| event date = 12/15/2016 04:10 MST
| event date = 12/15/2016 04:10 MST
| last update date = 12/15/2016
| last update date = 12/15/2016
| title = Alert Declared - Catastrophic Failure Of An Emergency Diesel Generator
| title = Alert Declared - Catastrophic Failure of an Emergency Diesel Generator
| event text = The following event description is based on information currently available.  If through subsequent reviews of this event additional information is identified that is pertinent to this event or alters the information being provided at this time a follow-up notification will be made via the ENS or under the reporting requirements of 10CFR50.73.
| event text = The following event description is based on information currently available.  If through subsequent reviews of this event additional information is identified that is pertinent to this event or alters the information being provided at this time a follow-up notification will be made via the ENS or under the reporting requirements of 10CFR50.73.
During a scheduled surveillance test run of the PVNGS [Palo Verde Nuclear Generating Station] Unit 3 'B' Train Emergency Diesel Generator, there was a catastrophic failure of a piston to include crankcase damage and diesel trip.  The Emergency Plan has been entered and an ALERT was declared at 0410 [MST] on 12/15/16 based on an explosion resulting in visible damage to a safety system required for safe shutdown.  The cause of the failure is unknown at this time.  PVNGS Fire Department responded and no fire was observed.  Unit 3 remains on line at 100% power. No other safety functions are impacted.
During a scheduled surveillance test run of the PVNGS [Palo Verde Nuclear Generating Station] Unit 3 'B' Train Emergency Diesel Generator, there was a catastrophic failure of a piston to include crankcase damage and diesel trip.  The Emergency Plan has been entered and an ALERT was declared at 0410 [MST] on 12/15/16 based on an explosion resulting in visible damage to a safety system required for safe shutdown.  The cause of the failure is unknown at this time.  PVNGS Fire Department responded and no fire was observed.  Unit 3 remains on line at 100% power. No other safety functions are impacted.

Latest revision as of 21:43, 1 March 2018

ENS 52435 +/-
Where
Palo Verde Arizona Public Service icon.png
Arizona (NRC Region 4)
Reporting
Emergency class: Alert
10 CFR 50.72(a) (1) (i), Emergency Class Declaration
Time - Person (Reporting Time:+-4.25 h-0.177 days <br />-0.0253 weeks <br />-0.00582 months <br />)
Opened: Andrew Liston
06:55 Dec 15, 2016
NRC Officer: Mark Abramovitz
Last Updated: Dec 15, 2016
52435 - NRC Website