ML20010D154: Difference between revisions
StriderTol (talk | contribs) Created page by program invented by StriderTol |
StriderTol (talk | contribs) StriderTol Bot change |
||
| Line 86: | Line 86: | ||
12 769 , , 23 779 . | 12 769 , , 23 779 . | ||
J, ., | J, ., | ||
13 773 3 780 ~. - | 13 773 3 780 ~. - | ||
14 755 _ | 14 755 _ | ||
| Line 98: | Line 97: | ||
On this formst. list the average daily unit power level in MWe-Net for c:ch d:y in the reporting month. Compute to the ne: rest whole meg: watt. | On this formst. list the average daily unit power level in MWe-Net for c:ch d:y in the reporting month. Compute to the ne: rest whole meg: watt. | ||
%g " e *. | %g " e *. | ||
p , | p , | ||
. . t | . . t | ||
._ m | ._ m | ||
Revision as of 09:58, 17 February 2020
| ML20010D154 | |
| Person / Time | |
|---|---|
| Site: | Farley |
| Issue date: | 08/01/1981 |
| From: | Hairston W ALABAMA POWER CO. |
| To: | |
| Shared Package | |
| ML20010D153 | List: |
| References | |
| NUDOCS 8108240060 | |
| Download: ML20010D154 (3) | |
Text
,.
a OPERATI iG DATA REPORT DOCKET NO. 50-348 DATE 8/1/81 COMPLETED BY W.G.hairston, III TELEPHONE (ZU))69925156 OPERATING STATUS
- 1. Unit Name: J SePh M. Farley - Unit 1 Notes 1) Cumulative data
- 2. Reporting Period: July, 1981 since 12/1/77, date of
- 3. Licensed Thennal Power (MWt):
2652 commercial operation.
- 4. Nameplate Rating (Gross MWe): 860
- 5. Design Electrical Rating (Net MWe): 829
- 6. Maximum Dependable Capacity (Gross MWe): 844.6
- 7. Maximum Dependable Capacity (Net MWe): 803.6
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7)Since Last Report.Gise Reasons:
N/A
- 9. Power Lesel To Which Re tsicted. If Any (Net MWe): N/A
- 10. Rea>ons For Restrictions,1f Any: N/A This Month Yr.-to-Da te Cuhulatise
- 11. ilours In Reporting Period 744 5,087 32,135
- 12. Number Of flours Reactor Was Critical 744 2,840.8 20,023.1
- 13. Reactor Reserte Shutdown !!ours 0 374.1 2,820.9
- 14. Ilours Generator On.Line 744 2,670.6 19,374.0
- 15. Unit Reserve Shutdown Hours 0 , , .
0 0
- 16. Gross Thennal Energy Generated (MWH) 1.889.655.9 J ,500,017.8 48,489,909.6
- 17. Gross Electrical Energy Generated (MWH) 590,366 2,052,874 15,472,282
- 18. Net Electrical Energy Generated (MWH) 558,978 1 911,386 14.519,136
- 19. Unit Service Factor 100.0 _ 52.5 60.3
- 20. Unit Availability Factor 100.0 _
52.5 60.3
- 21. Unit capacity Factor (Using MDC Net) 93.5 46.8 _
56.2
- 22. Unit Capacity Factor (Using DER Net) 90.6 45.3 54.5
- 23. Unit Forced Outage Rate 00.0 10.8 07.5 _
- 24. ShutdownsSchedated Oser Next 6 Months (Type.Date.and Duration of Each):
Maintenance / Design Change Modifications associated with TMI-2; Mid-September, 1981; Anoroximately 2-3 weeks.
- 25. If Shur Down At End Of Report Period. Estimated Date of Startup: N/A
- 26. Units In Test Status (Prior to Commercial Operation): Forecast Achiesed
_ INITIA L CRITICA LITY 8/6/77 8/9/77 INITIA L ELECTRICITY 8/20/77 8/18/77 COMMERCIAL OPERATION 12/1/77 12/1/77-8108240060 810817 PDR ADOCK 05000348 R PDR (u1771
AVERAGE DAILY UNIT POWER LEVEL ,
+
,/
~
,.'~ DOCKET NO.
50-348 t .*' UNIT 1 DATE 8/1/81
~ .
N
- C' II"I E III NLETED BY
, ,t TELEPHONE (205) 899-5156 MONTl! July. 1981 ,
DAY AVERAGE DAILY POWER LEVEL
- DAY AVERAGE DAll POWER LEVEL (MWe-Net) (MWe. Net) 1 411 17
~778 - '.
775 2 781 IS
~ '
3 789 786 - -
39 4 722 -
20 785 . ..- .
3 593 .
.1 4
786 - - -
6 654 3 785 ,,.,.
7 777 786 m i . .
23 1 g 783 y 782 9 784 -
731 ~ --
25-
~ '
10 780
- 26 704 -
774 780 .
T gg . .
12 769 , , 23 779 .
J, .,
13 773 3 780 ~. -
14 755 _
30 783
. 15 767 .-
- 33 '784 ,
16 .
-775 -. . .
~
INS 7RUCDONS - ' -
On this formst. list the average daily unit power level in MWe-Net for c:ch d:y in the reporting month. Compute to the ne: rest whole meg: watt.
%g " e *.
p ,
. . t
._ m
, D "
UNIT SIIUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-348 UNIT NAME J.M.Feirley-Unit [
DATE _ R /1/R1 REPORT MONTil July, 1981 COMPLETED BY U.C.HMrston . III '
TELEPilONE (705)R99-5156 "E -
e ei .3 no : . 5
-o .2 _e E , .s X Licensee cg cLa Cause & Corrective No. Date g 3g g jg5 Event u? $.'3 Action to H iN0
$5 5 j di g Report e 5O Prevent Recurrence 6
018 810701 F 0 G 4 N/A RB ZZZZZZ Continuation of Power reduction from 6/30/81 due to accumulation of 72 penalty points for axial flux differ-ence (AI) being out'of target band during power ascension.
019 210704 F 0 A 4 N/A RB INSTRU Unit power reduced to and held at less than .'5% (639 Mwe) due to indicated Quadrant Power Tilt Ratio exceeding Tech. Spec, limit (QPTR-1.07) . Recalibrated NIS fol-lowing verification that QPTR had not.
exceeded Tech. Spec. limit.
020 810725 S 0 B 4 N/A HB INSTRU Unit power reduced to and held at
, 33% ,(205 MWe) to place flow trans-mitter FT-426 back in service.
I 2 3 4 1: 1 orced Reason: Metliod: lixhibit G . Instinctions S: Scheduled A liquipment Failure (Explain) ' l. Manual for Preparation of Data ll Maintenance of Test 2.Manu.il Scram. I?ntiy Sheet > for I.icensee C. Refueling 3. Automatic Seram. Event Report (LliR)l ile (NUREG.
D. Regulatory Restriction 4 Other(Explain) 0161)
E. Operator Training & License lixamination 1;. Administrative 5
G. Operational Error (Explain) Exlubit ! Same Source
('l/77) II.Othes (Fxplain) -
,