ML20081B541
| ML20081B541 | |
| Person / Time | |
|---|---|
| Site: | North Anna |
| Issue date: | 02/28/1995 |
| From: | Ohanlon J, Stall J VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.) |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| 95-128, NUDOCS 9503160242 | |
| Download: ML20081B541 (11) | |
Text
F ]
l o 't ]
c i VIMOINIA ELECTRIC AND Powen COMPANY Ricnxown,VINGINIA 20263 March 10,1995
, 4 U. S. Nuclear Regulatory Commission Serial No.95-128 Attention: Document Control Desk NL&P/GSS R0 Washington, D.C. 20555 Docket Nos. 50-338 50-339 License Nos. NPF-4 NPF-7 Gentlemen: !
VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION UNITS 1 AND 2 MONTHLY OPERATING REPORT j Enclosed is the Monthly Operating Report for North Anna Power Station Units 1 and 2 for the month of February 1995.
Very truly yours, j
/N James P. O'Hanlon Senior Vice President - Nuclear l Enclosure cc: U.S. Nuclear Regulatory Commission ,
Region ll 1 101 Marietta Street, NW Suite 2900 Atlanta, GA 30323 Mr. R. D. McWhorter NRC Senior Resident inspector ,
North Anna Power Station !
160035 9503160242 950228 1 PDR ADOCK 05000338 h R PDR / \ l I ,
- s ;
I '
l
- .1 -
r :
l I
t- .
p l l' (
5 VIRGINIA POWER COMPANY l NORTH ANNA POWER STATION :
MONTHLY OPERATING REPORT i
i MONTH: Februarv YEAR: 1995 l l
i i
i I
l I
4 j
h Approved: !
I i
l Station Manager i
, .. ,m _
+7 m < s
,e J+ -
3 r
, , <r *[ _
,.; OPE'ATING DATA REPORT
- r h
DOCKET Wo.: 50-338 l DATE: March 6, 1995 ,
CONTACT: J. A. Stall _!
PHONE: (703) 894 2101-
. OPERATING STATUS
~ . . ". r 1.~ Unit Names................................ North Anna 1 ;
i
- 2. - Report i ng Per i od: . . . . . . . . . . . . . . . . . . . . . . . . . February 1995 "
E , 3. Licensed Thermal Power (MWt) ............. 2,893
'4. Nameplate Rating (Gross W e):............. 994 l p 5. Design Electrical Rating (Net MWe):....... 907
'- ' 6. Maximan Dependable capacity (Gross MWe) .. -948
- 7. Maximum Dependable Capacity (Net MWe) .... 900' .
l l
p 8. If changes occur in Capacity Ratings (Items No. 3 thru 7) since last report, give reasons: _N/A l l
. i f
. 9. Power level to which restricted, if any (Net MWe): N/A .)
- 10. Reasons for restrictions, if any: N/A l
.?
This Month Y-t-D Cumulative l i
- 11. Hours in Reporting Period................................. 672.0 1,416.0 ' 146,292.0- )
- 12. Nmber of Hours React or was Cri t i ca l . . . . . . . . . . . . . . . . . . . . . . 672.0 1,394.6 - 109,842.4 l
- 13. Reactor Reserve Shutdown Hours............................ 0.0 20.9 6,951.4 -!
- 14. Hours Generator 0n-Line................................... 672.0 1,389.8 106,843.5
- 15. Uni t Reserve Shut down Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.0 0.0 .
0.0 j
- 16. Gross Thermal Energy Generated (MWH)...................... 1,944,102.1 3,%9,638.9 284,155,218.8 j
- 17. Gross Electrical Energy Generated (MWH)................... 639,645.0 1,306,067.0 93,381,687.0 j
- 18. Net E l ect ri cal Energy Generat ed (MWM ) . . . . . . . . . . . . . . . . . . . . . 608,813.0 1,242,832.0 88,445,118.0 .I 1
- 19. Unit Service Factor....................................... 100.0% 98.1% 73.0%
~
- 20. Unit Availability Factor.................................. 100.0% 98.1% 73.0%
- 21. Uni t Capac i t y F ac t or (us i ng MDC Net ) . . . . . . . . . . . . . . . . . . . . . . 100.7% 97.5% 67.6%
- 22. Unit capacity Factor (using DER Net)...................... 99.9% 96.8% 66.7% ~
1
- 23. Forced Outage Rate........................................ 0.0%' 1.9% 9.9%
- 24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):_N/A
'l i
- 25. If Shutdown at end of Report Period, estimated time of Startup:_N/A j
' 26. Units in Test Status (Prior to Comercial Operation):
Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY )
COMMERCIAL OPERATION
]
l i
l l
l
I' l
i
/
AVERAGE DAILY UNIT POWER LEVEL 4
Docket No.: 50-338 Units- NA-1 l' Date: March 6. 1995
Contact:
J. A. Stall l Phone: (703) 894-2101 s
i MONTH: February 1995 '
-9 g
DAY AVERAGE DAILY POWER DAY AVERAGE DAILY POWER LEVEL (MWe-Net) LEVEL (MWe-Net) 1 908 17 905 r 2 906 18 908 l 3 906 19 907 !
4 906 20 907 5 905 . 21 907 ;
6 904 22 907 7- 904 23 908 8 906 24 907 ')
9 905 25 908 '
10 906 26 907 l 11 906 27 _ _ .
902 12 905 28 907 13 905 14 905 !
15 906 '
16 908 i
r i
Instructions: l On this. format, list the average daily unit power level in MWe- -t Net for each day in the reporting month. Compute to the nearest !
whole megawatt. '
P
p- ,- ,
- I NORTH ANNA POWER STATION i
?
UNIT NO.:'_1_
NONTH: Februarv~ ,
- .. s SUNNARY OF.. OPERATING EXPERIENCE Page 1 of 1 .
t Listed below 'in chronological sequence is a summary of- operating experiences for this - month which required load reductions or resulted in-
-significant non-load related incidents.
Date Time Data ;
February 01, 1995 0000 Began month with unit at 100's power,-954 MWe. 'I i
February 28, 1995 2400 Ended month with unit at 100% power, 954 MWe. !
i I
t e
h t
i j
l
-(
4h,/
j.- , .
- .3
.Page. 1 .of __1-UNIT SHUTDOWN'AND., POWER' REDUCTIONS Explanation Sheet Docket No.:: 50-338 Report Month February Unit Names NA-l' t- .-
Year 1995_ Date March 6. 1995
[:
Contact:
J. A. Stall
- No entry this month.
u l
l
.I
')
+
-y ,
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.: 50-338 UNIT NAME: NA-1c DATE: March 6,.1995 REPORT MONTH: February 1995 CONTACT:-J. A.. Stall PHONE: (703) 894-2101 1 2 3 4 5
'No. Date Type Duration Reason Method of Licensee. System Component .Cause & Corrective (hrs) Shutting . Event Code Code Action to.
Down Reactor Report # rrevent Recurrence
- No Entry This Month 1: Type 2: Reason 3: Method 4:
F= Forced A= Equipment Failure (explain) 1= Manual' Exhibit F - Instructions S= Scheduled B= Maintenance or Test 2= Manual Scram -for preparation of Data t
C= Refueling 3= Automatic Scram Entry Sheets for~ Licensee D= Regulatory Restriction 4= Continuations Event Report (LER) File E= Operator Training & License Examination 5= Load Reduction (NUREG-0161).
F= Administrative 9=Other G= Operational Errer 5:
H=Other (explain) Exhibit H - Same Source
- v. <
j
- 5' s,2f ,
OPERAT!!G DATA REPORT.
, e
.; 't .
M DOCKET No.:. 50-339 i DATE: March 6, 1995 CONTACT: J. A. Stall ~ .
~ ' '
. PHONE: (703) 894 2101~
- o. ;
OPERATING STATUS ,
'i
- 1. Uni t Name: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nor th Anna 2
- 12. Report i ng Per i od: . . . . . . . . . . . . . . . . . . . . . . . . . February 1995 l
' 3. Licensed Thermal Power (MWt):............. 2893 ,
-t 4 Nameplate Rating (Gross MWe):............. 979
- 5. Design Electrical Rating (Net MWe):....... 907 6.- Maximum Dependable capacity (Gross MWe):.. 935 =I
- 7. Maximum Dependable Capacity (Net MWe) .... 887 t
- 8. If changes occur in Capacity Ratings (Items No. 3 thru 7) since last report, give reasons _N/A
- 9. Power level to which restricted, if any (Net MWe): N/A ^t
- 10. Reasons for restrictions, if any N/A This Month Y-t D Cumulative t
?
1
.11. Hours i n Report i ng Per i od. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 672.0 1,416.0- 124,560.0
- 12. Number of Hours Reactor was Critical...................... 672.0 1,416.0 104,349.5 !
- 13. Reactor Reserve Shutdown Maurs............................ 0.0 0.0 6,508.9
- 14. Hours Generator 0n-Line................................... 672.0 1,416.0 103,251.7
- 15. Unit Reserve Shutdown Hours............................... 0.0 0.0 0.0
- 16. Grosa Thermal Energy Generated (MWH) . . . . . . . . . . . . . . . . . . . . . 1,622,944.1 3,728,851.5 280,344,815.5 .
1
- 17. Gross Electrical Energy Generated (MWH)................... 529,606.0 1,212,500.0 91,689,357.0 ;
- 18. Net Electrical Energy Generated (MWH). .. .. .. .. ... . . ... .. .. 500,584.0. 1,149,551.0 87,689,519.0 ,
- 19. Unit Service Factor....................................... 100.0% 100.0% 82.9% i
- 20. Unit Availability Factor.................................. -100.0% 100.0% 82.9%
- 21. Unit capacity Factor (using MDC Net)...................... 84.0% 91.5% 78.2%
- 22. Unit Capacity Factor (using DER Net)...................... 82.1% 89.5% 77.6%
- 23. Forced Outage Rate........................................ 0.0% 0.0% 5.1%
- 24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each): _ Refueling / Steam Generator Replacement, 03/25/95, 96 days
- 25. If Shutdown at end of Report Period, estimated time of Startup: N/A
- 26. Units in Test Status (Prior to Commercial Operation):
Forecast Achieved i INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION I
l
- s. ,
'd; -' ; . ,
c - ,,
AVERAGE DAILY UNIT POWER LEVEL !
1 Docket No.: 50-339 I Unit: NA-2 -
Date: March 6. 1995
Contact:
J. A. Stall _
Phones. (703) 894-2101 ;
MONTH: February 1995 i
DAY AVERAGE DAILY POWER DAY AVERAGE DAILY POWER-LEVEL (MWe-Net) LEVEL (MWe-Net) . ,
1 814 17 726 _
2 811 18 724 :
3 809 19 722 4 806 20 716 l 5 795 21 709 6 787 22 708 7 785 23 702 8 ,784 24 696 l' 9 774 25 694 10 759 . . .
26 691 _ , . . _
I 11 758 27 680 i 12 756 28 679 13 753 14 751 ;
15 743 l 16 724 l
i Instructions: )
On this for , list the average daily unit power level in MWe- ;
Net for each es in the reporting month. Compute to the nearest l whole megawatt. l i
j
.i
r
, .: NORTH ANNA POWER STATION
, UNIT NO.:'_2_.
y/L.
~
-MONTH: February 3
SUMMARY
OF OPERATING EXPERIENCE i
Page 1 of 1
. Listed below in chronological sequence is a summary of operating
.cxperiences for this month which required load reductions or resulted in significant non-load related incidents.
Date Time p_sta February 01, 1995 0000- Began month with unit at 91% power, 864 MWe in' end-of-cycle coastdown.
February 28, 1995 2400 Ended month with unit at 76% power, 720 MWe.
Several small unit ramp-downs (<st power each) have occurred during this month to match Tave and Tref during end-of-cycle coastdown and are not individually recorded in this report.
l I
.;j '-'
Page 1 o f __ ,J,
[. ,
i/ > UNIT. SHUTDOWN AND POWER REDUCTIONS Explanation Sheet
-Docket No.: 50-339 Report Month Februarv Unit Names NA-2 _
Year 1995 Date: March 6. 1995
Contact:
J. A. Stall'
- No entry this month.
1
~
). ; L
,P.
UNIT SIRTfDOWNS AND POWER REDUCTIONS ,
DOCKET NO.: 50-339 UNIT NAME: NA-2 DATE: March 6, 1995 REPORT MONTH: February 1995 CONTACT: J. A. Stall-PHONE: (703) 894-2101 1 2 3 4 5 No. Date Type Duration Reason Method of Licensee System Component Cause & Corrective
! (hrs) Shutting Event Code Code Action to Down Reactor Report # Prevent Recurrence ONo Entry This Month.
1: Type 2: Reason 3: Method 4:
F= Forced A= Equipment Failure (explain) 1= Manual Exhibit F - Instructions S= Scheduled B= Maintenance or Test 2= Manual Scram- for preparation of Data C= Refueling 3= Automatic Scram Entry Sheets for Licensee D= Regulatory Restriction 4= Continuations Event Report (LER) File !
E= Operator Training & License Examination 5= Load Reduction (NUREG-0161).
F= Administrative 9=Other G= Operational Error 5:
H=Other (explain) Exhibit'H - Same Source i
. _ __ . .