| title = 24-Hour Condition | | title = 24-Hour Condition of License Report Due to Inoperable Division Ii Control Room Special Filter Train | ||
| event text = While attempting to perform the Control Room Special Filter Train Functional Test for Division ll, the required train flow test conditions could not be established. Investigation revealed that the inlet backdraft damper 2HVC*DMPV93 was latched closed and would not open automatically on a Special Filter Train start. | | event text = While attempting to perform the Control Room Special Filter Train Functional Test for Division ll, the required train flow test conditions could not be established. Investigation revealed that the inlet backdraft damper 2HVC*DMPV93 was latched closed and would not open automatically on a Special Filter Train start. | ||
The damper was found latched closed due to an improperly set spring-loaded 'stop.' As a result, the Division II Control Room Special Filter Train was declared inoperable as of 1530 on 1/28/04. Technical Specification 3.7.2, Condition A was entered which allows 7 days to restore the Division II Control Room Special Filter Train to an operable status. | The damper was found latched closed due to an improperly set spring-loaded 'stop.' As a result, the Division II Control Room Special Filter Train was declared inoperable as of 1530 on 1/28/04. Technical Specification 3.7.2, Condition A was entered which allows 7 days to restore the Division II Control Room Special Filter Train to an operable status. |
Revision as of 22:24, 1 March 2018
Where | |
---|---|
Nine Mile Point New York (NRC Region 1) | |
Reporting | |
Other Unspec Reqmnt | |
Time - Person (Reporting Time:+17.33 h0.722 days <br />0.103 weeks <br />0.0237 months <br />) | |
Opened: | David Richardson 13:50 Jan 29, 2004 |
NRC Officer: | Chauncey Gould |
Last Updated: | Jan 29, 2004 |