05000331/FIN-2018010-02: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 5: | Line 5: | ||
| finding integer = 02 | | finding integer = 02 | ||
| quarter = 2018Q1 | | quarter = 2018Q1 | ||
| IR section = NO | | IR section = NO SECTION | ||
| finding type = NCV | | finding type = NCV | ||
| significance = | | significance = Green | ||
| cornerstone = Mitigating Systems | | cornerstone = Mitigating Systems | ||
| violation of = 10 CFR 50.48 | | violation of = 10 CFR 50.48 | ||
| identified by = NRC | | identified by = NRC | ||
| Inspection procedure = IP | | Inspection procedure = IP 71111.05T | ||
| Inspector = | | Inspector = A Dahbur, I Hafeez, J Patel, R Daley | ||
| CCA = | | CCA = | ||
| INPO aspect = | | INPO aspect = | ||
| description = The inspectors identified a finding of very-low safety significance (Green), and associated Non-Cited ViolationofTitle10 of the Code of Federal Regulations, Part 50.48(c), and NFPA805, Section 4.2.4.1.6,Operations Guidance. Specifically, during the transition process to NFPA 805, performance-based standard fortheFire Protection Program, the licensee inadvertently removed a required operator action in the control room from plant operating procedure AOP 913, Fire. | | description = The inspectors identified a finding of very-low safety significance (Green), and associated Non-Cited ViolationofTitle10 of the Code of Federal Regulations, Part 50.48(c), and NFPA805, Section 4.2.4.1.6,Operations Guidance. Specifically, during the transition process to NFPA 805, performance-based standard fortheFire Protection Program, the licensee inadvertently removed a required operator action in the control room from plant operating procedure AOP 913, Fire. | ||
}} | }} |
Latest revision as of 08:00, 30 May 2018
Site: | Duane Arnold |
---|---|
Report | IR 05000331/2018010 Section NO SECTION |
Date counted | Mar 31, 2018 (2018Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05T |
Inspectors (proximate) | A Dahbur I Hafeez J Patel R Daley |
Violation of: | 10 CFR 50.48 |
INPO aspect | |
' | |