ENS 51091
ENS Event | |
---|---|
21:07 Aug 7, 2014 | |
Title | This Is a Continuation of En #50351 and En #50998 |
Event Description |
During an expanded scope inspection, deficiencies in the Control Building 147[foot] elevation were observed that caused the affected barrier to be considered nonfunctional: - Gaps were identified around cables in the foam cable tray penetration seal for penetration 1Z43H006F in the floor of the Cable Spreading Room (separating Fire Areas 0024A and 1104). The nonconforming condition observed for the affected fire barrier was identified as affecting both safe shutdown paths for Units 1 and 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10074859 The licensee will be notifying the NRC Resident Inspector.
During an expanded scope inspection for penetration seals, using more intrusive tools and methods, fire barriers in the Control Building El. 112 [foot] were found not to meet acceptance criteria. The fire protection engineering staff has examined the situations and recommends that these conditions be considered NON-FUNCTIONAL. - An issue was identified with the wall separating the el. 112 [foot] Control Building Working Floor, Fire Area (FA) 0001 from the Station Battery Room 1B, FA 1005. - An issue was identified with the wall separating the Station Battery Room 2A, Fire Area (FA) 2004 from the Station Battery Room 2B, FA 2005, on el. 112 [foot]. The nonconforming conditions observed for the affected fire barriers were identified as affecting both safe shutdown paths for Units 1 and 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10077573 & 10077574. The licensee has notified the NRC Resident Inspector. Notified the R2DO(O'Donohue).
During an expanded scope inspection for penetration seals, using more intrusive tools and methods, fire barriers in the Control Building El. 112 [foot] were found not to meet acceptance criteria. The fire protection engineering staff has examined the situations and recommends that these conditions be considered NON-FUNCTIONAL: - Issues were identified with the wall separating the el. 112 [foot] Control Building Working Floor, Fire Area (FA) 0001 from the Unit 1 AC Inverter Room, FA 1008. The nonconforming conditions observed for the affected fire barriers were identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10078011. The licensee has notified the NRC Resident Inspector. Notified the R2DO (Rose).
During an expanded scope inspection for penetration seals, using more intrusive tools and methods, fire barriers in the Control Building El. 112 [foot] were found not to meet acceptance criteria. The fire protection engineering staff has examined the situations and recommends that these conditions be considered NON-FUNCTIONAL: - Issues were identified with the wall separating the el. 112 [foot] Control Building U2 Water Analysis Room, Fire Area (FA) 2006 from the Control Building East Corridor, FA 0007 The nonconforming conditions observed for the affected fire barriers were identified as affecting both safe shutdown paths for Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10078561. The licensee has notified the NRC Resident Inspector. Notified the R2DO (Rose). |
Where | |
---|---|
Hatch Georgia (NRC Region 2) | |
Reporting | |
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
Time - Person (Reporting Time:+7004.63 h291.86 days <br />41.694 weeks <br />9.595 months <br />) | |
Opened: | Scott Britt 17:45 May 26, 2015 |
NRC Officer: | Jeff Herrera |
Last Updated: | Jun 3, 2015 |
51091 - NRC Website | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
Unit 2 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
WEEKMONTHYEARENS 526502017-03-30T13:22:00030 March 2017 13:22:00
[Table view]10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Due to Potential Tornado Generated Missiles ENS 525312017-02-03T19:58:0003 February 2017 19:58:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition - Appendix R Fire Analysis ENS 511202015-06-04T14:03:0004 June 2015 14:03:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for a Postulated Fire ENS 510702015-05-14T20:00:00014 May 2015 20:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Due to Excessive Toxic Chemicals Onsite ENS 506622014-12-09T23:25:0009 December 2014 23:25:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Non-Functional Fire Barrier Discovered Affecting Both Safe Shutdown Paths ENS 506292014-11-19T21:18:00019 November 2014 21:18:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Fire Penetration Not Meeting Requirements ENS 504552014-09-13T07:07:00013 September 2014 07:07:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Fire Penetration Did Not Meet Appendix R Requirements ENS 503512014-08-07T21:07:0007 August 2014 21:07:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Due to Discovery of Degraded Fire Barrier Walls ENS 509982014-08-07T21:07:0007 August 2014 21:07:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition This Is a Continuation of En #50351 ENS 510912014-08-07T21:07:0007 August 2014 21:07:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition This Is a Continuation of En #50351 and En #50998 ENS 501602014-05-30T20:10:00030 May 2014 20:10:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Grouting in Fire Penetrations Does Not Meet Requirements ENS 499152014-03-14T15:55:00014 March 2014 15:55:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment ENS 496072013-12-04T20:40:0004 December 2013 20:40:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition a Potential Electrical Hot Short in the Rhr Shutdown Cooling Control Cable Could Result in an Inter-System Loca ENS 492852013-08-15T20:10:00015 August 2013 20:10:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition a Hot Short in the Rhr Shutdown Cooling Control Cable Could Result in an Inter-System Loca ENS 439922008-02-18T06:20:00018 February 2008 06:20:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Due to #2 Turbine Bypass Valve Failure ENS 435032007-07-18T16:20:00018 July 2007 16:20:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition, 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Unanalyzed Condition - Vent Space Less than Design Basis ENS 434992007-07-17T12:00:00017 July 2007 12:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition - Vent Space Less than Design Basis 2017-03-30T13:22:00 | |