05000445/FIN-2018001-03: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
 
(Created page by program invented by StriderTol)
 
Line 5: Line 5:
| finding integer = 03
| finding integer = 03
| quarter = 2018Q1
| quarter = 2018Q1
| IR section = NO CC AREA
| IR section = 1R12
| finding type = NCV
| finding type = NCV
| significance =  
| significance = Green
| cornerstone = Mitigating Systems
| cornerstone = Mitigating Systems
| violation of = Technical Specification
| violation of = Technical Specification
| identified by = NRC
| identified by = NRC
| Inspection procedure = IP 1R12
| Inspection procedure = IP 71111.12
| Inspector = 71111.1
| Inspector = J Josey, R Kumana, I Anchondo, E Uribe, M Haire
| CCA = N/A for ROP
| CCA =  
| INPO aspect = NO SL
| INPO aspect =  
| description = The inspectors identified a Green,non-cited violation of Technical Specification 5.4.1, Procedures, associated with the licensees failure to provide procedures appropriate to the circumstances.  Specifically, station procedure INC-2085, Rework and Replacement of I&C Equipment, did not contain adequate instructions for wiring current to pressure (I/P) converters for safety related components which resulted in the steam generator atmospheric relief valve I/P converters being placed in a seismically unqualified configuration.  This finding was entered into the licensees corrective action program as Condition Report CR-2017-011922.
| description = The inspectors identified a Green,non-cited violation of Technical Specification 5.4.1, Procedures, associated with the licensees failure to provide procedures appropriate to the circumstances.  Specifically, station procedure INC-2085, Rework and Replacement of I&C Equipment, did not contain adequate instructions for wiring current to pressure (I/P) converters for safety related components which resulted in the steam generator atmospheric relief valve I/P converters being placed in a seismically unqualified configuration.  This finding was entered into the licensees corrective action program as Condition Report CR-2017-011922.
}}
}}

Latest revision as of 08:00, 30 May 2018

03
Site: Comanche Peak Luminant icon.png
Report IR 05000445/2018001 Section 1R12
Date counted Mar 31, 2018 (2018Q1)
Type: NCV: Green
cornerstone Mitigating Systems
Identified by: NRC identified
Inspection Procedure: IP 71111.12
Inspectors (proximate) J Josey
R Kumana
I Anchondo
E Uribe
M Haire
Violation of: Technical Specification