ENS 49665: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 12/19/2013 15:11 EST
| event date = 12/19/2013 15:11 EST
| last update date = 02/14/2014
| last update date = 02/14/2014
| title = Loss Of Reactor Building Ventilation
| title = Loss of Reactor Building Ventilation
| event text = At 1511 [EST] on December 19, 2013, bus 10A404 (D channel 4 kv 1E vital bus) deenergized while transferring infeed breakers after degraded voltage testing.  Reactor building ventilation fans tripped resulting in a loss of secondary containment negative pressure.  Filtration Recirculation and Ventilation System (FRVS) was manually started and secondary containment negative pressure was restored at 1525 [EST].
| event text = At 1511 [EST] on December 19, 2013, bus 10A404 (D channel 4 kv 1E vital bus) deenergized while transferring infeed breakers after degraded voltage testing.  Reactor building ventilation fans tripped resulting in a loss of secondary containment negative pressure.  Filtration Recirculation and Ventilation System (FRVS) was manually started and secondary containment negative pressure was restored at 1525 [EST].
Secondary containment pressure is stable with differential pressure negative.
Secondary containment pressure is stable with differential pressure negative.

Latest revision as of 20:51, 1 March 2018

ENS 49665 +/-
Where
Hope Creek PSEG icon.png
New Jersey (NRC Region 1)
Reporting
10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material
Time - Person (Reporting Time:+-0.88 h-0.0367 days <br />-0.00524 weeks <br />-0.00121 months <br />)
Opened: Michael Moore
19:18 Dec 19, 2013
NRC Officer: Dong Park
Last Updated: Feb 14, 2014
49665 - NRC Website
Loading map...