| event date = 02/06/2005 10:08 CST
| event date = 02/06/2005 10:08 CST
| last update date = 02/06/2005
| last update date = 02/06/2005
| title = 24 Hour Report Of A Safety Equipment Failure
| title = 24 Hour Report of a Safety Equipment Failure
| event text = The licensee provided the following information via facsimile:
| event text = The licensee provided the following information via facsimile:
At 1008, on 2-06-05, the Plant Shift Superintendent [PSS] was notified that at the C-360 Toll and Transfer Facility on autoclave 4, the vent line block valve, XV-434, failed to close when the control switch was operated to the closed position.  A check of the valve indicator showed that the valve moved to approximately 75% of the closed position.  This valve is a single isolation point (no redundant valve) for two TSR [Technical and Safety Requirements] systems: (1) The Autoclave Steam Pressure Control System and (2) The Autoclave Water Inventory Control System.  The autoclave was in mode 5, an applicable TSR mode for both systems.  The PSS declared the systems inoperable and TSR LCOs 2.1.3.3 and 2.1.4.3 were implemented to remove the autoclave from service and place it in mode 2 within one hour.
At 1008, on 2-06-05, the Plant Shift Superintendent [PSS] was notified that at the C-360 Toll and Transfer Facility on autoclave 4, the vent line block valve, XV-434, failed to close when the control switch was operated to the closed position.  A check of the valve indicator showed that the valve moved to approximately 75% of the closed position.  This valve is a single isolation point (no redundant valve) for two TSR [Technical and Safety Requirements] systems: (1) The Autoclave Steam Pressure Control System and (2) The Autoclave Water Inventory Control System.  The autoclave was in mode 5, an applicable TSR mode for both systems.  The PSS declared the systems inoperable and TSR LCOs 2.1.3.3 and 2.1.4.3 were implemented to remove the autoclave from service and place it in mode 2 within one hour.

Revision as of 22:21, 1 March 2018

ENS 41378 +/-
Where
Paducah Gaseous Diffusion Plant
Paducah, Kentucky (NRC Region 2)
License number: Gdp-1
Reporting
10 CFR 76.120(c)(2)
Time - Person (Reporting Time:+1.33 h0.0554 days <br />0.00792 weeks <br />0.00182 months <br />)
Opened: Tony Hudson
17:28 Feb 6, 2005
NRC Officer: Bill Huffman
Last Updated: Feb 6, 2005