Text
- _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ . _ _ _ .
A A Kfc
'o,, UNITED STATES P[ ,
4, n NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555
{ $
%,*****/
r"318 CG Docket No. 50-282 Mr. D. M. Musolf, Manager Nuclear Support Services Northern States Power Company 414 Nicollet Mall Midland Square, 4th Floor Minneapolis, Minnesota 55401
Dear Mr. Musolf:
SUBJECT:
PROJECTED VALUES OF MATERIAL PROPERTIES FOR FRACTURE TOUGHNESS REQUIREMENTS FOR PROTECTION AGAINST PRESSURIZED THERMAL SHOCK EVENTS-PRAIRIE ISLAND NUCLEAR GENERATING PLANT UNIT NO. 1 On June 23, 1986, the Commission issued a Safety Evaluation (SE) on
" Projected Values of Material Properties for Fracture Toughness Requirements For Protection Against Pressurized Thermal Shock Events" for Prairie Island
- Nuclear Generating Plant Unit No. 1. Errors have been found on pages 2 and 3 of the SE.
Corrections are listed below and a reissue of the SE is enclosed.
- 1. Top of page 2 - The number for " Utility Submittal" for "M (Margin, F) was left out. The number should be "59."
- 2. Page 2 " Evaluation of the Calculated RT " - The material properties ofthecontrollingmaterialandtheass$Natedmarginandchemistry factor were incorrect for copper and nickel. The correct factor is 0.14 for copper (Cu) and 0.17 for nickel (Ni). This error causes the equation to change.
- 3. Page 33 line 2 and line 4 from top of page "189.4 F" should be "154.1 F" for the limiting circumferential weld material.
860easco97 DR ADocg a60818 p 99999282 PDR
_2_
0 4.
Pageg,)line3-thelargemarginbecomes"(145.9F)"insteadof 110.6 F .
Please accept our apologies for any inconvenience these errors may have caused you.
Sincerely, s/
Dominic C. Dilanni, Project Manager 3
Project Directorate #1 Division of PWR Licensing-A 3-
Enclosure:
'As Stated
?
8 ll '
Surname: PShuttlew .
DDilanni/lp Glear Date: 08//.F/86 08/ /f/86 08/lf/86
,