TXX-6966, Final Deficiency Rept CP-86-53 Re Seismic Design of Conduit. Initially Reported on 861021.Installation of Fiberglass Cloth/Resin Matl or Optional Conduit Supports Currently Scheduled for Completion by 880420
| ML20236P157 | |
| Person / Time | |
|---|---|
| Site: | Comanche Peak |
| Issue date: | 11/13/1987 |
| From: | Counsil W, Woodlan D TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC) |
| To: | NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM) |
| References | |
| CP-86-53, TXX-6966, NUDOCS 8711170177 | |
| Download: ML20236P157 (1) | |
Text
_ _ _ _ .
1
(; 1 1
g 'I 4
I
= Log # TXX-6966 3 L 5 Fi1e #-10110 I
.= = .
.903.10- ,
- 7EFELECTRIC Ref #10CFR50.55(e) 1
' Nove aber 13, 1987 Milliam G. Counsil-l\ Emmtive Vice Prnident l
-U. S. Nuclear Regulatory Commission .
Attention: Document Control Desk p Washington, D. C. 20555 ,
i L
SUBJECT:
COMANCHE PEAK. STEAM ELECTRIC STATION (CPSES)
DOCKET N05. 50-445 AND 50-446 SEISMIC DESIGN OF CONDVIT SDAR: CP-86-53-(FINALREPORT) i Gentlemen: j
'i On October 21, 1986, we notified you by our letter, logged TXX-6054, of a l deficiency involving the seismic design of conduit, which we deemed reportable ,
under the provisions of 10CFR50.55(e). Our latest report on this issue was B c TXX-6913, dated November 4,1987.
The additional testing performed to evaluate the ability of the fiber glass l cloth / resin material-to resist torsional moments has been completed. The test results indicate'that the fiberglass cloth / resin material will resist the torsional moments and is an acceptable solution for use outside containment'.
. As an alternative, conduit supports may be substituted as required on a case by case basis for the fiberglass cloth / resin material to resist the torsional moments. ,
Installation of the fiberglass cloth / resin material or optional conduit i supports is currently scheduled for completion by April 20, 1988.
Very truly yours, h,b b W. G. Co nsil 8711170177 871113 5 l PDR ADOCK 05 g:
y !
S D. R. Woodlan Supervisor, Docket Licensing {
RSB:tgj c-Mr. R. D. Martin, Region IV Resident inspectors, CPSES (3) p ;
i/
\
400 North Olive Street LB 81 Dallas, Texas 75201
-