ENS 44086: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 03/21/2008 15:25 CDT
| event date = 03/21/2008 15:25 CDT
| last update date = 03/21/2008
| last update date = 03/21/2008
| title = Automatic Reactor Scram From A Main Turbine Trip
| title = Automatic Reactor Scram from a Main Turbine Trip
| event text = Actuation of an RPS signal while the reactor was critical.
| event text = Actuation of an RPS signal while the reactor was critical.
At 1525 a generator trip signal on the main transformers initiated a reactor scram due to Turbine Stop and Control Valve fast closure.  Safety relief valves operated initially to lower reactor pressure.  Turbine bypass valves operated initially to lower reactor pressure.  Turbine bypass valves are maintaining pressure control currently.  Reactor recirc pumps A and B transferred to slow speed operation as expected.  No ECCS initiations were received.  Reactor level is being controlled with normal systems condensate and feedwater.  Lowest level indicated was approximately -6" wide range.  Level 3 initiations occurred to group 3 isolation valves.  No valves operated, they are normally closed.
At 1525 a generator trip signal on the main transformers initiated a reactor scram due to Turbine Stop and Control Valve fast closure.  Safety relief valves operated initially to lower reactor pressure.  Turbine bypass valves operated initially to lower reactor pressure.  Turbine bypass valves are maintaining pressure control currently.  Reactor recirc pumps A and B transferred to slow speed operation as expected.  No ECCS initiations were received.  Reactor level is being controlled with normal systems condensate and feedwater.  Lowest level indicated was approximately -6" wide range.  Level 3 initiations occurred to group 3 isolation valves.  No valves operated, they are normally closed.

Latest revision as of 22:14, 1 March 2018

ENS 44086 +/-
Where
Grand Gulf Entergy icon.png
Mississippi (NRC Region 4)
Reporting
10 CFR 50.72(b)(2)(iv)(B), RPS Actuation
Time - Person (Reporting Time:+-2.43 h-0.101 days <br />-0.0145 weeks <br />-0.00333 months <br />)
Opened: Ernest Mathes
17:59 Mar 21, 2008
NRC Officer: Mark Abramovitz
Last Updated: Mar 21, 2008
44086 - NRC Website
Loading map...