Finding | |
---|---|
Title | Failure to Correct an Adverse Condition Associated with Diesel Generator Load Sequencer Module |
Description | Green. A finding of very low safety significance and an associated NCV of 10 CFR, Part 50, Appendix B, Criterion XVI, Corrective Action, was self-revealed for the licensees failure to promptly correct a condition adverse to quality. Specifically, the licensee failed to correct an adverse condition associated with the emergency diesel generator (DG) load sequencer and power supply module as revealed when the electrolytic capacitor failed two days after installation. The 12 DG was declared inoperable, the licensee replaced the failed module, and an equipment apparent cause evaluation was completed for the equipment failure. An internal operating experience review revealed that a similar issue occurred in 2005 and corrective actions to address that failure, which included establishing shelf life and age requirements for electrolytic capacitors that were part of power supply modules, were not applied to this module. The licensee entered this issue into their CAP as CRPLP201603260. The issue was determined to be more than minor in accordance with IMC 0612, Appendix B, because the performance deficiency was associated with the Equipment Performance attribute of the Mitigating Systems cornerstone and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences (i.e., core damage). Specifically, the licensee failed to correct a condition adverse to quality, which rendered the 12 DG inoperable. This condition would have prevented the DG from automatically starting and loading on the prescribed signal. The finding was screened in accordance with IMC 0609, Appendix A, and was determined to have very low safety significance (Green) based on answering No to all the screening questions under the Mitigating Structure, System and Components, and Functionality section. The inspectors concluded that the corrective actions for the adverse condition of the aging electrolytic capacitors should have been implemented greater than three years ago, so the finding was not reflective of current licensee performance. Therefore, no cross-cutting aspect was identified. |
Site: | Palisades |
---|---|
Report | IR 05000255/2016004 Section 4OA2 |
Date counted | Dec 31, 2016 (2016Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Self-revealing |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | A Nguyen B Bartlett E Duncan G Hansen I Khan J Boettcher J Kutlesa M Learn M Ziolkowski N Fields R Edwards V Meghani V Myers |
Violation of: | 10 CFR 50 Appendix B Criterion XVI |
INPO aspect | |
' | |