ENS 41527: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 16: | Line 16: | ||
| event date = 03/26/2005 03:00 CST | | event date = 03/26/2005 03:00 CST | ||
| last update date = 03/27/2005 | | last update date = 03/27/2005 | ||
| title = Technical Specification Required Shutdown Due | | title = Technical Specification Required Shutdown Due to Inoperable Esw Train. | ||
| event text = The following information was faxed by the licensee: | | event text = The following information was faxed by the licensee: | ||
At 0300, 3/23/05, 72-hour Technical Specification Action 3.7.8.A was entered when a pinhole leak was discovered in 'B' Essential Service Water (ESW). Subsequent ultrasonic testing (UT) determined that approximately seven linear feet of piping in the 'B' ESW train was affected and required replacement. UT testing was satisfactorily performed on the 'A' ESW train to ensure a similar problem did not exist. | At 0300, 3/23/05, 72-hour Technical Specification Action 3.7.8.A was entered when a pinhole leak was discovered in 'B' Essential Service Water (ESW). Subsequent ultrasonic testing (UT) determined that approximately seven linear feet of piping in the 'B' ESW train was affected and required replacement. UT testing was satisfactorily performed on the 'A' ESW train to ensure a similar problem did not exist. |
Latest revision as of 21:21, 1 March 2018
Where | |
---|---|
Callaway Missouri (NRC Region 4) | |
Reporting | |
10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown | |
LER: | 05000483/LER-2005-002 |
Time - Person (Reporting Time:+-10.25 h-0.427 days <br />-0.061 weeks <br />-0.014 months <br />) | |
Opened: | Hope Bradley 22:45 Mar 25, 2005 |
NRC Officer: | John Knoke |
Last Updated: | Mar 27, 2005 |
41527 - NRC Website
| |