Special Rept 50-321/1985-001:on 850122,24 & 31,vol in Fire Water Storage Tanks Dropped Below 270,000 Gallon Requirement.Caused by Loss of Power to Air Compressor,Broken Air Compressor Belt & Fire Main Break,Respectively