ENS 41330: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 01/13/2005 09:49 EST
| event date = 01/13/2005 09:49 EST
| last update date = 01/13/2005
| last update date = 01/13/2005
| title = Entry Into Technical Specification Required Shut Down Due To Loss Of Essential Bus
| title = Entry Into Technical Specification Required Shut Down Due to Loss of Essential Bus
| event text = The following information was provided by the licensee via facsimile:
| event text = The following information was provided by the licensee via facsimile:
At 0849 hours on January 13, 2005, during testing of Essential Bus D1 (Undervoltage Units monthly functional test) [the] Potential Transformer secondary fuse blew.  This caused an Essential 4160 VAC Bus D1 undervoltage condition.  Emergency Diesel Generator #2 auto started due to the undervoltage condition on Essential Bus D1.  This auto start of EDG #2 is reportable IAW [in accordance with] 10CFR50.72(b)(3)(iv)(a).
At 0849 hours on January 13, 2005, during testing of Essential Bus D1 (Undervoltage Units monthly functional test) [the] Potential Transformer secondary fuse blew.  This caused an Essential 4160 VAC Bus D1 undervoltage condition.  Emergency Diesel Generator #2 auto started due to the undervoltage condition on Essential Bus D1.  This auto start of EDG #2 is reportable IAW [in accordance with] 10CFR50.72(b)(3)(iv)(a).

Latest revision as of 21:21, 1 March 2018

ENS 41330 +/-
Where
Davis Besse Cleveland Electric icon.png
Ohio (NRC Region 3)
Reporting
10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown

10 CFR 50.72(b)(3)(iv)(A), System Actuation
LER: 05000346/LER-2005-001
Time - Person (Reporting Time:+-1.28 h-0.0533 days <br />-0.00762 weeks <br />-0.00175 months <br />)
Opened: Anthony Stallard
13:32 Jan 13, 2005
NRC Officer: Bill Huffman
Last Updated: Jan 13, 2005
41330 - NRC Website
Loading map...