- Date: 9/10/73
. ,
Time: 3:00 a.m.
.- o .
.
/ ABNORMAL OCCURRENCE REPORT NO. 73-21
.
SUBJECT:
Failure of 21 Ilydraulic Shock and Sway Arrestors on piping systems in the Drywell, including units on both Core Spray and both
'
Isolation Condenser loops.
.
This event is considered to be an abnormal occurrence as defined in the Technical Specifications, paragraph 1.15.D. Notification of this event as required by the Technical Specifications, para-
. grap:16.6.2.a, was made to AEC Region I, Directorate of Regulatory
,
.
Operations, by telephone on Monday, September 10, 1973, at 12:45 p.m., and personally to Mr. E. Greeman on Monday, September 10, 1973.
.
SITUATION: The plant was shutdown on September 8,1973 for the purpose of inspecting the flydraulic Shock and Sway Arrestors located on
~ ~
piping systems throughout the Drfwell.
CAUSE: The snubbers were made inoperable due to a loss of hydraulic fluid.
REMEDIAL ACTION:
The failed liydraulit Shock and Sway Arrestors were replaced using
- ,
snubbers ' rebuilt with seal kits supplied by the Bergen Paterson Pipe Support Company. The new' seals are of'a different type, which according to Bergen Paterson, will provide a longer seal life.
.
p
-
.
.
O: 4
,
'
.- .
b~
AbnoEnal Occurrence .
September 10, 1973 - -
Report No. 73-21 ,
.
.
SAFETY SIGNIFICANCE:
<
The loss of snubber operability resulted in a reduction in the ability of the plant to safely survive a design bases earthquake.
The failures were such that they affected both Core Spray and
.
e both Emergency Condenser Systems, e
, o e
,
e a I
- e e
0 e
e o e
%
.
e 0
.
.
6 -.
.