StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
| Line 16: | Line 16: | ||
| event date = 12/19/2013 15:11 EST | | event date = 12/19/2013 15:11 EST | ||
| last update date = 02/14/2014 | | last update date = 02/14/2014 | ||
| title = Loss | | title = Loss of Reactor Building Ventilation | ||
| event text = At 1511 [EST] on December 19, 2013, bus 10A404 (D channel 4 kv 1E vital bus) deenergized while transferring infeed breakers after degraded voltage testing. Reactor building ventilation fans tripped resulting in a loss of secondary containment negative pressure. Filtration Recirculation and Ventilation System (FRVS) was manually started and secondary containment negative pressure was restored at 1525 [EST]. | | event text = At 1511 [EST] on December 19, 2013, bus 10A404 (D channel 4 kv 1E vital bus) deenergized while transferring infeed breakers after degraded voltage testing. Reactor building ventilation fans tripped resulting in a loss of secondary containment negative pressure. Filtration Recirculation and Ventilation System (FRVS) was manually started and secondary containment negative pressure was restored at 1525 [EST]. | ||
Secondary containment pressure is stable with differential pressure negative. | Secondary containment pressure is stable with differential pressure negative. | ||
Latest revision as of 20:51, 1 March 2018
| Where | |
|---|---|
| Hope Creek New Jersey (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material | |
| Time - Person (Reporting Time:+-0.88 h-0.0367 days <br />-0.00524 weeks <br />-0.00121 months <br />) | |
| Opened: | Michael Moore 19:18 Dec 19, 2013 |
| NRC Officer: | Dong Park |
| Last Updated: | Feb 14, 2014 |