| Title | Uf6 Release Detection System Inoperable |
| Event Description | At 0320 CDST, on 4-22-07 the Plant Shift Superintendent (PSS) was notified that the control power for C-337A #1 Autoclave had been lost due to a blown control power fuse. Investigation of a problem with the Autoclave 1 West CV-510 valve close indicating light not functioning properly was in progress at the time the fuse blew. Maintenance personnel were performing non-intrusive checks of the valve's limit switch and had activated the limit switch operating plunger when the fuse blew. No maintenance work package was used for these checks. The power supply for the local autoclave area audible and visible alarms for the UF6 Release Detection System are fed from the #1 Autoclave control power. Due to this loss of control power, the UF6 Release Detection System was rendered inoperable. At the time of the incident, the C-337A facility was operating in an operational mode in which the UF6 Release Detection System was required to be operable, TSR 2.2.4.1 Mode 5. The C-337A Operations Monitoring Room where UF6 Release Detection System alarms would have been received was unoccupied at the time of the fuse failure due to C-337A personnel in the autoclave area assisting with the CV-510 light investigation. The system was declared inoperable and Limiting Conditions of Operation (LCO) required action, TSR 2.2.4.1 A.1, was put in place until power could be restored. Subsequent troubleshooting revealed the CV-510 limit switch was broken and has shorted the control circuit to ground when activated causing the fuse to blow. Power was restored and the UF6 Release Detection System was declared operable at 0539 on 4-22-07 following repairs and PMT.
The event is reportable as a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> event as required by 10 CFR 76.120(c)(2)(i); An event in which equipment is disabled or fails to function as designed when the equipment is required by TSR to be available and operable and no redundant equipment was available to perform the required safety function. The NRC Senior Resident Inspector has been notified of this event. |
| Where | |
|---|---|
| Paducah Gaseous Diffusion Plant Paducah, Kentucky (NRC Region 2) | |
| License number: | GDP-1 |
| Reporting | |
| 10 CFR 76.120(c)(2) | |
| Time - Person (Reporting Time:+5.55 h0.231 days <br />0.033 weeks <br />0.0076 months <br />) | |
| Opened: | Wf Cage 13:53 Apr 22, 2007 |
| NRC Officer: | Jason Kozal |
| Last Updated: | Apr 22, 2007 |
| 43312 - NRC Website
Loading map... | |
Paducah Gaseous Diffusion Plant with 10 CFR 76.120(c)(2) | |
WEEKMONTHYEARENS 500992014-05-08T15:24:0008 May 2014 15:24:00
[Table view]10 CFR 76.120(c)(2) High Pressure Fire Water Sprinkler System B-6 Declared Inoperable ENS 499532014-03-24T01:50:00024 March 2014 01:50:00 10 CFR 76.120(c)(2) Safety Equipment Potential Failure - High Pressure Fire Water Sprinkler System ENS 499182014-03-14T18:30:00014 March 2014 18:30:00 10 CFR 76.120(c)(2) High Pressure Fire Water Systems Declared Inoperable ENS 485222012-11-19T22:25:00019 November 2012 22:25:00 10 CFR 76.120(c)(2) Uninterruptible Power Supply Safety Equipment Failure ENS 480222012-06-12T20:45:00012 June 2012 20:45:00 10 CFR 76.120(c)(2) Safety Equipment Failure - Criticality Air Horns Not Tested for Audibility ENS 479112012-05-08T21:16:0008 May 2012 21:16:00 10 CFR 76.120(c)(2), Response Autoclave High Pressure Isolation System Failure ENS 475312011-12-17T06:01:00017 December 2011 06:01:00 10 CFR 76.120(c)(2) Possible Degradation in High Pressure Fire Water Sprinkler Heads ENS 473762011-10-26T18:20:00026 October 2011 18:20:00 10 CFR 76.120(c)(2) 24 Hour Report Due to Detection of Linear Defect in Surge Volume Accumulator ENS 469962011-06-28T05:05:00028 June 2011 05:05:00 10 CFR 76.120(c)(2) Failure of #2 Fire Water Pump to Realign ENS 468532011-05-15T17:54:00015 May 2011 17:54:00 10 CFR 76.120(c)(2) Portion of High Pressure Fire Water System Declared Inoperable ENS 458902010-04-30T15:15:00030 April 2010 15:15:00 10 CFR 76.120(c)(2) Tar Found on Overpressure Rupture Discs Potentially Changing the Relief Set Point ENS 458002010-03-29T13:08:00029 March 2010 13:08:00 10 CFR 76.120(c)(2) Safety Equipment Failure - Process Gas Detection System Found Inoperable ENS 456292010-01-13T14:50:00013 January 2010 14:50:00 10 CFR 76.120(c)(2) Process Gas Leak Detection System Inoperable ENS 455272009-11-29T00:50:00029 November 2009 00:50:00 10 CFR 76.120(c)(2) Safety Equipment Disabled Due to a Ground in the Area Control Room Alarm ENS 453652009-09-19T18:23:00019 September 2009 18:23:00 10 CFR 76.120(c)(2) High Voltage Process Gas Leak Detector Rendered Inoperable ENS 453022009-08-26T02:40:00026 August 2009 02:40:00 10 CFR 76.120(c)(2) Autoclave Pressure Relief System Inoperable ENS 448202009-01-31T07:50:00031 January 2009 07:50:00 10 CFR 76.120(c)(2) Loss of Power to Criticality Accident Alarm System Horn ENS 448192009-01-30T18:17:00030 January 2009 18:17:00 10 CFR 76.120(c)(2) 24 Hour Report of Process Gas Leak Detection System Inoperability ENS 447422008-12-27T02:43:00027 December 2008 02:43:00 10 CFR 76.120(c)(2) Process Gas Leak Detection System Inoperable ENS 447052008-12-08T08:19:0008 December 2008 08:19:00 10 CFR 76.120(c)(2) Process Gas Leak Detection System Inoperable ENS 446642008-11-18T09:08:00018 November 2008 09:08:00 10 CFR 76.120(c)(2) Fire Water Sprinkler System Out of Service ENS 446212008-11-01T13:37:0001 November 2008 13:37:00 10 CFR 76.120(c)(2) Process Gas Leak Detection System Not Functioning Correctly ENS 446082008-10-28T13:49:00028 October 2008 13:49:00 10 CFR 76.120(c)(2) Process Gas Leak Detection System Inoperable ENS 445152008-09-23T14:37:00023 September 2008 14:37:00 10 CFR 76.120(c)(2) Safety Equipment Failure Due to Loss of Power ENS 444482008-08-28T16:43:00028 August 2008 16:43:00 10 CFR 76.120(c)(2), Other Unspec Reqmnt Leak in High Pressure Fire Water System ENS 443562008-07-20T17:20:00020 July 2008 17:20:00 10 CFR 76.120(c)(2) Failure of Process Gas Leak Detection System ENS 442022008-05-12T17:30:00012 May 2008 17:30:00 10 CFR 76.120(c)(2) 24-Hr Report - Uf6 Release Detection System Failure ENS 441582008-04-22T14:00:00022 April 2008 14:00:00 10 CFR 76.120(c)(2) Improperly Installed Steel Angle Supports on Freezer Sublimer Vessel ENS 441342008-04-11T00:03:00011 April 2008 00:03:00 10 CFR 76.120(c)(2) Failed Detector Heads ENS 439872008-02-14T08:07:00014 February 2008 08:07:00 10 CFR 76.120(c)(2) Alarm Received from Uf6 Release Detection System ENS 439532008-01-31T20:06:00031 January 2008 20:06:00 10 CFR 76.120(c)(2) 24 Hour Report of Release Detection System Failure ENS 439032008-01-13T21:12:00013 January 2008 21:12:00 10 CFR 76.120(c)(2) Failure of Uf6 Release Detection System ENS 438012007-11-21T02:28:00021 November 2007 02:28:00 10 CFR 76.120(c)(2) Failure of Uf6 Release Detection System ENS 437082007-10-09T22:00:0009 October 2007 22:00:00 10 CFR 76.120(c)(2) Safety System Valve Did Not Operate as Expected ENS 436962007-10-05T21:43:0005 October 2007 21:43:00 10 CFR 76.120(c)(2) Process Gas Leak Detection (Pgld) System Inoperable ENS 436862007-10-02T19:06:0002 October 2007 19:06:00 10 CFR 76.120(c)(2) Release Detection System (Pgld) Declared Inoperable ENS 436702007-09-27T05:12:00027 September 2007 05:12:00 10 CFR 76.120(c)(2) Temporary Loss of Smoke Detector Function ENS 433122007-04-22T08:20:00022 April 2007 08:20:00 10 CFR 76.120(c)(2) Uf6 Release Detection System Inoperable ENS 433052007-04-17T00:15:00017 April 2007 00:15:00 10 CFR 76.120(c)(2) Large Water Leak on High Pressure Fire Water System ENS 432682007-03-30T15:30:00030 March 2007 15:30:00 10 CFR 76.120(c)(2) Safety Equipment Failure - Process Gas Leak Detection System ENS 429732006-11-07T22:07:0007 November 2006 22:07:00 10 CFR 76.120(c)(2) Failure of Process Gas Leak Detection System ENS 429722006-11-07T14:59:0007 November 2006 14:59:00 10 CFR 76.120(c)(2) Process Gas Leak Detector Failure ENS 428662006-09-28T23:02:00028 September 2006 23:02:00 10 CFR 76.120(c)(2) Failure of Autoclave High Cylinder Pressure System ENS 427632006-08-10T22:05:00010 August 2006 22:05:00 10 CFR 76.120(c)(2) Inoperable High Pressure Fire Water System ENS 425902006-05-20T12:15:00020 May 2006 12:15:00 10 CFR 76.120(c)(2) High Pressure Transmitter Failure ENS 424942006-04-12T13:13:00012 April 2006 13:13:00 10 CFR 76.120(c)(2) Uf6 Release Detection System Failed During Testing ENS 422382006-01-02T10:38:0002 January 2006 10:38:00 10 CFR 76.120(c)(2) Report of Safety Equipment Failure ENS 421762005-11-29T14:45:00029 November 2005 14:45:00 10 CFR 76.120(c)(2) Faulty Switch Rendered Criticality Accident Alarm System Inoperable ENS 418822005-07-29T02:25:00029 July 2005 02:25:00 10 CFR 76.120(c)(2) Failure of Safety Equipment on C-310 Cylinder Valve Closure System ENS 413782005-02-06T16:08:0006 February 2005 16:08:00 10 CFR 76.120(c)(2) 24 Hour Report of a Safety Equipment Failure ENS 412442004-12-04T12:50:0004 December 2004 12:50:00 10 CFR 76.120(c)(2) High Pressure Transmitter Failure ENS 412232004-11-23T19:25:00023 November 2004 19:25:00 10 CFR 76.120(c)(2) Failure of Uf6 Release Detection System Due to Loss of Electrical Power ENS 407382004-05-09T06:30:0009 May 2004 06:30:00 10 CFR 76.120(c)(2) Failure of the High Voltage Uf6 Release Detection System ENS 404992004-02-02T10:15:0002 February 2004 10:15:00 10 CFR 76.120(c)(2) Failure of C-360 #1 Autoclave High Pressure Isolation System. ENS 404922004-01-30T15:41:00030 January 2004 15:41:00 10 CFR 76.120(c)(2) Safety Equipment Failure ENS 404382004-01-12T00:00:00012 January 2004 00:00:00 10 CFR 76.120(c)(2) Safety Equipment Fails to Function ENS 404232004-01-02T08:30:0002 January 2004 08:30:00 10 CFR 76.120(c)(2) Failure of Autoclave Isolation System 2014-05-08T15:24:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_43312&oldid=1184204"