05000331/FIN-2018010-02: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
 
(Created page by program invented by StriderTol)
 
Line 5: Line 5:
| finding integer = 02
| finding integer = 02
| quarter = 2018Q1
| quarter = 2018Q1
| IR section = NO CC AREA
| IR section = NO SECTION
| finding type = NCV
| finding type = NCV
| significance =  
| significance = Green
| cornerstone = Mitigating Systems
| cornerstone = Mitigating Systems
| violation of = 10 CFR 50.48
| violation of = 10 CFR 50.48
| identified by = NRC
| identified by = NRC
| Inspection procedure = IP NO SECTION
| Inspection procedure = IP 71111.05T
| Inspector = 71111.05
| Inspector = A Dahbur, I Hafeez, J Patel, R Daley
| CCA = N/A for ROP
| CCA =  
| INPO aspect = NO SL
| INPO aspect =  
| description = The inspectors identified a finding of very-low safety significance (Green), and associated Non-Cited ViolationofTitle10 of the Code of Federal Regulations, Part 50.48(c), and NFPA805, Section 4.2.4.1.6,Operations Guidance.  Specifically, during the transition process to NFPA 805, performance-based standard fortheFire Protection Program, the licensee inadvertently removed a required operator action in the control room from plant operating procedure AOP 913, Fire.
| description = The inspectors identified a finding of very-low safety significance (Green), and associated Non-Cited ViolationofTitle10 of the Code of Federal Regulations, Part 50.48(c), and NFPA805, Section 4.2.4.1.6,Operations Guidance.  Specifically, during the transition process to NFPA 805, performance-based standard fortheFire Protection Program, the licensee inadvertently removed a required operator action in the control room from plant operating procedure AOP 913, Fire.
}}
}}

Latest revision as of 08:00, 30 May 2018

02
Site: Duane Arnold NextEra Energy icon.png
Report IR 05000331/2018010 Section NO SECTION
Date counted Mar 31, 2018 (2018Q1)
Type: NCV: Green
cornerstone Mitigating Systems
Identified by: NRC identified
Inspection Procedure: IP 71111.05T
Inspectors (proximate) A Dahbur
I Hafeez
J Patel
R Daley
Violation of: 10 CFR 50.48
INPO aspect
'