Finding | |
---|---|
Title | Failure to Identify and Remove Diesel Fire Pump Battery Terminal Corrosion |
Description | The inspectors identified a finding of very low safety significance (Green) and associated NCV of Technical Specifications for the licensees failure to adequately implement the diesel fire pump (DFP) battery surveillance procedure. Specifically, the licensee failed to identify and remove corrosion on the DFP battery terminals, which was contrary to the surveillance procedure that implemented the fire protection program. A similar NCV was previously cited by the NRC on October 17, 2011, and documented in inspection report 05000237/2011008; 05000249/2011008, Failure to Identify Diesel Fire Pump Battery Terminal Corrosion. The licensee entered the issue into their corrective action program and planned to clean the battery terminals. In addition, the licensee planned to replace the 2/3 DFP batteries in July 2012. The inspectors determined that the finding was more than minor because, if left uncorrected, the presence of corrosion in conjunction with identified voltage issues for two battery cells could affect the reliability of the diesel fire pump. This finding was of very low safety significance because the DFP had started as part of a recent routine surveillance. This finding has a cross-cutting aspect in the area of PI&R because the licensee failed to identify the battery corrosion accurately and in a timely manner commensurate with their safety significance. |
Site: | Dresden |
---|---|
Report | IR 05000237/2012007 Section 4OA2 |
Date counted | Jun 30, 2012 (2012Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | Z Falevits R Orlikowski V Meghani J Cameron H Freeman T Briley |
CCA | P.1, Identification |
INPO aspect | PI.1 |
' | |
Finding - Dresden - IR 05000237/2012007 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Dresden) @ 2012Q2