| title = Technical Support Center Non-Functional Due To Hvac System Malfunction
| title = Technical Support Center Non-Functional Due to Hvac System Malfunction
| event text = The facility Technical Support Center (TSC) was rendered non-functional due to a malfunction in the TSC HVAC system.  A lugged connection on the air conditioning system control power relay became loose causing a loss of contact between the spade and the relay.  Repairs have been completed and the air conditioning has been returned to service.  However, the out of service time was greater than 30 minutes, which by the station's reporting procedures, is an 8 hour non-emergency report.  The out of service time was from 0935 to 1342 CST.   
| event text = The facility Technical Support Center (TSC) was rendered non-functional due to a malfunction in the TSC HVAC system.  A lugged connection on the air conditioning system control power relay became loose causing a loss of contact between the spade and the relay.  Repairs have been completed and the air conditioning has been returned to service.  However, the out of service time was greater than 30 minutes, which by the station's reporting procedures, is an 8 hour non-emergency report.  The out of service time was from 0935 to 1342 CST.   
Compensatory measures per site procedure FNP-0-EIP-6.0 (TSC Setup and Activation) for maintaining emergency assessment, off-site response, and off-site communication capabilities were available.  These measures included the conditional relocation of the TSC staff in the event of a declared emergency if the Emergency Director deems the TSC to be uninhabitable.
Compensatory measures per site procedure FNP-0-EIP-6.0 (TSC Setup and Activation) for maintaining emergency assessment, off-site response, and off-site communication capabilities were available.  These measures included the conditional relocation of the TSC staff in the event of a declared emergency if the Emergency Director deems the TSC to be uninhabitable.

Latest revision as of 21:01, 1 March 2018

ENS 48718 +/-
Where
Farley Southern Nuclear icon.png
Alabama (NRC Region 2)
Reporting
10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness
Time - Person (Reporting Time:+1.52 h0.0633 days <br />0.00905 weeks <br />0.00208 months <br />)
Opened: Charles Barefield
17:36 Feb 5, 2013
NRC Officer: Donald Norwood
Last Updated: Feb 5, 2013
48718 - NRC Website