| title = Loss Of Secondary Containment Differential Pressure
| title = Loss of Secondary Containment Differential Pressure
| event text = On March 29, 2016 at 2256 [EDT], Secondary Containment Zone 2 (Unit 2 Reactor Building) differential pressure lowered to 0.0 [inches] WG [water gauge] due to a failed closed discharge damper on the in service Zone 2 exhaust fan. Required differential pressure per SR 3.6.4.1.1 could not be maintained. Zone 2 ventilation was restored by starting the standby Zone 2 exhaust fan.  Zone 2 differential pressure recovered to [greater than] 0.25 [inches] WG at 2321 hours.  Zone 3 (Unit 1&2  Reactor Buildings) ventilation remained in service and stable.  Zone 1(Unit 1 Reactor Building) ventilation remained in service however it is not required in this mode of Operation.
| event text = On March 29, 2016 at 2256 [EDT], Secondary Containment Zone 2 (Unit 2 Reactor Building) differential pressure lowered to 0.0 [inches] WG [water gauge] due to a failed closed discharge damper on the in service Zone 2 exhaust fan. Required differential pressure per SR 3.6.4.1.1 could not be maintained. Zone 2 ventilation was restored by starting the standby Zone 2 exhaust fan.  Zone 2 differential pressure recovered to [greater than] 0.25 [inches] WG at 2321 hours.  Zone 3 (Unit 1&2  Reactor Buildings) ventilation remained in service and stable.  Zone 1(Unit 1 Reactor Building) ventilation remained in service however it is not required in this mode of Operation.
This event is being reported under 10 CFR 50.72(b)(3)(v)(C) and per the guidance of NUREG 1022 Rev 3 section 3.2.7 as a loss of a Safety Function.  There is no redundant Susquehanna Secondary Containment System.
This event is being reported under 10 CFR 50.72(b)(3)(v)(C) and per the guidance of NUREG 1022 Rev 3 section 3.2.7 as a loss of a Safety Function.  There is no redundant Susquehanna Secondary Containment System.

Latest revision as of 20:45, 1 March 2018

ENS 51830 +/-
Where
Susquehanna 
Pennsylvania (NRC Region 1)
Reporting
10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material
LER: 05000387/LER-2016-012
Regarding Secondary Containment Declared Inoperable Due to Loss of Differential Pressure as a Result of a Solenoid Valve
Time - Person (Reporting Time:+-0.72 h-0.03 days <br />-0.00429 weeks <br />-9.86256e-4 months <br />)
Opened: Ronald Fry
02:13 Mar 30, 2016
NRC Officer: Dong Park
Last Updated: Mar 30, 2016