Line 16: Line 16:
| event date = 07/10/2017 02:50 EDT
| event date = 07/10/2017 02:50 EDT
| last update date = 07/10/2017
| last update date = 07/10/2017
| title = Loss Of Secondary Containment Due To Failure Of Non-Safety Related Discharge Damper
| title = Loss of Secondary Containment Due to Failure of Non-Safety Related Discharge Damper
| event text = On July 10th, 2017 at 0250 hrs. [EDT] a loss of secondary containment differential pressure (D/P) occurred due to failure of a non-safety related discharge damper associated with 2V205B Reactor Building Zone II Exhaust Fan.  This caused a reduction in Reactor Building Zone II (Unit 2) D/P to less than the required 0.25 inches WC [Water Column].  
| event text = On July 10th, 2017 at 0250 hrs. [EDT] a loss of secondary containment differential pressure (D/P) occurred due to failure of a non-safety related discharge damper associated with 2V205B Reactor Building Zone II Exhaust Fan.  This caused a reduction in Reactor Building Zone II (Unit 2) D/P to less than the required 0.25 inches WC [Water Column].  
2V205A Reactor Building Zone II Exhaust Fan was manually started and Reactor Building Zone II D/P was restored to greater than 0.25 inches WC by 0301 hrs.  
2V205A Reactor Building Zone II Exhaust Fan was manually started and Reactor Building Zone II D/P was restored to greater than 0.25 inches WC by 0301 hrs.  

Latest revision as of 20:42, 1 March 2018

ENS 52844 +/-
Where
Susquehanna Talen Energy icon.png
Pennsylvania (NRC Region 1)
Reporting
10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material
LER: 05000388/LER-2017-006
Time - Person (Reporting Time:+0.75 h0.0313 days <br />0.00446 weeks <br />0.00103 months <br />)
Opened: Steven Koch
07:35 Jul 10, 2017
NRC Officer: Steve Sandin
Last Updated: Jul 10, 2017
52844 - NRC Website