Finding | |
---|---|
Title | Failure to Properly Pre-Plan and Perform Maintenance on the Cable Vault and Switchgear Ventilation System |
Description | The inspectors identified a non-cited violation of Technical Specification 6.8, Procedures and Programs, associated with the licensees failure to properly pre-plan and perform maintenance on safety-related components in accordance with EN-DC-335, Preventative Maintenance Basis Template. Specifically, the licensee did not follow the required preventive maintenance basis template for the safety-related cable vault and switchgear ventilation system, and was performing vibration monitoring of these components on an 18-month frequency instead of the required 3-month frequency. As a result, the licensee was deviating from the industry standard preventive maintenance recommendations without documented technical bases, and the required preventive maintenance tasks on these safety-related components were not performed. The licensee entered this condition into their corrective action program as condition report CR-WF3-2016-02353. The licensee restored compliance by assigning the proper preventive maintenance activities for the components in this system and instituting the appropriate frequency. In addition, a maintenance scope review is being performed. The performance deficiency was more than minor because it affected the Equipment Performance attribute of the Mitigating Systems cornerstone and its objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, actions to detect, preclude and address degradation of the safety-related components were delayed. The inspectors screened the finding in accordance with NRC Inspection Manual Chapter (IMC) 0609, Significance Determination Process. Using IMC 0609, Appendix A, The Significance Determination Process for Findings At-Power, the inspectors determined that the finding was of very low significance (Green) because all the screening questions in Exhibit 2 Mitigating Systems Screening Questions were answered No. The finding had an Identification cross-cutting aspect in the area of Problem Identification and Resolution because individuals did not identify issues completely, accurately, and in a timely manner in accordance with the corrective action program. Specifically, during previous vibration tests, the licensee had opportunities to identify the incorrect classification of the preventive maintenance task but did not do so [P.1]. |
Site: | Waterford |
---|---|
Report | IR 05000382/2016002 Section 1R12 |
Date counted | Jun 30, 2016 (2016Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.12 |
Inspectors (proximate) | C Speer F Ramirez G Miller P Elkmann |
Violation of: | Technical Specification - Procedures |
CCA | P.1, Identification |
INPO aspect | PI.1 |
' | |
Finding - Waterford - IR 05000382/2016002 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Waterford) @ 2016Q2
Self-Identified List (Waterford)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||