ENS 41330: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 16: | Line 16: | ||
| event date = 01/13/2005 09:49 EST | | event date = 01/13/2005 09:49 EST | ||
| last update date = 01/13/2005 | | last update date = 01/13/2005 | ||
| title = Entry Into Technical Specification Required Shut Down Due | | title = Entry Into Technical Specification Required Shut Down Due to Loss of Essential Bus | ||
| event text = The following information was provided by the licensee via facsimile: | | event text = The following information was provided by the licensee via facsimile: | ||
At 0849 hours on January 13, 2005, during testing of Essential Bus D1 (Undervoltage Units monthly functional test) [the] Potential Transformer secondary fuse blew. This caused an Essential 4160 VAC Bus D1 undervoltage condition. Emergency Diesel Generator #2 auto started due to the undervoltage condition on Essential Bus D1. This auto start of EDG #2 is reportable IAW [in accordance with] 10CFR50.72(b)(3)(iv)(a). | At 0849 hours on January 13, 2005, during testing of Essential Bus D1 (Undervoltage Units monthly functional test) [the] Potential Transformer secondary fuse blew. This caused an Essential 4160 VAC Bus D1 undervoltage condition. Emergency Diesel Generator #2 auto started due to the undervoltage condition on Essential Bus D1. This auto start of EDG #2 is reportable IAW [in accordance with] 10CFR50.72(b)(3)(iv)(a). |
Latest revision as of 21:21, 1 March 2018
Where | |
---|---|
Davis Besse Ohio (NRC Region 3) | |
Reporting | |
10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown 10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
LER: | 05000346/LER-2005-001 |
Time - Person (Reporting Time:+-1.28 h-0.0533 days <br />-0.00762 weeks <br />-0.00175 months <br />) | |
Opened: | Anthony Stallard 13:32 Jan 13, 2005 |
NRC Officer: | Bill Huffman |
Last Updated: | Jan 13, 2005 |
41330 - NRC Website
| |