ENS 50110: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 16: | Line 16: | ||
| event date = 05/12/2014 08:45 CDT | | event date = 05/12/2014 08:45 CDT | ||
| last update date = 05/12/2014 | | last update date = 05/12/2014 | ||
| title = Planned Maintenance | | title = Planned Maintenance on Safety Parameter Display System | ||
| event text = At 0845 [CDT] during planned maintenance, the annunciators which would indicate flooding in the Emergency Core Cooling System (ECCS) Pump Rooms to the max safe water level in the rooms were disabled. These max safe water level alarms are used to assess the emergency action level (EAL) entry condition (HA4) for flooding (ALERT classification). | | event text = At 0845 [CDT] during planned maintenance, the annunciators which would indicate flooding in the Emergency Core Cooling System (ECCS) Pump Rooms to the max safe water level in the rooms were disabled. These max safe water level alarms are used to assess the emergency action level (EAL) entry condition (HA4) for flooding (ALERT classification). | ||
Compensatory measures are in place to perform periodic walk downs of RHR A, RHR B, RHR C, HPCS, LPCS, RCIC rooms and the fuel building basement once per shift to verify no leakage. Additionally, the annunciator for max normal water level is operational and pump run times are still available in the Main Control Room to indicate increased leakage into the ECCS rooms. This max normal water level alarm is used to assess the EAL entry condition (HU4) for flooding (Unusual Event classification) and EOP-8 entry. | Compensatory measures are in place to perform periodic walk downs of RHR A, RHR B, RHR C, HPCS, LPCS, RCIC rooms and the fuel building basement once per shift to verify no leakage. Additionally, the annunciator for max normal water level is operational and pump run times are still available in the Main Control Room to indicate increased leakage into the ECCS rooms. This max normal water level alarm is used to assess the EAL entry condition (HU4) for flooding (Unusual Event classification) and EOP-8 entry. |
Latest revision as of 20:50, 1 March 2018
Where | |
---|---|
Clinton Illinois (NRC Region 3) | |
Reporting | |
10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness | |
Time - Person (Reporting Time:+3.87 h0.161 days <br />0.023 weeks <br />0.0053 months <br />) | |
Opened: | Dan Hunt 17:37 May 12, 2014 |
NRC Officer: | Pete Snyder |
Last Updated: | May 12, 2014 |
50110 - NRC Website
| |