ENS 51159
From kanterella
Jump to navigation
Jump to search
ENS Event | |
---|---|
08:52 Jun 16, 2015 | |
Title | Emergency Diesel Generator Found Inoperable |
Event Description | At 0452 EDT hours on June 16, 2015, during performance of a surveillance test for the Division 3 4160 Volt Bus Undervoltage/Degraded Voltage Channel Calibration and Logic System Functional Test, the K36 degraded voltage time delay relay was found outside of the Technical Specification 3.3.8.1 allowable value, resulting in an inoperable condition of the Division 3 Emergency Diesel Generator (EDG). The Division 3 EDG had previously been declared inoperable for performance of the surveillance testing.
The K36 degraded voltage time delay relay initiates load shedding, isolates the Division 3 bus, and starts the Division 3 EDG. The Technical Specification allowable value is 180 to 270 seconds. The as-found time was 272.66 seconds. The K36 relay was calibrated in accordance with plant procedures and returned to service at 0730 hours0.00845 days <br />0.203 hours <br />0.00121 weeks <br />2.77765e-4 months <br /> on June 16, 2015. The Division 3 EDG is the on-site power source for the High Pressure Core Spray system which is a single train system. Therefore, this event is being reported in accordance with 10 CFR 50.72(b)(3)(v)(D) as an event or condition that could have prevented the fulfillment of a safety function. The NRC Resident Inspector has been informed. |
Where | |
---|---|
Perry Ohio (NRC Region 3) | |
Reporting | |
10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
LER: | 05000440/LER-2015-001 |
Time - Person (Reporting Time:+2.7 h0.113 days <br />0.0161 weeks <br />0.0037 months <br />) | |
Opened: | Thomas Morse 11:34 Jun 16, 2015 |
NRC Officer: | Mark Abramovitz |
Last Updated: | Jun 16, 2015 |
51159 - NRC Website | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_51159&oldid=83491"