05000255/FIN-2016004-01
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Have Appropriate Controls in Place for Combustible Materials |
Description | Green. A finding of very low safety significance and an associated NCV of Title 10 of the Code of Federal Regulations (10 CFR), Part 50, Section 48(c) was identified by the inspectors for the licensees failure to appropriately implement the requirements of procedure ENDC161, Control of Combustibles. Specifically, between January 1, 2016 and October 22, 2016, the inspectors identified several examples of the licensees failure to have appropriate controls in place for the storage of combustible materials in excess of the limits required for those respective areas without a completed transient combustible evaluation (TCE). Also, on several occasions from October 19, 2016 to October 22, 2016, the required compensatory actions for a TCE related to the dry fuel storage cask transporter vehicle were not appropriately implemented as required by procedure ENDC161. The licensee entered these issues in their corrective action program (CAP) as condition reports (CRs) CRPLP201603633, CRPLP201605148, and CRPLP20160564. Corrective actions for these issues included completing the required TCEs, ensuring the combustible materials in the areas were addressed by the combustible loading calculations, and ensuring appropriate compensatory measures were implemented. The issue was determined to be more than minor in accordance with IMC 0612, Appendix B, Issue Screening, because it was associated with the Protection Against External Factors attribute, in the area of Fire, of the Mitigating Systems cornerstone and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences (i.e., core damage). Specifically, transient combustible materials without required TCEs were stored in the charging pump cubicles and in the refueling and spent fuel pool areas. The finding screened as having very low safety significance (Green) in accordance with IMC 0609, Appendix F, Fire Protection Significance Determination Process, since none of the stored materials were self-igniting, low flashpoint liquids, or heat sources and was therefore assigned a Low degradation rating. The finding had a cross-cutting aspect of Training in the Human Performance cross-cutting area due to the common element of a lack of knowledge of the individuals with the control of combustibles process and understanding their roles in that process (H.9). |
Site: | Palisades |
---|---|
Report | IR 05000255/2016004 Section 1R05 |
Date counted | Dec 31, 2016 (2016Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | A Nguyen B Bartlett E Duncan G Hansen I Khan J Boettcher J Kutlesa M Learn M Ziolkowski N Fields R Edwards V Meghani V Myers |
Violation of: | 10 CFR 50.48 |
CCA | H.9, Training |
INPO aspect | CL.4 |
' | |
Finding - Palisades - IR 05000255/2016004 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Palisades) @ 2016Q4
Self-Identified List (Palisades)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||