05000244/LER-2007-001, Regarding Loss of Electrical Generation Results in Plant Trip

From kanterella
(Redirected from 05000244/LER-2007-001)
Jump to navigation Jump to search
Regarding Loss of Electrical Generation Results in Plant Trip
ML071310387
Person / Time
Site: Ginna 
Issue date: 03/23/2007
From: Korsnick M
Constellation Energy Group, Ginna
To:
Document Control Desk, Plant Licensing Branch III-2
References
LER 07-001-00
Download: ML071310387 (8)


LER-2007-001, Regarding Loss of Electrical Generation Results in Plant Trip
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
2442007001R00 - NRC Website

text

Maria Korsnick Site Vice President Constellation Energy-Generation Group Des-goea % f1A R.E. Ginna Nuclear Power Plant, LLC 1503 Lake Road Ontario, New York 14619-9364 585.771.5200 585.771.3943 Fax mada.korsnick@constellation.com March 23, 2007 U.S. Nuclear Regulatory Commission Washington, DC 20555 ATTENTION:

SUBJECT:

Document Control Desk R.E. Ginna Nuclear Power Plant Docket No. 50-244 LER 2007-001, Loss of Electrical Generation Results in Plant Trip The attached Licensee Event Report (LER) 2007-001 is submitted in accordance with 10 CFR 50.73, Licensee Event Report System. There are no new commitments contained in this submittal. Should you have questions regarding the information in this submittal, please contact Mr. Robert Randall at (585) 771-5219 or robert.randall@constellation.com.

Very truly yours, Mary G.orsnick Attachments: (1)

LER 2007-001 cc:

S. J. Collins, NRC D. V. Pickett, NRC Resident Inspector, NRC (Ginna)

ývf DC P~t

,1/11/07 I,,

LER 2007-001 Loss of Electrical Generation Results in Plant Trip

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPIRES: O0&M07 the NnC may not conduct digits/characters for each block) or sponsor, and a person Is not required to respond to. the Information atesfo ac lok collection.

3. PAGE R.E. Ginna Nuclear Power Plant 05000244 1 OF 6
4. TITLE Loss of Electrical Generation Results In Plant Trip
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE S. OTHER FACILITIES INVOLVED MONTH DAY YEAR YEAR SEQUENTIAL REV MONTH DAY YEAR 05000 J -

NUMBER NO.

050 01 27 2007 2007 - 001 -

00 -

3 23 2007 1___°_____u___

05000

9. OPERATING MODE
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR§: (Check all that apply) o3 20.22011(b)

[3 20.2203(a)(3)(il 13 50.73(a)(2)(I)(C)

[3 50.73(a)(2)(vil) 13 20.2201(d)

[3 20.2203(a)(3)(ii) 13 50.73(a)(2)(i)(A)

[] 50.73(a)(2)(vill)(A)

[3 20.2203(a)(1) 03 20.2203(a)(4)

[3 50.73(a)(2)(ii)(B)

[3 50.73(a)(2)(vll)(B) o 20.2203(a)(2)(1)

[3 50.36(c)(1)(i(A) 0 50.73(a)(2)(Ri)

[3 50.73(a){2)(Ix)(A)

10. POWER LEVEL 0

20.2203(a)(2)(ii) 03 50.36(c)(1)(ii)(A) 0 50.73(a)(2)(iv)(A)

[3 50.73(a)(2)(x)

ER 20.2203(a)(2)(iil)

[l 50.36(c)(2)

[3 50.73(a)(2)(v)(A)

[3 73.71 (a)(4) o 20.2203(a)(2)(iv)

G 50.46(a)(3)(Ii)

[0 50.73(a)(2)(v)(B)

[] 73.71 (a)(5) 100 [3 20.2203(a)(2)(v) 0 50.73(a)(2)(I)(A)

[3 50.73(a)(2)(v)(C)

[0 OTHER [o 20.2203(a)(2)(vO) 0 50.73(a)(2)(i)(B)

[] 50.73(a)(2)(v)(D)

Specify in Abstract below or In (If more space Is required, use additional copies of (if more space Is required, use additional copies of O7f more space is required, use additional coples of (If more space is required, use additional copies of (If more space Is required, use additional coples of NRC Form 365A)

B.

PREVIOUS LERs ON SIMILAR EVENTS:

A similar Ginna LER event historical search was conducted which resulted In no similar events.

C.

THE ENERGY INDUSTRY IDENTIFICATION SYSTEM (EIIS) COMPONENT FUNCTION IDENTIFIER AND SYSTEM NAME OF EACH COMPONENT OR SYSTEM REFERRED TO IN THIS LER:

COMPONENT IEEE 803 IEEE 805 FUNCTION NUMBER SYSTEM IDENTIFICATION Pump P

SJ Pump P

BA Valve, Relief RV SB Valve, Relief RV AB Connector CON JJ NRC FORM 36SA (1-2001)