ML19254E584: Difference between revisions
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 18: | Line 18: | ||
=Text= | =Text= | ||
{{#Wiki_filter:. | {{#Wiki_filter:. | ||
8 .. | 8 .. | ||
STATE OF ILLINOIS ) | STATE OF ILLINOIS ) | ||
) SS. ' | ) SS. ' | ||
Line 28: | Line 24: | ||
AFFIDAVIT OF MELVIN S. ABRAMS MELVIN S. ABRAMS, being first duly sworn according to law comes forward and states: | AFFIDAVIT OF MELVIN S. ABRAMS MELVIN S. ABRAMS, being first duly sworn according to law comes forward and states: | ||
: 1. My name is Melvin S. Abrams. I am employed as Director, Fire Research Department, Portiand Cement Associa-tion at the Construction Technology Laboratories located in Skokie, Illinois. " | : 1. My name is Melvin S. Abrams. I am employed as Director, Fire Research Department, Portiand Cement Associa-tion at the Construction Technology Laboratories located in Skokie, Illinois. " | ||
: 2. I received a Bachelor of Science Degree in Mathematics from Illinois Institute of Technology in 1955. In 1958 I took graduate courses in the field of mechanics. From 1949 to the present time, I have been employed by the Portland Cement Association. For the past 20 years, I have been a member of the Fire Research Section and have managed the section since 1970. In this position I have carried out a number of fire test research programs. During the.past 10 years, an important part of my work has been the inspection, evaluation and recommendations for repair of numerous fire | : 2. I received a Bachelor of Science Degree in Mathematics from Illinois Institute of Technology in 1955. In 1958 I took graduate courses in the field of mechanics. From 1949 to the present time, I have been employed by the Portland Cement Association. For the past 20 years, I have been a member of the Fire Research Section and have managed the section since 1970. In this position I have carried out a number of fire test research programs. During the.past 10 years, an important part of my work has been the inspection, evaluation and recommendations for repair of numerous fire damaged structures, including nuclear facilities. I am a member of the American Society of Testing and Materials, the American Concrete Institute and the National Fire Protection .. | ||
damaged structures, including nuclear facilities. I am a member of the American Society of Testing and Materials, the American Concrete Institute and the National Fire Protection .. | |||
Association and am a member of several committees in these i283 l34 79110106/0 | Association and am a member of several committees in these i283 l34 79110106/0 | ||
. .- . organizations dealing with fire test methods, fire resistance and fire protection. | . .- . organizations dealing with fire test methods, fire resistance and fire protection. | ||
: 3. In my position as Director of the Fire Research Department, I directed and witnessed the fire protective cable tray fire test to evaluate the performance of thermal insulation material as a fire shield to protect electrical continuity of cables which was sponsored in part by The Cincinnati Gas & Electric Company, Dayton Power and Light Company and Columbus and Southern Ohio Electric Company. I prepared the resulting " Fire Protective Cable Tray Fire Test Report" ("CTL Report") dated June 1979. The materials utilized, the test equipr.ent, the installation of the specimens in the furnace, the conduct of the test, the test results, including observations during and after the test, are com-pletely described in the Report. This Report is true and correct to the best of my knowledge, information and belief, and I incorporate it into this affidavit by reference. | : 3. In my position as Director of the Fire Research Department, I directed and witnessed the fire protective cable tray fire test to evaluate the performance of thermal insulation material as a fire shield to protect electrical continuity of cables which was sponsored in part by The Cincinnati Gas & Electric Company, Dayton Power and Light Company and Columbus and Southern Ohio Electric Company. I prepared the resulting " Fire Protective Cable Tray Fire Test Report" ("CTL Report") dated June 1979. The materials utilized, the test equipr.ent, the installation of the specimens in the furnace, the conduct of the test, the test results, including observations during and after the test, are com-pletely described in the Report. This Report is true and correct to the best of my knowledge, information and belief, and I incorporate it into this affidavit by reference. | ||
: 4. In summary, the following are my conclusions applicable to the present contention regarding the cable trays insulated with three one-inch layers of Kaowool which were s'ubjected to a fire exposure corresponding to ASTM designation E119-79: | : 4. In summary, the following are my conclusions applicable to the present contention regarding the cable trays insulated with three one-inch layers of Kaowool which were s'ubjected to a fire exposure corresponding to ASTM designation E119-79: | ||
: 1. Wrapping cable trays with three 1-in. | : 1. Wrapping cable trays with three 1-in. | ||
layers of Kaowool blanket thermal in-sulation protected the circuit continuity | layers of Kaowool blanket thermal in-sulation protected the circuit continuity 1283 135 | ||
1283 135 | |||
of cables in the trays for 94 min. No short circuits were indicated on the light panel or by meggering before that time. | of cables in the trays for 94 min. No short circuits were indicated on the light panel or by meggering before that time. | ||
: 2. No short circuits occurred at a cable jacket temperature of 200C (392F), which is considered as the maximun con-tinuous service temperature for maintaining continuity of this type of cable jacketing. | : 2. No short circuits occurred at a cable jacket temperature of 200C (392F), which is considered as the maximun con-tinuous service temperature for maintaining continuity of this type of cable jacketing. | ||
: 3. Cable Tray 1 was removed from the furnace 30 min. after the end of the test. At this time, temperatures of the cables had increased about 50F over those at end of test. Cables were inspected visually, and it was determined that no damage occurred to cable jacketing material. | : 3. Cable Tray 1 was removed from the furnace 30 min. after the end of the test. At this time, temperatures of the cables had increased about 50F over those at end of test. Cables were inspected visually, and it was determined that no damage occurred to cable jacketing material. | ||
: 4. Tray 4 was removed from the furnace | : 4. Tray 4 was removed from the furnace about 3 1/2 hr. after the test was terminated. Temperatures of the cables continued to rise from 100 to 200F for about 1 1/2 hr. after the test was terminated. When the tray was removed, some cable temperatures were still about i283 i36 | ||
about 3 1/2 hr. after the test was terminated. Temperatures of the cables continued to rise from 100 to 200F for about 1 1/2 hr. after the test was terminated. When the tray was removed, some cable temperatures were still about i283 i36 | |||
. the same as those at end of test. A visual inspection of cables indicated that there was some softening of jacket material. However, one such cable was meggered and found to have circuit continuity. | . the same as those at end of test. A visual inspection of cables indicated that there was some softening of jacket material. However, one such cable was meggered and found to have circuit continuity. | ||
','9fM'm Sh&s" Melvin S. Abrams Sworn and subscribed to before me this day of 1979. | ','9fM'm Sh&s" Melvin S. Abrams Sworn and subscribed to before me this day of 1979. | ||
Notary Public My Commission expires . | Notary Public My Commission expires . | ||
1283 137 | 1283 137 | ||
.}} | .}} |
Latest revision as of 00:03, 2 February 2020
ML19254E584 | |
Person / Time | |
---|---|
Site: | Zimmer |
Issue date: | 09/28/1979 |
From: | Abrams M PORTLAND CEMENT ASSOCIATION |
To: | |
Shared Package | |
ML19254E583 | List: |
References | |
NUDOCS 7911010510 | |
Download: ML19254E584 (4) | |
Text
.
8 ..
STATE OF ILLINOIS )
) SS. '
COOK COUNTY )
AFFIDAVIT OF MELVIN S. ABRAMS MELVIN S. ABRAMS, being first duly sworn according to law comes forward and states:
- 1. My name is Melvin S. Abrams. I am employed as Director, Fire Research Department, Portiand Cement Associa-tion at the Construction Technology Laboratories located in Skokie, Illinois. "
- 2. I received a Bachelor of Science Degree in Mathematics from Illinois Institute of Technology in 1955. In 1958 I took graduate courses in the field of mechanics. From 1949 to the present time, I have been employed by the Portland Cement Association. For the past 20 years, I have been a member of the Fire Research Section and have managed the section since 1970. In this position I have carried out a number of fire test research programs. During the.past 10 years, an important part of my work has been the inspection, evaluation and recommendations for repair of numerous fire damaged structures, including nuclear facilities. I am a member of the American Society of Testing and Materials, the American Concrete Institute and the National Fire Protection ..
Association and am a member of several committees in these i283 l34 79110106/0
. .- . organizations dealing with fire test methods, fire resistance and fire protection.
- 3. In my position as Director of the Fire Research Department, I directed and witnessed the fire protective cable tray fire test to evaluate the performance of thermal insulation material as a fire shield to protect electrical continuity of cables which was sponsored in part by The Cincinnati Gas & Electric Company, Dayton Power and Light Company and Columbus and Southern Ohio Electric Company. I prepared the resulting " Fire Protective Cable Tray Fire Test Report" ("CTL Report") dated June 1979. The materials utilized, the test equipr.ent, the installation of the specimens in the furnace, the conduct of the test, the test results, including observations during and after the test, are com-pletely described in the Report. This Report is true and correct to the best of my knowledge, information and belief, and I incorporate it into this affidavit by reference.
- 4. In summary, the following are my conclusions applicable to the present contention regarding the cable trays insulated with three one-inch layers of Kaowool which were s'ubjected to a fire exposure corresponding to ASTM designation E119-79:
- 1. Wrapping cable trays with three 1-in.
layers of Kaowool blanket thermal in-sulation protected the circuit continuity 1283 135
of cables in the trays for 94 min. No short circuits were indicated on the light panel or by meggering before that time.
- 2. No short circuits occurred at a cable jacket temperature of 200C (392F), which is considered as the maximun con-tinuous service temperature for maintaining continuity of this type of cable jacketing.
- 3. Cable Tray 1 was removed from the furnace 30 min. after the end of the test. At this time, temperatures of the cables had increased about 50F over those at end of test. Cables were inspected visually, and it was determined that no damage occurred to cable jacketing material.
- 4. Tray 4 was removed from the furnace about 3 1/2 hr. after the test was terminated. Temperatures of the cables continued to rise from 100 to 200F for about 1 1/2 hr. after the test was terminated. When the tray was removed, some cable temperatures were still about i283 i36
. the same as those at end of test. A visual inspection of cables indicated that there was some softening of jacket material. However, one such cable was meggered and found to have circuit continuity.
','9fM'm Sh&s" Melvin S. Abrams Sworn and subscribed to before me this day of 1979.
Notary Public My Commission expires .