ENS 52892: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 08/08/2017 20:44 EDT
| event date = 08/08/2017 20:44 EDT
| last update date = 08/08/2017
| last update date = 08/08/2017
| title = Loss Of Secondary Containment Differential Pressure
| title = Loss of Secondary Containment Differential Pressure
| event text = On August 8th, 2017 at 2044 hrs. [EDT] a loss of secondary containment differential pressure (D/P) occurred due to an apparent equipment failure.  This caused a reduction in Reactor Building Zone II (Unit 2) D/P to less than the required 0.25 inch WC [water column] per SR [Surveillance Requirement] 3.6.4.1.1.  
| event text = On August 8th, 2017 at 2044 hrs. [EDT] a loss of secondary containment differential pressure (D/P) occurred due to an apparent equipment failure.  This caused a reduction in Reactor Building Zone II (Unit 2) D/P to less than the required 0.25 inch WC [water column] per SR [Surveillance Requirement] 3.6.4.1.1.  
Reactor Building Zone II Exhaust Fans were manually swapped and Reactor Building Zone II D/P was restored to greater than 0.25 inch WC by 2112 hrs.  
Reactor Building Zone II Exhaust Fans were manually swapped and Reactor Building Zone II D/P was restored to greater than 0.25 inch WC by 2112 hrs.  

Latest revision as of 20:42, 1 March 2018

ENS 52892 +/-
Where
Susquehanna Talen Energy icon.png
Pennsylvania (NRC Region 1)
Reporting
10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material
Time - Person (Reporting Time:+-2.18 h-0.0908 days <br />-0.013 weeks <br />-0.00299 months <br />)
Opened: Ronald Fry
22:33 Aug 8, 2017
NRC Officer: Dong Park
Last Updated: Aug 8, 2017
52892 - NRC Website
Loading map...