING MODE 1

20.2201(b) 20.2203(a)(3)(i) 50.73(a)(2)(i)(C) 50.73(a)(2)(vii) 20.2201(d) 20.2203(a)(3)(ii) 50.73(a)(2)(ii)(A) 50.73(a)(2)(viii)(A) 20.2203(a)(1) 20.2203(a)(4) 50.73(a)(2)(ii)(B) 50.73(a)(2)(viii)(B) 20.2203(a)(2)(i) 50.36(c)(1)(i)(A) 50.73(a)(2)(iii) 50.73(a)(2)(ix)(A) 20.2203(a)(2)(ii) 50.36(c)(1)(ii)(A) 50.73(a)(2)(iv)(A) 50.73(a)(2)(x) 20.2203(a)(2)(iii) 50.36(c)(2) 50.73(a)(2)(v)(A) 73.71(a)(4) 20.2203(a)(2)(iv) 50.46(a)(3)(ii) 50.73(a)(2)(v)(B) 73.71(a)(5) 20.2203(a)(2)(v) 50.73(a)(2)(i)(A) 50.73(a)(2)(v)(C)

OTHER

10. POWER LEVEL 100 20.2203(a)(2)(vi)

X 50.73(a)(2)(i)(B) 50.73(a)(2)(v)(D) specify in Abstract below or in (If more space is required, use additional copies of (If more space is required, use additional copies of (If more space is required, use additional copies of (If more space is required, use additional copies of NRC Form 366A) (17) (1) TVA does not consider these corrective actions regulatory commitments. The completion of these actions will be tracked in TVAs Corrective Action Program.

C.

Additional Information

Browns Ferry corrective action document PER 85316.

D.

Safety System Functional Failure Consideration:

This event does not involve a safety system functional failure which would be reported in accordance with NEI 99-02. Although two individual SB-A cells measured low voltage, the battery capacity remained such that it would have performed its design function.

E.

Loss of Normal Heat Removal Consideration:

N/A. This condition being reported did not involve a reactor scram.

VIII. COMMITMENTS

None