| event date = 10/01/2015 09:06 CDT
| event date = 10/01/2015 09:06 CDT
| last update date = 10/01/2015
| last update date = 10/01/2015
| title = Mode Change With Turbine Trip Leads Lifted
| title = Mode Change with Turbine Trip Leads Lifted
| event text = At 0906 [CDT], it was determined that U1 [Unit 1] was in a condition that could have prevented fulfillment of the turbine trip safety function and TS [Tech Spec] 3.0.3 was entered. Leads had been lifted to disable the turbine trip function on both SSPS [Solid State Protection System] trains while U1 was in Mode 4 (which is outside the mode of applicability). However, at 0059 [CDT], U1 entered Mode 3 with these leads still lifted. In Mode 3, both trains of the turbine trip function are required to be operable per TS 3.3.2. The turbine was subsequently tripped at 0932 [EDT] and the leads were re-landed enabling the turbine trip function at 0946 [CDT], TS 3.0.3 was subsequently exited. This condition is being reported in accordance with 10 CFR 50.72 (b)(3)(v)(D) for an event or condition that could have prevented the fulfillment of a safety function to mitigate the consequences of an accident.
| event text = At 0906 [CDT], it was determined that U1 [Unit 1] was in a condition that could have prevented fulfillment of the turbine trip safety function and TS [Tech Spec] 3.0.3 was entered. Leads had been lifted to disable the turbine trip function on both SSPS [Solid State Protection System] trains while U1 was in Mode 4 (which is outside the mode of applicability). However, at 0059 [CDT], U1 entered Mode 3 with these leads still lifted. In Mode 3, both trains of the turbine trip function are required to be operable per TS 3.3.2. The turbine was subsequently tripped at 0932 [EDT] and the leads were re-landed enabling the turbine trip function at 0946 [CDT], TS 3.0.3 was subsequently exited. This condition is being reported in accordance with 10 CFR 50.72 (b)(3)(v)(D) for an event or condition that could have prevented the fulfillment of a safety function to mitigate the consequences of an accident.
The Byron NRC site Resident Inspector has been notified of this condition.
The Byron NRC site Resident Inspector has been notified of this condition.

Latest revision as of 20:46, 1 March 2018

ENS 51436 +/-
Where
Byron Constellation icon.png
Illinois (NRC Region 3)
Reporting
10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident
LER: 05000454/LER-2015-006
Time - Person (Reporting Time:+0.53 h0.0221 days <br />0.00315 weeks <br />7.25994e-4 months <br />)
Opened: Greg Gugle
14:38 Oct 1, 2015
NRC Officer: Daniel Mills
Last Updated: Oct 1, 2015