Event Description | At 0313 EST on March 9th, 2021, during performance of Unit 1 High Pressure Coolant Injection (HPCI) valve exercising, the inboard vacuum breaker isolation valve did not stroke closed as expected, but remained mid-position. The affected penetration of primary containment was isolated by closing the outboard HPCI vacuum breaker isolation valve. This results in an unplanned inoperability of the Unit 1 HPCI system.
This is being reported as a loss of an entire safety function condition in accordance with 10CFR50.72(b)(3)(v)(D). The licensee notified the NRC Resident Inspector. Unit 1 is in a 14-day LCO for Tech Spec 3.5.1(d), HPCI inoperability. Tech Spec 3.6.1.3(a), Containment Penetration Valve, was completed with closing the outboard HPCI vacuum breaker isolation valve. The Units are in a normal offsite power line-up. |
Where | |
---|---|
Susquehanna Pennsylvania (NRC Region 1) | |
Reporting | |
10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
Time - Person (Reporting Time:+-0.08 h-0.00333 days <br />-4.761905e-4 weeks <br />-1.09584e-4 months <br />) | |
Opened: | Darvin Duttry 08:08 Mar 9, 2021 |
NRC Officer: | Bethany Cecere |
Last Updated: | Mar 9, 2021 |
55128 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 55128\u003C/a\u003E - \u003Ca href=\"/Susquehanna\" title=\"Susquehanna\"\u003ESusquehanna\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EHigh Pressure Coolant Injection Inoperable\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 55128 - Susquehanna\n","link":"","lat":41.09256666666667,"lon":-76.14176944444445,"icon":"/w/images/c/c7/Talen_Energy_icon.png"}],"imageoverlays":null} | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |