| Title | Control Room HVAC Rcu Head Bolts Not Torqued |
| Description | \
A self-revealed finding of very low safety significance (Green) and associated NCV of TS 5.4.1.a was identified for the licensees failure to specify torque values for the control room ventilation refrigeration condensing unit condenser head in the work instructions performed on January 19, 2012. The inspectors identified that this issue had a cross-cutting aspect in the area of Human Performance - Decision Making (H.1(b)). Inspectors determined that a contributor to this finding was that the Maintenance and Engineering Departments did not verify the assumptions or identify unintended consequences with possible variance in the interpretation and implementation of work instructions stating, tighten bolts using a crisscross pattern and good mechanical judgment, vice specifying a torque value from MA-MW-736-600. Although this work practice had been in place for years, mechanics questioned the lack of a torque value during the post leak repair to restore operability. Engineering replied with mechanical judgment rather than specifying a torque value indicating that the practice was indicative of current performance. The heat exchanger leak was repaired and the head reassembled with nominal torque values. The performance deficiency was more than minor because the performance deficiency, if left uncorrected, had the potential to lead to a more significant event. The inspectors performed an SDP Phase 1 screening for the finding using IMC 0609, Attachment 04, Initial Characterization of Findings, and IMC 0609, Appendix A, Exhibit 2, Mitigating Systems Screening Questions, and answered the first four questions No. Therefore, the finding screened as very low safety significance, or Green. |
| Site: | Quad Cities |
|---|---|
| Report | IR 05000254/2012004 Section 1R19 |
| Date counted | Sep 30, 2012 (2012Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71111.19 |
| Inspectors (proximate) | M Ring D Jones L Haeg J Mcghee B Cushman J Draper L Jones C Mathews |
| CCA | H.14, Conservative Bias |
| INPO aspect | DM.2 |
| ' | |
Finding - Quad Cities - IR 05000254/2012004 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Quad Cities) @ 2012Q3
Self-Identified List (Quad Cities)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||