| event date = 10/26/2018 00:00 EDT
| event date = 10/26/2018 00:00 EDT
| last update date = 10/27/2018
| last update date = 10/27/2018
| title =  
| title = Automatic Start of the Emergency Diesel Generator and Loss of Radiation Monitor
| event text =  
| event text = RCS [Reactor Coolant System] Pressure: vented to containment, refueling cavity greater than 23ft. [above reactor vessel]. RCS temperature: 96 degrees Fahrenheit.
The 12A bus de-energized, 'A' EDG [Emergency Diesel Generator] automatically started and loaded on [emergency] buses 14 and 18. The RCS configuration is refueling cavity level greater than 23ft. above the reactor flange with no impact to shutdown cooling.
Radiation monitor R-1, Control Room radiation monitor, lost power for 2 hrs 10 min. This placed Ginna in a major loss of emergency preparedness capabilities. A temporary radiation monitor has been installed in the Control Room.
Prior to the notification, the licensee had restored the 12A bus from offsite power and the R-1 monitor was re-energized.
The licensee notified the NRC Resident Inspector.
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2018/20181029en.html#en53696
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2018/20181029en.html#en53696
}}{{unit info
}}{{unit info

Latest revision as of 12:17, 30 October 2018

ENS 53696 +/-
Where
Ginna Constellation icon.png
New York (NRC Region 1)
Reporting
10 CFR 50.72(b)(3)(iv)(A), System Actuation

10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness
Time - Person (Reporting Time:+21.83 h0.91 days <br />0.13 weeks <br />0.0299 months <br />)
Opened: Wade Weber
01:50 Oct 27, 2018
NRC Officer: Ossy Font
Last Updated: Oct 27, 2018
53696 - NRC Website