Line 16: Line 16:
| event date = 03/17/2016 15:15 CDT
| event date = 03/17/2016 15:15 CDT
| last update date = 03/17/2016
| last update date = 03/17/2016
| title = Valid Engineered Safety Feature System Actuation Due To Lightning Strike
| title = Valid Engineered Safety Feature System Actuation Due to Lightning Strike
| event text = At 1515 [CDT] on March 17th 2016, Grand Gulf Nuclear Station received a valid actuation signal of the Division 2 Engineered Safety Feature (ESF) Load Shedding and Sequencing system. The actuation signal was most likely caused by a lightning strike to the offsite power source supplying this ESF bus. This caused a loss of the in service shutdown cooling system and associated system actuations.
| event text = At 1515 [CDT] on March 17th 2016, Grand Gulf Nuclear Station received a valid actuation signal of the Division 2 Engineered Safety Feature (ESF) Load Shedding and Sequencing system. The actuation signal was most likely caused by a lightning strike to the offsite power source supplying this ESF bus. This caused a loss of the in service shutdown cooling system and associated system actuations.
Grand Gulf Nuclear Station (GGNS) was in Mode 5 at 85 [degrees] F coolant temperature. Reactor Cavity was flooded to High Water Level with a time to reach 200 [degrees] F of 7.5hrs. GGNS is conducting a planned refuel outage with core alterations in progress. Systems were aligned as follows:
Grand Gulf Nuclear Station (GGNS) was in Mode 5 at 85 [degrees] F coolant temperature. Reactor Cavity was flooded to High Water Level with a time to reach 200 [degrees] F of 7.5hrs. GGNS is conducting a planned refuel outage with core alterations in progress. Systems were aligned as follows:

Latest revision as of 21:45, 1 March 2018

ENS 51800 +/-
Where
Grand Gulf Entergy icon.png
Mississippi (NRC Region 4)
Reporting
10 CFR 50.72(b)(3)(iv)(A), System Actuation

10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat
LER: 05000416/LER-2016-001
Time - Person (Reporting Time:+3 h0.125 days <br />0.0179 weeks <br />0.00411 months <br />)
Opened: Sean Dunfee
23:15 Mar 17, 2016
NRC Officer: Steven Vitto
Last Updated: Mar 17, 2016
51800 - NRC Website