ML16341C521: Difference between revisions
StriderTol (talk | contribs) Created page by program invented by StriderTol |
StriderTol (talk | contribs) Created page by program invented by StriderTol |
||
| Line 17: | Line 17: | ||
=Text= | =Text= | ||
{{#Wiki_filter:IINNDDIIAANNAA AANNDD MMIICCHHIIGGAANN PPOOWWEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision: 23Table: 9.10-1 Page: 1 of 1 | {{#Wiki_filter:IINNDDIIAANNAA AANNDD MMIICCHHIIGGAANN PPOOWWEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision: 23Table: 9.10-1 Page: 1 of 1 CONTROL ROOM VENTILATION SYSTEM MALFUNCTION ANALYSIS COMPONENT MALFUNCTION COMMENTS AND CONSEQUENCES | ||
: 1. Normal Intake Dampers Failure to close Two dampers in series ensure isolation of outside air normal intake. | |||
Failure to open Parallel dampers ensure outside air intake opens. 2. Pressurization/Cleanup Intake Dampers Fully open or multiple dampers | |||
open One damper partially open is correct alignment. A single failure may result in one damper fully open or 2 dampers partially open. Other failures are not | |||
considered credible. 3. Pressurization/Cleanup Recirculation Damper Failed to closed position All air flowing through the filter is from the intake and air cleanup is limited to a single pass. Control Room dose consequences may increase. The position of the recirculation damper is administratively controlled so it does not | |||
need to change position in response to a | |||
radiological accident.}} | |||
Revision as of 02:11, 30 June 2018
| ML16341C521 | |
| Person / Time | |
|---|---|
| Site: | Cook |
| Issue date: | 10/24/2016 |
| From: | Indiana Michigan Power Co |
| To: | Office of Nuclear Reactor Regulation |
| Shared Package | |
| ML16336A263 | List:
|
| References | |
| AEP-NRC-2016-42 | |
| Download: ML16341C521 (1) | |
Text
IINNDDIIAANNAA AANNDD MMIICCHHIIGGAANN PPOOWWEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision: 23Table: 9.10-1 Page: 1 of 1 CONTROL ROOM VENTILATION SYSTEM MALFUNCTION ANALYSIS COMPONENT MALFUNCTION COMMENTS AND CONSEQUENCES
- 1. Normal Intake Dampers Failure to close Two dampers in series ensure isolation of outside air normal intake.
Failure to open Parallel dampers ensure outside air intake opens. 2. Pressurization/Cleanup Intake Dampers Fully open or multiple dampers
open One damper partially open is correct alignment. A single failure may result in one damper fully open or 2 dampers partially open. Other failures are not
considered credible. 3. Pressurization/Cleanup Recirculation Damper Failed to closed position All air flowing through the filter is from the intake and air cleanup is limited to a single pass. Control Room dose consequences may increase. The position of the recirculation damper is administratively controlled so it does not
need to change position in response to a
radiological accident.