ML20207L814: Difference between revisions

From kanterella
Jump to navigation Jump to search
StriderTol Bot change
StriderTol Bot change
 
(One intermediate revision by the same user not shown)
Line 18: Line 18:


=Text=
=Text=
{{#Wiki_filter:.   .
{{#Wiki_filter:.
                                    U.S. NUCLEAR REGULATOR COMMISSION
.
                                                    REGION III
U.S. NUCLEAR REGULATOR COMMISSION
        Reports No. 50-266/86021(DRS); 50-301/86018(DRS)
REGION III
        Docket Nos. 50-266; 50-301                                 Licenses No. DPR-24; DRP-27
Reports No. 50-266/86021(DRS); 50-301/86018(DRS)
        Licensee: Wisconsin Electric Power Company
Docket Nos. 50-266; 50-301
                    231 West Michigan
Licenses No. DPR-24; DRP-27
                    Milwaukee, Wisconsin 53203
Licensee: Wisconsin Electric Power Company
        Facility Name:     Point Beach Units 1 and 2
231 West Michigan
        Inspection At:     Two Creeks, Wisconsin
Milwaukee, Wisconsin 53203
        Inspection Conducted:       September 26, through December 11, 1986
Facility Name:
        Inspectors:         MkNz     h                                         /[6/77
Point Beach Units 1 and 2
                                                                                Date
Inspection At:
                                                                                  /lflH
Two Creeks, Wisconsin
                                                                                Date
Inspection Conducted:
                      %             -
September 26, through December 11, 1986
                                        A-
Inspectors:
        Approved By:   M.A. Ring,Chieh                                             '/4[b
MkNz
                        Test Programs Section                                   Dats
h
        Inspection Summary
/[6/77
        Inspection on September 26 through December 11, 1986 (Reports No. 50-266/86021(DRS);
Date
        No. 50-301/86018(ORS))
/lflH
        Areas Inspected:       Routine announced inspection by Region III based inspectors
Date
        of the containment integrated leak rate test (CILRT) procedure, CILRT
%
        performance witnessing; CILRT results; local leak rate test (Type B and C)
-
        procedure and results. NRC modules utilized during this inspection included
A-
        70307, 70313, 70323 and 61720.
Approved By:
        Results: One violation was identified (failure to follow the requirements of
M.A. Ring,Chieh
        Appendix J - Paragraph 7.a.(3)).
'/4[b
Test Programs Section
Dats
Inspection Summary
Inspection on September 26 through December 11, 1986 (Reports No. 50-266/86021(DRS);
No. 50-301/86018(ORS))
Areas Inspected:
Routine announced inspection by Region III based inspectors
of the containment integrated leak rate test (CILRT) procedure, CILRT
performance witnessing; CILRT results; local leak rate test (Type B and C)
procedure and results.
NRC modules utilized during this inspection included
70307, 70313, 70323 and 61720.
Results:
One violation was identified (failure to follow the requirements of
Appendix J - Paragraph 7.a.(3)).
,
,
        8701120357 8701o7
8701120357 8701o7
        gDR     ADOCK 05000266
gDR
                              PDR
ADOCK 05000266
PDR
i
i
!
!
    .
.
5
5
                                                                                              - - - - - +
, -
              , -      ---e       e   ,     . - ,-       m   -,.           --
---e
e
,
. - ,-
m
-,.
--
- - - - - +


            -                             ,                                   .           . - . - ..                           .                   .     . _-     . - -.. .
-
      - ..            .
,
                    .
.
                                                                                                          DETAILS
. - . - ..
.
.
. _-
. - -.. .
- ..
.
.
.
                          1.-                 Persons. Contacted
DETAILS
b                                                                                                                                                                                                     .
1.-
                                            Wisconsin Electric Power Company
Persons. Contacted
.
b
.
Wisconsin Electric Power Company
:
:
                                            +*J. J. Zach, Manager
+*J. J. Zach, Manager
                                              +C. Krause, Senior Project Engineer                                                                                                                   +
+C. Krause, Senior Project Engineer
                                            +*S.   W. Pullins, ISI Engineer
+
                                              +A. Reimer,. Superintendent, Plant Engineer
+*S. W. Pullins, ISI Engineer
                                            +*S.'R. Sherwood, Engineer, Nuclear
+A. Reimer,. Superintendent, Plant Engineer
                                              +J. Knorr,-Regulatory Engineer
+*S.'R. Sherwood, Engineer, Nuclear
+J. Knorr,-Regulatory Engineer
*F. A. Fluetje, Administrative Specialist
i
i
'
'
                                              *F. A. Fluetje, Administrative Specialist
+R. Fromm, Modifications Engineer
                                              +R.   Fromm, Modifications Engineer
+D. Kohn, Engineer
                                              +D.   Kohn, Engineer
Bechtel Corporation
                                            Bechtel Corporation
)
)                                           *L.-Young, Engineering Specialist
*L.-Young, Engineering Specialist
                      1
B. Patel, Engineering Specialist
                                              B. Patel, Engineering Specialist
1
                                              R. Blum, Engineering Specialist
R. Blum, Engineering Specialist
                                          ?Volumetrics,Inc.
?Volumetrics,Inc.
,.                                            D. H. Peyvan, Project Engineer
D. H. Peyvan, Project Engineer
,.
:-
:-
                                            * Denotes persons attending the preliminary exit meeting of October 2, 1986.
* Denotes persons attending the preliminary exit meeting of October 2, 1986.
                                            + Denotes persons in attendance during the telephone conference call of
+ Denotes persons in attendance during the telephone conference call of
December 11, 1986.
,
,
                                              December 11, 1986.
I
I                                            The inspectors also contacted other licensee personnel including                                                                                         i
The inspectors also contacted other licensee personnel including
                                            members of the technical, operating and regulatory assurance staff.
i
                                            Licensee Action on Previous Inspection Findings
members of the technical, operating and regulatory assurance staff.
#
#
                      2.
2.
Licensee Action on Previous Inspection Findings
'
'
                                            a.     (0 pen) Open Item (266/84005-01):                                     This item involved an inspector
a.
                                                    observation that the licensee had not established controls for the                                                                               '
(0 pen) Open Item (266/84005-01):
                                                    assignment of and changes to the weighting factors for the RTDs or
This item involved an inspector
                                                    dowcells. During a review of the licensee's integrated leak rate
observation that the licensee had not established controls for the
                                                    test (ILRT) procedure, the inspector observed that assignment of and
'
'
                                                  -changes'to the weighting factors were still not included in the ILRT                                                                             l
assignment of and changes to the weighting factors for the RTDs or
                                                    procedure. The licensee personcel indicated they were in the                                                                                     :
dowcells.
                                                    process of reviewing the matter but had not documented their proposed
During a review of the licensee's integrated leak rate
,                                                  action to establish controls for the assignment of weighting factors.
test (ILRT) procedure, the inspector observed that assignment of and
                                                    This item remains.open pending licensee action.
-changes'to the weighting factors were still not included in the ILRT
                                            b.     (0 pen) Open Item (266/84005-02):                                     This item involved inspector                                               4
l
                                                    determination that the licensee's ILRT procedure had not established
'
                                                    data rejection criteria for outlying observations in the collection
procedure.
                                                    of data. Consequently, the licensee would not have a technical basis
The licensee personcel indicated they were in the
                                                    to reject erroneous data resulting from human or instrument error.
:
                                                                                                              2
process of reviewing the matter but had not documented their proposed
action to establish controls for the assignment of weighting factors.
,
This item remains.open pending licensee action.
b.
(0 pen) Open Item (266/84005-02):
This item involved inspector
4
determination that the licensee's ILRT procedure had not established
data rejection criteria for outlying observations in the collection
of data.
Consequently, the licensee would not have a technical basis
to reject erroneous data resulting from human or instrument error.
2
4
4
.
.
  e -9       p:v=.--     ,,---.----ww--m           w y. w+,y4,-- 7.-y- ,--,y%,--.,,mp,y
e
                                                                              ,
-9
                                                                                          -
p:v=.--
                                                                                                        ,-  ,y   ,y,.,wwww           -'-*w-Nm***a'w*rW 9e -evr-enw ~
,,---.----ww--m
                                                                                                                                                                    w---v-     v*-'rw--v' +rw - - -
w y. w+,y4,--
7.-y-
,--,y%,--.,,mp,y
,-
,y
,y,.,wwww
-'-*w-Nm***a'w*rW
9e
-evr-enw
~
w---v-
v*-'rw--v'
+rw
- - -
,
-


_
_
  . .
.
            The licensee indicated they had not established criteria to reject
.
              outliers, but would consider ANSI /ANS-56.8 as guidance. This item
The licensee indicated they had not established criteria to reject
              remains open pending licensee action.
outliers, but would consider ANSI /ANS-56.8 as guidance.
      3. Containment Integrated Leak Rate Test Procedure Review
This item
        a.   Procedure Review
remains open pending licensee action.
            The inspectors reviewed " Procedure for the Containment Integrated
3.
              Leakage Rate Test Type ' A' Point Beach Nuclear Plant Unit No. 2,"
Containment Integrated Leak Rate Test Procedure Review
              Revision 7, relative to the requirements of 10 CFR 50, Appendix J,
a.
            ANSI N45.4-1972 and the FSAR. All inspector comments were
Procedure Review
              satisfactorily resolved.
The inspectors reviewed " Procedure for the Containment Integrated
        b. Clarifications of Appendix J Requirements
Leakage Rate Test Type ' A' Point Beach Nuclear Plant Unit No. 2,"
            To ensure the licensee's understanding of Appendix J requirements,
Revision 7, relative to the requirements of 10 CFR 50, Appendix J,
              the inspectors conducted numerous discussions with licensee
ANSI N45.4-1972 and the FSAR.
            personnel during the course of the inspection. The following
All inspector comments were
              is a summary of the requirements discussed with the licensee.
satisfactorily resolved.
              (1) The only methods of data reduction acceptable to the NRC are
b.
                    total time or point-to point as described in ANSI N45.4-1972
Clarifications of Appendix J Requirements
                    including a statistically calculated instrument error analysis.
To ensure the licensee's understanding of Appendix J requirements,
                    The following options are available to the licensee and are
the inspectors conducted numerous discussions with licensee
                    suggested in the following order:
personnel during the course of the inspection.
                    (a) Total time (<24 hour duration test) in accordance with
The following
                          Bechtel Corp. Topical Report BN-TOP-1, Revision 1.
is a summary of the requirements discussed with the licensee.
                          Whenever this method is used BN-TOP-1 must be followed in
(1) The only methods of data reduction acceptable to the NRC are
                          its entirety except for any section which conflicts with
total time or point-to point as described in ANSI N45.4-1972
                          Appendix J requirements.
including a statistically calculated instrument error analysis.
                    (b) Total time (>24 hour duration test) using single-sided
The following options are available to the licensee and are
                          95% UCL.
suggested in the following order:
                    (c) Proposed Regulatory Guide MS 021-5, Regulatory Position
(a) Total time (<24 hour duration test) in accordance with
                          No. 13. If this method is utilized the licensee must
Bechtel Corp. Topical Report BN-TOP-1, Revision 1.
                          submi' an exemption request to NRC and receive approval
Whenever this method is used BN-TOP-1 must be followed in
                          for its use prior to the expiration of the Type A test
its entirety except for any section which conflicts with
                          frequency requirements stated in the Technical Specifications.
Appendix J requirements.
              (2) Periodic Type A, B, and C tests must include as-found results
(b) Total time (>24 hour duration test) using single-sided
                    as well as as-left.   In order to perform Type B and C tests
95% UCL.
                    prior to a Type A, an exemption from the Appendix J requirement
(c) Proposed Regulatory Guide MS 021-5, Regulatory Position
                    must be obtained from NRR.   The exemption request must state
No. 13.
                    how the licensee plans to determine the as-found condition of
If this method is utilized the licensee must
                    the containment since local leak rate tests are being performed
submi' an exemption request to NRC and receive approval
                    ahead of the CILRT. An acceptable method is to commit to add
for its use prior to the expiration of the Type A test
                    any improvements in leakage rates, which are the results of
frequency requirements stated in the Technical Specifications.
                    repairs and adjustments (R&A), to the Type A test results
(2) Periodic Type A, B, and C tests must include as-found results
                    using the " minimum pathway leakage" methodology.   This method
as well as as-left.
                    requires that:
In order to perform Type B and C tests
                                              3
prior to a Type A, an exemption from the Appendix J requirement
must be obtained from NRR.
The exemption request must state
how the licensee plans to determine the as-found condition of
the containment since local leak rate tests are being performed
ahead of the CILRT.
An acceptable method is to commit to add
any improvements in leakage rates, which are the results of
repairs and adjustments (R&A), to the Type A test results
using the " minimum pathway leakage" methodology.
This method
requires that:
3


          . ,                       ~     . . .                                                           ..                           .               -
. ,
    '
~
      "-v
. . .
..
.
-
'
"-v
' (a) In the case where individual leak rates are assigned to
.
.
                                                            ' (a) In the case where individual leak rates are assigned to
.
.
'
two valves in series (both before and after the R&A), the
                                                                    two valves in series (both before and after the R&A), the
'
                                                                    penetration through' leakage would simply be the smaller
penetration through' leakage would simply be the smaller
                                                                    of the two valves' leak rates.
of the two valves' leak rates.
                                                              (b) . In the case where a leak rate is obtained by pressurizing
(b) . In the case where a leak rate is obtained by pressurizing
                                                                    between two isolation valves and-the individual valve's
between two isolation valves and-the individual valve's
                                                                    leak rate is not quantified, the as-found and as-left                                                                 j
leak rate is not quantified, the as-found and as-left
j
;
penetration through-leakage for each valve would be
:
50 percent of the measured leak' rate if both valves
;
;
                                                                    penetration through-leakage for each valve would be                                                                    :
are repaired.
                                                                    50 percent of the measured leak' rate if both valves
.
;                                                                    are repaired.
,
.
'.
                                                                                                                                                                                            ,
(c) . In the case where a leak rate is obtained by pressurizing
'.
between two isolation valves and only one valve is
                                                              (c) . In the case where a leak rate is obtained by pressurizing
i
                                                                    between two isolation valves and only one valve is
repaired, the as-found penetration leak rate would
i                                                                   repaired, the as-found penetration leak rate would
conservatively be the final measured leak rate, and
                                                                    conservatively be the final measured leak rate, and
the as-left penetration through leak rate would be
                                                                    the as-left penetration through leak rate would be
1
1
zero (this assumes the repaired valve leaks zero).
                                                                    zero (this assumes the repaired valve leaks zero).
l
l                                       (3) Penetrations which are required to be Type C tested, as
(3) Penetrations which are required to be Type C tested, as
!                                                           described in the FSAR and SER, must be vented inside and
!
*'                                                           outside the containment during the CILRT. All vented
described in the FSAR and SER, must be vented inside and
                                                            penetrations must be drained of water inside the containment
*'
<
outside the containment during the CILRT.
                                                            and between the penetration valves to assure exposure of the                                                                   *
All vented
,                                                          containment isolation valves to containment air test pressure.
penetrations must be drained of water inside the containment
{                                                           The degree of draining of vented penetrations outside of                                                                       !
and between the penetration valves to assure exposure of the
                                                            containment is controlled by the requirement that the valves
*
                                                            be subjected to the post-accident differential pressure, or
<
                                                            proof that the-system was built to stringent quality assurance
containment isolation valves to containment air test pressure.
,
{
The degree of draining of vented penetrations outside of
!
containment is controlled by the requirement that the valves
be subjected to the post-accident differential pressure, or
proof that the-system was built to stringent quality assurance
'
standards comparable to those required for a seismic system.
.
.
        '
(4) Whenever penetration configurations during a CILRT deviate from
                                                            standards comparable to those required for a seismic system.
the ideal, the results of LLRTs for such penetrations must be
                                        (4) Whenever penetration configurations during a CILRT deviate from
3
3
                                                            the ideal, the results of LLRTs for such penetrations must be
added as a penalty to the CILRT results at the 95% confidence
                                                            added as a penalty to the CILRT results at the 95% confidence
level.
                                                              level. This penetration leakage penalty is determined'using
This penetration leakage penalty is determined'using
;                                                           the " minimum pathway leakage" methodology.                                     This methodology
;
l-                                                           is defined as the minimum leakage value that can be quantified
the " minimum pathway leakage" methodology.
                                                            through a penetration leakage path (e.g., the smallest leakage
This methodology
                                                            of two valves in series). This assumes no single active
l-
is defined as the minimum leakage value that can be quantified
through a penetration leakage path (e.g., the smallest leakage
of two valves in series). This assumes no single active
failure of redundant leakage barriers. Additionally, any
,
,
                                                            failure of redundant leakage barriers. Additionally, any
increase in containment sump, fuel pool, reactor water, or
'
'
                                                            increase in containment sump, fuel pool, reactor water, or
:
:                                                            suppression pool level during the course of the CILRT must be
suppression pool level during the course of the CILRT must be
[
taken as a penalty to the CILRT results.
If penalties exist,
they must be added (subtraction is never permitted) to the
i
i
                                                            taken as a penalty to the CILRT results. If penalties exist,
upper confidence level of the CILRT results.
                                                            they must be added (subtraction is never permitted) to the
,
                                                            upper confidence level of the CILRT results.
(5) The start of the CILRT must be noted in the test log at the
!
time the licensee determines that the containment stabilization
j
has been satisfactorily completed.
Reinitializing a test in
j
progress must be " forward looking," that is, the new start time
must be the time at which the decision to restart is made.
,
,
                                        (5) The start of the CILRT must be noted in the test log at the
!                                                            time the licensee determines that the containment stabilization
j                                                            has been satisfactorily completed. Reinitializing a test in
j                                                            progress must be " forward looking," that is, the new start time
,                                                          must be the time at which the decision to restart is made.
l
l
                                                            This also implies that the licensee has determined that the
This also implies that the licensee has determined that the
F
F
'
'
                                                                                                          4
4
.
.
E
E
              ,.r,- ,+ . , _w+,. , -   .--,----,...%,.,-,,%%m.,                 ..m.--.-.,,,,.%-,..,w,.,     ,,,,,,,%.--,,.,-.~,....~,y           ,,.% , r.-., r-. ..,-,r,.- , , , . ,
,.r,-
,+ . , _w+,. , -
.--,----,...%,.,-,,%%m.,
..m.--.-.,,,,.%-,..,w,.,
,,,,,,,%.--,,.,-.~,....~,y
,,.%
,
r.-.,
r-.
..,-,r,.-
, , , . ,


    .   .
.
          i. 1   ,    test has failed,'and has enough data'to quantify the leakage
.
      ,   ,        . rate. 'Any deviation from these positions should be discussed,
i.
  ,
1
                    'and documented, with the NRC inspector as they occur to avoid
test has failed,'and has enough data'to quantify the leakage
                      later invalidations of the test results.   Examples of acceptable
,
                    deviations of reinitializing the start time of the test in the
. rate. 'Any deviation from these positions should be discussed,
                    past a're: ' time at'which a~ leaking penetration which has an
,
                    -obvious effect on the test data was secured, accidental opening
,
                    and later closing of a valve which has an obvious effect on the
'and documented, with the NRC inspector as they occur to avoid
                    test data, the time at which an airlock outer door was closed
,
                    and the inner door was open.
later invalidations of the test results.
              (6) The supplemental or verification test should start within
Examples of acceptable
                    one hour after the completion of the CILRT. If problems
deviations of reinitializing the start time of the test in the
                    are encountered in the start-of the supplemental test, data
past a're: ' time at'which a~ leaking penetration which has an
                    recording must continue and be considered part of the CILRT
-obvious effect on the test data was secured, accidental opening
                    until the problems are corrected and the supplemental test
and later closing of a valve which has an obvious effect on the
                    can begin.
test data, the time at which an airlock outer door was closed
              (7) For the supplemental test, the size of the superimposed leak
and the inner door was open.
                    rate must be between 0.75 and 1.25 times the maximum allowable
(6) The supplemental or verification test should start within
                    leak rate (La). The higher the value, the better.       The
one hour after the completion of the CILRT.
                    supplemental test must be of sufficient duration to demonstrate
If problems
                    the accuracy of the test. The NRC looks for the results to
are encountered in the start-of the supplemental test, data
                    stabilize within the acceptance criteria, rather than the,
recording must continue and be considered part of the CILRT
                    results being within the acceptance criteria.     Whenever the
until the problems are corrected and the supplemental test
                    BN-TOP-1 methodology is being used, the length of the
can begin.
                    supplemental ~ test cannot be less than approximately one-half
(7) For the supplemental test, the size of the superimposed leak
                    the length'of the CILRT.
rate must be between 0.75 and 1.25 times the maximum allowable
              (8) During a CILRT, it may become necessary to reject or delete
leak rate (La).
                    specific sensors or data points due to drifting or erroneous
The higher the value, the better.
                    sensors, or data outliers.     Data rejection criteria should
The
                    be developed and used so that there is a consistent,
supplemental test must be of sufficient duration to demonstrate
                    technical basis for data rejection.     One example of an
the accuracy of the test. The NRC looks for the results to
                    acceptable method for data outliers is described in an appendix
stabilize within the acceptance criteria, rather than the,
                    to ANSI /ANS 56.8-1981. Sensor data rejection criteria should
results being within the acceptance criteria.
                    be plant specific and based upon a sensor's trend relative to
Whenever the
                                                          ~
BN-TOP-1 methodology is being used, the length of the
                    the average scatter, slope, and/or absolute output of the sensor.
supplemental ~ test cannot be less than approximately one-half
              (9) The water level in the steam generators during the CILRT must
the length'of the CILRT.
                    be low enough to ensure it does not enter the main steam lines
(8) During a CILRT, it may become necessary to reject or delete
specific sensors or data points due to drifting or erroneous
sensors, or data outliers.
Data rejection criteria should
be developed and used so that there is a consistent,
technical basis for data rejection.
One example of an
acceptable method for data outliers is described in an appendix
to ANSI /ANS 56.8-1981.
Sensor data rejection criteria should
be plant specific and based upon a sensor's trend relative to
~
the average scatter, slope, and/or absolute output of the sensor.
(9) The water level in the steam generators during the CILRT must
be low enough to ensure it does not enter the main steam lines
unless flooding of the main steam lines is called for the in
3
3
                    unless flooding of the main steam lines is called for the in
;
;                    the loss of coolant emergency procedures.
the loss of coolant emergency procedures.
!             (10) An acceptable method for determining if the sum of Type B and
!
                    C tests exceeds the 0.60 La Appendix J limit is to utilize the
(10) An acceptable method for determining if the sum of Type B and
,                    " maximum pathway leakage" method. This methodology is defined
C tests exceeds the 0.60 La Appendix J limit is to utilize the
                    as the maximum leakage value that can be quantified through a
" maximum pathway leakage" method.
[                    penetration leakage path (e.g., the larger, not total, leakage
This methodology is defined
,
[
as the maximum leakage value that can be quantified through a
penetration leakage path (e.g., the larger, not total, leakage
of two valves in series).
This assumes a single active failure
i
i
'
'
                    of two valves in series). This assumes a single active failure
to the better of the two leakage barriers in series when
                    to the better of the two leakage barriers in series when
L
L                   performing Type B or C tests.
performing Type B or C tests.
i
i
i                                               5
i
5


. .
.
            (11) Test connections must be administrative 1y controlled to
.
                  ensure their leak tightness or otherwise be subject to
(11) Test connections must be administrative 1y controlled to
                  Type C testing. 'One way to ensure their leak tightness
ensure their leak tightness or otherwise be subject to
                  is to cap, with a good seal, the test connection after
Type C testing. 'One way to ensure their leak tightness
                  its use. Proper administrative controls should ensure
is to cap, with a good seal, the test connection after
                  valve closure and cap reinstallation within the local
its use.
                  leak rate testing procedure, and with a checklist prior
Proper administrative controls should ensure
                  to unit restart.
valve closure and cap reinstallation within the local
            (12) Whenever a valve is replaced, repaired, or repacked during an
leak rate testing procedure, and with a checklist prior
                  outage for which Type A, B, and/or C surveillance testing was
to unit restart.
                  scheduled, local leak rate testing for the as-found as well as
(12) Whenever a valve is replaced, repaired, or repacked during an
                  the as-left condition must be performed on that penetration.
outage for which Type A, B, and/or C surveillance testing was
                  In the case of a replaced valve, the as-found test can be waived
scheduled, local leak rate testing for the as-found as well as
                  if no other containment isolation valve of similar design exists
the as-left condition must be performed on that penetration.
                  at the site.
In the case of a replaced valve, the as-found test can be waived
      No violations or deviations were identified in this area.
if no other containment isolation valve of similar design exists
    4. Containment Integrated Leak Rate Test Witnessing (Unit 2)
at the site.
      a.   Instrumentation
No violations or deviations were identified in this area.
          The inspector reviewed the calibration data and determined all the
4.
            instruments used in the CILRT had been properly calibrated and that
Containment Integrated Leak Rate Test Witnessing (Unit 2)
          the correct weighting factors had been placed in the computer
a.
          program as required. The following instrumentation was used
Instrumentation
          throughout the test.
The inspector reviewed the calibration data and determined all the
                _ Type           Quantity
instruments used in the CILRT had been properly calibrated and that
          RTDs                       24
the correct weighting factors had been placed in the computer
          Dewcells                   12
program as required.
          Pressure Gauges               2
The following instrumentation was used
          Flowmeter                     1
throughout the test.
          During the integrated leak rate test dewcell number 12 was deleted
_ Type
          from the dan scan due to erratic (step changes) behavior. The test
Quantity
          data was reinitialized using the other 11 dewcells and the weighting
RTDs
          factors were reassigned. No other sensors or data sets were
24
          rejected during the test.
Dewcells
      b. Temperature Survey
12
          The inspectors reviewed the temperature survey performed by the
Pressure Gauges
          licensee prior to containment pressurization. The survey was
2
          performed with all containment fans off. Both the survey, the
Flowmeter
          CILRT, and the verification test were performed with the fans off.
1
          The results of the temperature survey were satisfactory for
During the integrated leak rate test dewcell number 12 was deleted
                                            6
from the dan scan due to erratic (step changes) behavior.
                                    _ _ _   _       _
The test
                                                              ._   _         ._
data was reinitialized using the other 11 dewcells and the weighting
factors were reassigned.
No other sensors or data sets were
rejected during the test.
b.
Temperature Survey
The inspectors reviewed the temperature survey performed by the
licensee prior to containment pressurization.
The survey was
performed with all containment fans off.
Both the survey, the
CILRT, and the verification test were performed with the fans off.
The results of the temperature survey were satisfactory for
6
_ _ _
_
_
._
_
._


                                                                                      I
I
  . .                                                                                 l
.
                                                                                      l
.
                                                                                      l
l
                                                                                      l
l
                                                                                      ;
l
              the containment condition under which the Type "A" test was
;
              performed. The survey confirmed that the temperature readings
the containment condition under which the Type "A" test was
              of the RTDs were representative of each containment subvolume.
performed.
        c.   Witness of Test
The survey confirmed that the temperature readings
              The inspectors witnessed the. reduced pressure CILRT on October 1,
of the RTDs were representative of each containment subvolume.
            .1986, and noted that test prerequisites were met and that the
c.
              appropriate revision to the test procedure was followed by test
Witness of Test
              personnel. Valve lineups for the following systems were verified to
The inspectors witnessed the. reduced pressure CILRT on October 1,
              ensure that no fluid could enter the containment atmosphere and that
.1986, and noted that test prerequisites were met and that the
              adequate venting and draining was provided:
appropriate revision to the test procedure was followed by test
              System                                                 Penetration (s)
personnel.
              Component Cooling to and from 1P1A                         15 and 17
Valve lineups for the following systems were verified to
              Component Cooling to and from IP1B                         16 and 18
ensure that no fluid could enter the containment atmosphere and that
              Service Air Supply to Containment                             33C
adequate venting and draining was provided:
              Hot Leg Sample                                               28A
System
              Pressurizer Steam Space Sample                               28C
Penetration (s)
              Reactor Makeup Water to Containment                           30C
Component Cooling to and from 1P1A
              Nitrogen to Safety Injection Accumulators                     14C
15 and 17
              Instrument Air Supply                                     33A and 33B
Component Cooling to and from IP1B
              Nitrogen Supply Line to Pressurizer Relief Tank               14A
16 and 18
              Demineralized Water Supply to Containment                     12A
Service Air Supply to Containment
              No violations or deviations were identified.
33C
      5. Test Results Evaluation
Hot Leg Sample
        a.   Reduced Pressure CILRT Data Evaluation
28A
              Upon satisfactorily completion of the required stabilization period.
Pressurizer Steam Space Sample
              An'eight hour reduced pressure CILRT was performed at 45.2 PSIA
28C
              during October 1, 1986, with data collected and reduced by the
Reactor Makeup Water to Containment
              licensee every 15 minutes. The inspectors independently monitored
30C
              and evaluated leak rate and instrument performance. There was
Nitrogen to Safety Injection Accumulators
              agreement between the inspectors' and licensee's results as
14C
              indicated by the following summary (units are in weight percent
Instrument Air Supply
              per day).
33A and 33B
              Measurement                     Licensee               Inspectors
Nitrogen Supply Line to Pressurizer Relief Tank
              Leakage rate measured             0.026                   0.026
14A
              during ILRT (Ltm)
Demineralized Water Supply to Containment
              Ltm at upper 95%                   0.102                   0.102
12A
              Confidence level
No violations or deviations were identified.
              Appendix J acceptance criteria at 95% UCL <0.75 Lt or <0.201 wt.%/ day.
5.
                                            7
Test Results Evaluation
a.
Reduced Pressure CILRT Data Evaluation
Upon satisfactorily completion of the required stabilization period.
An'eight hour reduced pressure CILRT was performed at 45.2 PSIA
during October 1, 1986, with data collected and reduced by the
licensee every 15 minutes.
The inspectors independently monitored
and evaluated leak rate and instrument performance.
There was
agreement between the inspectors' and licensee's results as
indicated by the following summary (units are in weight percent
per day).
Measurement
Licensee
Inspectors
Leakage rate measured
0.026
0.026
during ILRT (Ltm)
Ltm at upper 95%
0.102
0.102
Confidence level
Appendix J acceptance criteria at 95% UCL <0.75 Lt or <0.201 wt.%/ day.
7
-
-


                                                                                                              _
_
  - .
-
      b.  Supplemental Test Data Evaluation
          After the satisfactory completion of the reduced pressure eight hour
          CILRT, a known leakage (based on the inspectors' independent readings
          and calculations) of 5.68 SCFM, equivalent to 0.268 weight percent
          per day (wt.%/ day) was induced. Data was collected and analyzed by
          the licensee every 15 minutes. The inspectors independently monitored
          and evaluated leak rate data to verify the licensee's results. After
          five hours, the supplemental test was terminated with satisfactory
.
.
'
b.
          results as indicated by the following summary (units are in weight
Supplemental Test Data Evaluation
          percent per day).
After the satisfactory completion of the reduced pressure eight hour
          Measurement                                  Licensee                          Inspectors
CILRT, a known leakage (based on the inspectors' independent readings
          Measured leakage rate                          0.312                              0.312
and calculations) of 5.68 SCFM, equivalent to 0.268 weight percent
          during supplemental, Lc
per day (wt.%/ day) was induced.
!        Induced leakage rate, Lo                      0.268                              0.268
Data was collected and analyzed by
          Lc - (Lo + Ltm)                                0.018                              0.018
the licensee every 15 minutes.
          Appendix J acceptance criteria: -0.067 <[Lc-(Lo + Ltm)] <+0.067.
The inspectors independently monitored
                                                                -
and evaluated leak rate data to verify the licensee's results.
          As indicated above, the licensee's test verification resiilts were
After
          stable and within the acceptance criteria.
five hours, the supplemental test was terminated with satisfactory
      c. CILRT Valve Lineup Penalties
          Due to penetration configurations which deviated from the penetration
          lineup requirement for the CILRT, the results of local leak rate
          tests for each penetration must be added to Ltm at the 95 percent
          UCL.    The following penalties must be added using the minimum
          pathway leakage for the following penetrations or possible sources
          of in-leakage:
.
.
results as indicated by the following summary (units are in weight
'
'
                                                                          Local Leak Rate Based
percent per day).
                                                                          On Latest Test (Units
Measurement
          Penetration / Equipment                                               are in SCCM)
Licensee
          Service Air                                                                     495
Inspectors
          Post Accident Containment Sampling Connection                                     0
Measured leakage rate
          Letdown                                                                         101
0.312
          Seal Injection A                                                                   6
0.312
          Seal Injection B                                                                   1
during supplemental, Lc
          N2 Bottles and Accumulators                                             13,563
!
          Containment Pressure Connection                                                   0
Induced leakage rate, Lo
          Aux Charging                                                                     28
0.268
          Charging                                                                           2
0.268
          Total = 14,196 SCCM = .0237 wt.%/ day.
Lc - (Lo + Ltm)
          No violations or deviations were identified.
0.018
0.018
Appendix J acceptance criteria: -0.067 <[Lc-(Lo + Ltm)] <+0.067.
-
As indicated above, the licensee's test verification resiilts were
stable and within the acceptance criteria.
c.
CILRT Valve Lineup Penalties
Due to penetration configurations which deviated from the penetration
lineup requirement for the CILRT, the results of local leak rate
tests for each penetration must be added to Ltm at the 95 percent
UCL.
The following penalties must be added using the minimum
pathway leakage for the following penetrations or possible sources
of in-leakage:
Local Leak Rate Based
.
'
On Latest Test (Units
Penetration / Equipment
are in SCCM)
Service Air
495
Post Accident Containment Sampling Connection
0
Letdown
101
Seal Injection A
6
Seal Injection B
1
N Bottles and Accumulators
13,563
2
Containment Pressure Connection
0
Aux Charging
28
Charging
2
Total = 14,196 SCCM = .0237 wt.%/ day.
No violations or deviations were identified.
i
i
                                                  8
8
                .     -
.
                                . - . . . . - _ _ - _ _           . _ . .         . _ - -         --. - - - .   _.
-
. - . . .
. - _ _ - _ _
. _ .
.
. _ - -
--. - - - .
_.


  . .
.
      .
.
        d.   As-Found Condition of CILRT Results
.
              The as-found condition is the condition of the containment at the
d.
              beginning of the outage prior to any repairs or adjustments to the
As-Found Condition of CILRT Results
              containment boundary. Since the licensee performed the CILRT prior to
The as-found condition is the condition of the containment at the
              repairs of the containment isolation valves and penetrations, the only
beginning of the outage prior to any repairs or adjustments to the
              adjustment was due to valve lineup penalties that deviated from the
containment boundary.
                ideal. The as-found Type A test result can then be obtained by adding
Since the licensee performed the CILRT prior to
              the adjustments to the overall Type A test result. The licensee is
repairs of the containment isolation valves and penetrations, the only
                limited to the Appendix J limit of <0.75 Lt or <0.201 wt.%/ day leakage.
adjustment was due to valve lineup penalties that deviated from the
              The following is a summary of the as-found containment leak rate
ideal.
              (units are in weight percent per day):
The as-found Type A test result can then be obtained by adding
              Measurement
the adjustments to the overall Type A test result.
              CILRT Valve Lineup Penalties                     0.024
The licensee is
              As-found Type A test results                     0.102
limited to the Appendix J limit of <0.75 Lt or <0.201 wt.%/ day leakage.
              Total As-found                                   0.126
The following is a summary of the as-found containment leak rate
              The licensee passed this CILRT in the as-found condition.
(units are in weight percent per day):
      6. Local Leak Rate Test Review
Measurement
        The inspector reviewed local leak rate test Procedure No. 0I-58,
CILRT Valve Lineup Penalties
        Revision 7, " Leak Testing of Containment Isolation Valves Units 1 and 2
0.024
        General Instructions and Information," for testing method, acceptance
As-found Type A test results
        criteria and penetrations to be tested. The inspector also reviewed
0.102
        and verified the containment local leak rate test program to determine
Total As-found
        whether the sum of LLRT results met the acceptance criteria (<0.6 La or
0.126
        <231,000 SCCM).     In addition, the inspector verified that penetrations
The licensee passed this CILRT in the as-found condition.
        and containment isolation valves were tested at the required frequency
6.
        and that measuring and that equipment was calibrated at the required
Local Leak Rate Test Review
        intervals. The following set of local leak rate tests results were
The inspector reviewed local leak rate test Procedure No. 0I-58,
        reviewed:
Revision 7, " Leak Testing of Containment Isolation Valves Units 1 and 2
          Unit                   Refueling Outage                                 Date When Performed
General Instructions and Information," for testing method, acceptance
            1                           10                                                     December 1982
criteria and penetrations to be tested.
            2                             9                                                     April 1983
The inspector also reviewed
            1                           11                                                     August 1983
and verified the containment local leak rate test program to determine
            2                           10                                                     October 1984
whether the sum of LLRT results met the acceptance criteria (<0.6 La or
            1                           12                                                     September 1984
<231,000 SCCM).
            2                           11                                                     November 1985
In addition, the inspector verified that penetrations
            1                           13                                                     June 1986
and containment isolation valves were tested at the required frequency
        During the review of the local leak rate test (LLRT) results, the
and that measuring and that equipment was calibrated at the required
        inspector observed that measuring and test equipment identification
intervals.
        numbers were not documented on LLRT results.     The licensee currently uses
The following set of local leak rate tests results were
        three leak rate indicators which have different ranges but overlap at the
reviewed:
        lower and higher readings. The serial number and the ra;ge of the leak
Unit
        rate indicators are as follows: (1) No. TIS-1008A, from 0 to 2 standard
Refueling Outage
Date When Performed
1
10
December 1982
2
9
April 1983
1
11
August 1983
2
10
October 1984
1
12
September 1984
2
11
November 1985
1
13
June 1986
During the review of the local leak rate test (LLRT) results, the
inspector observed that measuring and test equipment identification
numbers were not documented on LLRT results.
The licensee currently uses
three leak rate indicators which have different ranges but overlap at the
lower and higher readings. The serial number and the ra;ge of the leak
rate indicators are as follows:
(1) No. TIS-1008A, from 0 to 2 standard
l
l
l
l
                                              9
9
I
I
              ,-,           n , , .           ,   ,-.       . - - - - . - - . - - - . . , _ , .--. - , , . . - ,-
,-,
n
, ,
.
,
,-.
. - - - - . - - . - - - . . , _ , .--. - , , . .
- ,-


  .:
.:
      I
I
                                          ^
^
          liters per minute (SLM), (2) No. TIS-1012 has three ranges, from 0.02 to
liters per minute (SLM), (2) No. TIS-1012 has three ranges, from 0.02 to
          0.2 SLM, 0.2 to 2 SLM, and 0-20 SLM and (3) No. TIS-10088, from.0 to
0.2 SLM, 0.2 to 2 SLM, and 0-20 SLM and (3) No. TIS-10088, from.0 to
                    .
.
-
-
          400 SLM. -The inspector reviewed records to determine whether out of
400 SLM. -The inspector reviewed records to determine whether out of
          cal.ibration test equipment was being reported to the leak rate testing
cal.ibration test equipment was being reported to the leak rate testing
          department and whether the LLRT results were being adjusted to account
department and whether the LLRT results were being adjusted to account
          for the as-found calibration errors. Although no problems were found
for the as-found calibration errors.
          in this area, the inspector was concerned that' erroneous LLRT corrections
Although no problems were found
          could. occur since the range and test equipment were never documented. On
in this area, the inspector was concerned that' erroneous LLRT corrections
          September 30, 1986, the licensee issued an internal memo instructing all
could. occur since the range and test equipment were never documented. On
          personnel performing local leak rate tests to document the' test equipment
September 30, 1986, the licensee issued an internal memo instructing all
          used and the range. This item.is open pending review of future LLRT
personnel performing local leak rate tests to document the' test equipment
          results. (266/86021-01; 301/86018-01).
used and the range.
        7. Review of Previous CILRT Results
This item.is open pending review of future LLRT
          a.   The inspectors' reviewed the results of previous CILRTs as presented
results.
                by the licensee in their reports to the NRC. The reports reviewed
(266/86021-01; 301/86018-01).
                and the conclusions reached by the inspectors were discussed with the
7.
                licensee and are as follows:
Review of Previous CILRT Results
a.
The inspectors' reviewed the results of previous CILRTs as presented
by the licensee in their reports to the NRC.
The reports reviewed
and the conclusions reached by the inspectors were discussed with the
licensee and are as follows:
'
'
                (1) Unit No. 1 October 1981 CILRT
(1) Unit No. 1 October 1981 CILRT
                      The calculated leakage rate at the 95% UCL was 0.068 wt.%/ day.
The calculated leakage rate at the 95% UCL was 0.068 wt.%/ day.
                      According to the report nine penetrations were not in the ideal
According to the report nine penetrations were not in the ideal
                      test configuration, therefore requiring a penalty to be added
test configuration, therefore requiring a penalty to be added
                      to the CILRT results. It also indicates that repairs and
to the CILRT results.
                      adjustments'were made prior to the Type A test. .The values
It also indicates that repairs and
                      given for those nine penetrations before repairs was 149,058
adjustments'were made prior to the Type A test. .The values
                      scc / min or 0.758 wt.%/ day and after repairs was 4,064 scc / min'
given for those nine penetrations before repairs was 149,058
                      or 0.027 wt.%/ day. Based on the results'given in the report
scc / min or 0.758 wt.%/ day and after repairs was 4,064 scc / min'
                      the as-found containment leakage rate was 0.799 wt.%/ day and
or 0.027 wt.%/ day.
                      the as left containment leakage rate was 0.095 wt.%/ day. The
Based on the results'given in the report
                      acceptance criteria = 0.75 Lt = 0.212 wt.%/ day. The Type A test
the as-found containment leakage rate was 0.799 wt.%/ day and
                      was a failure in the as-found condition.
the as left containment leakage rate was 0.095 wt.%/ day.
                (2) Unit No. 2 April 1982 CILRT
The
                      The calculated leakage rate at the 95% UCL was 0.072 wt.%/ day.
acceptance criteria = 0.75 Lt = 0.212 wt.%/ day.
                      According to the report eleven penetrations were not in the
The Type A test
                      ideal test configuration, therefore requiring a penalty to be
was a failure in the as-found condition.
                      added to the CILRT results. It also' indicates that repairs and
(2) Unit No. 2 April 1982 CILRT
                      adjustments were made prior to the Type A test. The values
The calculated leakage rate at the 95% UCL was 0.072 wt.%/ day.
                      given for those eleven penetrations before repairs was 126,462
According to the report eleven penetrations were not in the
                      sec/ min or 0.147 wt.%/ day'and after repairs was 1,471 scc / min or
ideal test configuration, therefore requiring a penalty to be
                      0.002 wt.%/ day.   Based on the results given in the report the as
added to the CILRT results.
                      found containment leakage rate was 0.217 wt.%/ day and that as
It also' indicates that repairs and
                      left containment leakage rate was 0.074 wt.%/ day. The acceptance
adjustments were made prior to the Type A test.
                      criteria = 0.75 Lt = 0.201 wt.%/ day. The Type A test was a
The values
                      failure in the as found condition; however, since the test
given for those eleven penetrations before repairs was 126,462
                      just concluded (October 1986) was successful in the as-found
sec/ min or 0.147 wt.%/ day'and after repairs was 1,471 scc / min or
                      condition the results of the 1982 CILRT will have no effect on
0.002 wt.%/ day.
                      future test frequency.
Based on the results given in the report the as
                                                10
found containment leakage rate was 0.217 wt.%/ day and that as
left containment leakage rate was 0.074 wt.%/ day.
The acceptance
criteria = 0.75 Lt = 0.201 wt.%/ day.
The Type A test was a
failure in the as found condition; however, since the test
just concluded (October 1986) was successful in the as-found
condition the results of the 1982 CILRT will have no effect on
future test frequency.
10


                                                                                                                                    _ ._ _ ..           _             _ ..         .
_ ._ _ ..
                                            1
_
  4-               .
_
                  ,
..
    L
.
                                                                                                                                                                                      -{
1
                                                              ~ (3) Unit No.~1' April 1984 CILRT.
4-
                                                              ~
.
      .                                                              The calculated leakage rate, Ltm, was 0.186~wt.%/ day with a
,
                                                                      95% UCL of 0.202 wt.%/ day, adjusted for.the PORV 2N bottles
L
                                                                      leakage. The superimposed leakage rate, Lo, during the
-{
                                                                      supplemental _ test was 0.147 wt.%/ day.                               The measured leakage
~ (3) Unit No.~1' April 1984 CILRT.
                                                                      rate, Lc, during the supplemental test, adjusted for the PORV
.
                                                                      N2 bottles leakage, was 0.234 wt.%/ day. 10 CFR 50, Appendix J,
The calculated leakage rate, Ltm, was 0.186~wt.%/ day with a
                                                                      requires.that a Type A text be verified by a supplemental test
~
                                                                    of sufficient duration to establish accurately.the change in
95% UCL of 0.202 wt.%/ day, adjusted for.the PORV N bottles
                                                                      leakage between the Type A test and the supplemental test, and
2
                                                                    that for the results to be acceptable the differenta between
leakage. The superimposed leakage rate, Lo, during the
                                                                              ~
supplemental _ test was 0.147 wt.%/ day.
                                                                    the two tests can not exceed 0.25 Lt. In this case, the
The measured leakage
                                                                    difference between the Type A test and the supplemental test
rate, Lc, during the supplemental test, adjusted for the PORV
                                                                    .was: Ltm - (Lc - Lo) = 0.186-(0.234 - 0.147) = 0.099 wt.%/ day.
N bottles leakage, was 0.234 wt.%/ day.
                                                                    Since 0.25 Lt = 0.053 wt.%/ day, the results of the supplemental
10 CFR 50, Appendix J,
                                                                    test were not acceptable.
2requires.that a Type A text be verified by a supplemental test
                                                                    Appendix J requires that if the results of the supplemental                                                     N
of sufficient duration to establish accurately.the change in
                                                                    test are not within 0.25 Lt, the cause must be determined,
leakage between the Type A test and the supplemental test, and
                                                                    corrective action taken, and a successful test performed. The                                                   m
that for the results to be acceptable the differenta between
                                                                                                                                                                                    ^'
the two tests can not exceed 0.25 Lt.
                                                                    report-shows that the data was misinterpreted by the licensee                                               ~;
In this case, the
                                                                    which resulted in a failure to realize that the supplemental
~
                                                                    test had failed. As a result, no cause of failure was                                                             #
difference between the Type A test and the supplemental test
                          '
.was: Ltm - (Lc - Lo) = 0.186-(0.234 - 0.147) = 0.099 wt.%/ day.
                                                                    determined, no corrective action was taken, and a successful                                                   "
Since 0.25 Lt = 0.053 wt.%/ day, the results of the supplemental
                                                                    supplemental text was never performed. This is a violation
test were not acceptable.
                                                                    -(266/86021-02) of 10 CFR 50, Appendix J.
Appendix J requires that if the results of the supplemental
                                                                    Since the supplemental test failed to verify the accur'acy of
N
                                                                    the Type A test, the inspectors find the entire 1984 CILRT-
test are not within 0.25 Lt, the cause must be determined,
                                                                    invalid. A review of the CILRTs performed during the present
corrective action taken, and a successful test performed.
                                                                    ten year service period showed that three tests will have been
The
                                                                    performed once the licensee conducts the CILRT scheduled for
m
                                                                    April 1987; therefore meeting Appendix J requirements. A-
^'
                                                                    review of Technical Specifications requirements for containment
report-shows that the data was misinterpreted by the licensee
                                                                    integrity showed no coupling of the testing frequency with the
~;
                                                                    definition of containment integrity. As a result, the voiding                                                     i
which resulted in a failure to realize that the supplemental
                                                                    of the April 1984 CILRT did not place Unit 1 in violation of
test had failed.
                                                                    containment integrity,
As a result, no cause of failure was
i                                                             b.     During the recent interview of December 11, 1986, the licensee
#
i                                                                   expressed disagreement with the Region III position regarding the
determined, no corrective action was taken, and a successful
                                                                    April 1984 Unit 1 test. In addition, the licensee stated that
'
                                                                    the results presented for the penalties taken on the 1981
"
                                                                    (Unit 1) and 1982 (Unit 2) tests had been calculated using the
supplemental text was never performed.
                                                                    maximum leakage pathway method. The inspector stated that the
This is a violation
                                                                    licensee should recalculate the penalties using the minimum
-(266/86021-02) of 10 CFR 50, Appendix J.
                                                                    leakage pathway method and correct the reports submitted. This
Since the supplemental test failed to verify the accur'acy of
,                                                                    matter is open pending review of the licensee's local leak rate
the Type A test, the inspectors find the entire 1984 CILRT-
invalid. A review of the CILRTs performed during the present
ten year service period showed that three tests will have been
performed once the licensee conducts the CILRT scheduled for
April 1987; therefore meeting Appendix J requirements.
A-
review of Technical Specifications requirements for containment
integrity showed no coupling of the testing frequency with the
definition of containment integrity. As a result, the voiding
i
of the April 1984 CILRT did not place Unit 1 in violation of
containment integrity,
i
b.
During the recent interview of December 11, 1986, the licensee
i
expressed disagreement with the Region III position regarding the
April 1984 Unit 1 test.
In addition, the licensee stated that
the results presented for the penalties taken on the 1981
(Unit 1) and 1982 (Unit 2) tests had been calculated using the
maximum leakage pathway method.
The inspector stated that the
licensee should recalculate the penalties using the minimum
leakage pathway method and correct the reports submitted.
This
matter is open pending review of the licensee's local leak rate
,
l
l
                                                                    test data (266/86021-03; 301/86018-02).
test data (266/86021-03; 301/86018-02).
.
.
,
,
*
*
                                                                                                                      11                                                               i
11
i
l
l
  .     . -,- - . . - . . - - . . , . . - . . , - - . - - - .                         . - - . , - - - - - , , . . - . . . . . . - .               . - . - - . _ , _ .     - _ -
.
. -,- - . . - . . - - . . , . . - . . , - - . - - - .
. - - . , - - - - - , , . . - . . . . . . - .
. - . - - . _ , _ .
- -


                                                                                                      _
_
  - ..
      8. Open Ite71
          Open itsis<are matters which have been discussed with the licensee,
          which will be reviewed by the inspector and which involve some action
          on the paat of the NRC or licensee or both. Open items disclosed during
          the inspection are discussed in Paragraphs 6 and 7.b.
      9. Exit Interview
          The inspectors met with licensee representatives denoted in Paragraph 1
          during the inspection on October 2, 1986 and again by telephone at the
          conclusion of the inspection on December 11, 1986. The inspectors
          summarized the scope and findings of the inspection. The licensee
          acknowledged the information and did not indicate that any of the-
          information disclosed during the inspection could be considered
          proprietary in nature.
-
-
                                                                          12
..
            . _ _ _ _ .     - - _ _
8.
                                      , , - _ _ _ _ _ - _ . - - . _ - . - . _ . , _ . -._ . _ _ . . _ - _ _ _ . _ _ . _
Open Ite71
Open itsis<are matters which have been discussed with the licensee,
which will be reviewed by the inspector and which involve some action
on the paat of the NRC or licensee or both. Open items disclosed during
the inspection are discussed in Paragraphs 6 and 7.b.
9.
Exit Interview
The inspectors met with licensee representatives denoted in Paragraph 1
during the inspection on October 2, 1986 and again by telephone at the
conclusion of the inspection on December 11, 1986.
The inspectors
summarized the scope and findings of the inspection.
The licensee
acknowledged the information and did not indicate that any of the-
information disclosed during the inspection could be considered
proprietary in nature.
-
12
. _ _ _ _ .
- - _ _
, , - _ _ _ _ _ - _ . - - . _ - . - . _ .
, _ .
-. .
. .
-
.
.
_
}}
}}

Latest revision as of 17:13, 23 May 2025

Insp Repts 50-266/86-21 & 50-301/86-18 on 860926-1211. Violation Noted:Failure to Follow 10CFR50,App J Requirements Re Verification of Type a Test Results by Performing Supplemental Test
ML20207L814
Person / Time
Site: Point Beach  
Issue date: 01/06/1987
From: Maura F, Mendez R, Ring M
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML20207L803 List:
References
50-266-86-21, 50-301-86-18, NUDOCS 8701120357
Download: ML20207L814 (12)


See also: IR 05000266/1986021

Text

{{#Wiki_filter:. . U.S. NUCLEAR REGULATOR COMMISSION REGION III Reports No. 50-266/86021(DRS); 50-301/86018(DRS) Docket Nos. 50-266; 50-301 Licenses No. DPR-24; DRP-27 Licensee: Wisconsin Electric Power Company 231 West Michigan Milwaukee, Wisconsin 53203 Facility Name: Point Beach Units 1 and 2 Inspection At: Two Creeks, Wisconsin Inspection Conducted: September 26, through December 11, 1986 Inspectors: MkNz h /[6/77 Date /lflH Date % - A- Approved By: M.A. Ring,Chieh '/4[b Test Programs Section Dats Inspection Summary Inspection on September 26 through December 11, 1986 (Reports No. 50-266/86021(DRS); No. 50-301/86018(ORS)) Areas Inspected: Routine announced inspection by Region III based inspectors of the containment integrated leak rate test (CILRT) procedure, CILRT performance witnessing; CILRT results; local leak rate test (Type B and C) procedure and results. NRC modules utilized during this inspection included 70307, 70313, 70323 and 61720. Results: One violation was identified (failure to follow the requirements of Appendix J - Paragraph 7.a.(3)). , 8701120357 8701o7 gDR ADOCK 05000266 PDR i ! . 5 , - ---e e , . - ,- m -,. -- - - - - - +

- , . . - . - .. . . . _- . - -.. . - .. . . DETAILS 1.- Persons. Contacted . b . Wisconsin Electric Power Company

+*J. J. Zach, Manager +C. Krause, Senior Project Engineer + +*S. W. Pullins, ISI Engineer +A. Reimer,. Superintendent, Plant Engineer +*S.'R. Sherwood, Engineer, Nuclear +J. Knorr,-Regulatory Engineer

  • F. A. Fluetje, Administrative Specialist

i ' +R. Fromm, Modifications Engineer +D. Kohn, Engineer Bechtel Corporation )

  • L.-Young, Engineering Specialist

B. Patel, Engineering Specialist 1 R. Blum, Engineering Specialist ?Volumetrics,Inc. D. H. Peyvan, Project Engineer ,.

-
  • Denotes persons attending the preliminary exit meeting of October 2, 1986.

+ Denotes persons in attendance during the telephone conference call of December 11, 1986. , I The inspectors also contacted other licensee personnel including i members of the technical, operating and regulatory assurance staff.

2. Licensee Action on Previous Inspection Findings ' a. (0 pen) Open Item (266/84005-01): This item involved an inspector observation that the licensee had not established controls for the ' assignment of and changes to the weighting factors for the RTDs or dowcells. During a review of the licensee's integrated leak rate test (ILRT) procedure, the inspector observed that assignment of and -changes'to the weighting factors were still not included in the ILRT l ' procedure. The licensee personcel indicated they were in the

process of reviewing the matter but had not documented their proposed action to establish controls for the assignment of weighting factors. , This item remains.open pending licensee action. b. (0 pen) Open Item (266/84005-02): This item involved inspector 4 determination that the licensee's ILRT procedure had not established data rejection criteria for outlying observations in the collection of data. Consequently, the licensee would not have a technical basis to reject erroneous data resulting from human or instrument error. 2 4 . e -9 p:v=.-- ,,---.----ww--m w y. w+,y4,-- 7.-y- ,--,y%,--.,,mp,y ,- ,y ,y,.,wwww -'-*w-Nm***a'w*rW 9e -evr-enw ~ w---v- v*-'rw--v' +rw - - - , -

_ . . The licensee indicated they had not established criteria to reject outliers, but would consider ANSI /ANS-56.8 as guidance. This item remains open pending licensee action. 3. Containment Integrated Leak Rate Test Procedure Review a. Procedure Review The inspectors reviewed " Procedure for the Containment Integrated Leakage Rate Test Type ' A' Point Beach Nuclear Plant Unit No. 2," Revision 7, relative to the requirements of 10 CFR 50, Appendix J, ANSI N45.4-1972 and the FSAR. All inspector comments were satisfactorily resolved. b. Clarifications of Appendix J Requirements To ensure the licensee's understanding of Appendix J requirements, the inspectors conducted numerous discussions with licensee personnel during the course of the inspection. The following is a summary of the requirements discussed with the licensee. (1) The only methods of data reduction acceptable to the NRC are total time or point-to point as described in ANSI N45.4-1972 including a statistically calculated instrument error analysis. The following options are available to the licensee and are suggested in the following order: (a) Total time (<24 hour duration test) in accordance with Bechtel Corp. Topical Report BN-TOP-1, Revision 1. Whenever this method is used BN-TOP-1 must be followed in its entirety except for any section which conflicts with Appendix J requirements. (b) Total time (>24 hour duration test) using single-sided 95% UCL. (c) Proposed Regulatory Guide MS 021-5, Regulatory Position No. 13. If this method is utilized the licensee must submi' an exemption request to NRC and receive approval for its use prior to the expiration of the Type A test frequency requirements stated in the Technical Specifications. (2) Periodic Type A, B, and C tests must include as-found results as well as as-left. In order to perform Type B and C tests prior to a Type A, an exemption from the Appendix J requirement must be obtained from NRR. The exemption request must state how the licensee plans to determine the as-found condition of the containment since local leak rate tests are being performed ahead of the CILRT. An acceptable method is to commit to add any improvements in leakage rates, which are the results of repairs and adjustments (R&A), to the Type A test results using the " minimum pathway leakage" methodology. This method requires that: 3

. , ~ . . . .. . - ' "-v ' (a) In the case where individual leak rates are assigned to . . two valves in series (both before and after the R&A), the ' penetration through' leakage would simply be the smaller of the two valves' leak rates. (b) . In the case where a leak rate is obtained by pressurizing between two isolation valves and-the individual valve's leak rate is not quantified, the as-found and as-left j

penetration through-leakage for each valve would be

50 percent of the measured leak' rate if both valves

are repaired. . , '. (c) . In the case where a leak rate is obtained by pressurizing between two isolation valves and only one valve is i repaired, the as-found penetration leak rate would conservatively be the final measured leak rate, and the as-left penetration through leak rate would be 1 zero (this assumes the repaired valve leaks zero). l (3) Penetrations which are required to be Type C tested, as ! described in the FSAR and SER, must be vented inside and

  • '

outside the containment during the CILRT. All vented penetrations must be drained of water inside the containment and between the penetration valves to assure exposure of the

< containment isolation valves to containment air test pressure. , { The degree of draining of vented penetrations outside of ! containment is controlled by the requirement that the valves be subjected to the post-accident differential pressure, or proof that the-system was built to stringent quality assurance ' standards comparable to those required for a seismic system. . (4) Whenever penetration configurations during a CILRT deviate from the ideal, the results of LLRTs for such penetrations must be 3 added as a penalty to the CILRT results at the 95% confidence level. This penetration leakage penalty is determined'using

the " minimum pathway leakage" methodology. This methodology l- is defined as the minimum leakage value that can be quantified through a penetration leakage path (e.g., the smallest leakage of two valves in series). This assumes no single active failure of redundant leakage barriers. Additionally, any , increase in containment sump, fuel pool, reactor water, or '

suppression pool level during the course of the CILRT must be [ taken as a penalty to the CILRT results. If penalties exist, they must be added (subtraction is never permitted) to the i upper confidence level of the CILRT results. , (5) The start of the CILRT must be noted in the test log at the ! time the licensee determines that the containment stabilization j has been satisfactorily completed. Reinitializing a test in j progress must be " forward looking," that is, the new start time must be the time at which the decision to restart is made. , l This also implies that the licensee has determined that the F ' 4 . E ,.r,- ,+ . , _w+,. , - .--,----,...%,.,-,,%%m., ..m.--.-.,,,,.%-,..,w,., ,,,,,,,%.--,,.,-.~,....~,y ,,.% , r.-., r-. ..,-,r,.- , , , . ,

. . i. 1 test has failed,'and has enough data'to quantify the leakage , . rate. 'Any deviation from these positions should be discussed, , , 'and documented, with the NRC inspector as they occur to avoid , later invalidations of the test results. Examples of acceptable deviations of reinitializing the start time of the test in the past a're: ' time at'which a~ leaking penetration which has an -obvious effect on the test data was secured, accidental opening and later closing of a valve which has an obvious effect on the test data, the time at which an airlock outer door was closed and the inner door was open. (6) The supplemental or verification test should start within one hour after the completion of the CILRT. If problems are encountered in the start-of the supplemental test, data recording must continue and be considered part of the CILRT until the problems are corrected and the supplemental test can begin. (7) For the supplemental test, the size of the superimposed leak rate must be between 0.75 and 1.25 times the maximum allowable leak rate (La). The higher the value, the better. The supplemental test must be of sufficient duration to demonstrate the accuracy of the test. The NRC looks for the results to stabilize within the acceptance criteria, rather than the, results being within the acceptance criteria. Whenever the BN-TOP-1 methodology is being used, the length of the supplemental ~ test cannot be less than approximately one-half the length'of the CILRT. (8) During a CILRT, it may become necessary to reject or delete specific sensors or data points due to drifting or erroneous sensors, or data outliers. Data rejection criteria should be developed and used so that there is a consistent, technical basis for data rejection. One example of an acceptable method for data outliers is described in an appendix to ANSI /ANS 56.8-1981. Sensor data rejection criteria should be plant specific and based upon a sensor's trend relative to ~ the average scatter, slope, and/or absolute output of the sensor. (9) The water level in the steam generators during the CILRT must be low enough to ensure it does not enter the main steam lines unless flooding of the main steam lines is called for the in 3

the loss of coolant emergency procedures. ! (10) An acceptable method for determining if the sum of Type B and C tests exceeds the 0.60 La Appendix J limit is to utilize the " maximum pathway leakage" method. This methodology is defined , [ as the maximum leakage value that can be quantified through a penetration leakage path (e.g., the larger, not total, leakage of two valves in series). This assumes a single active failure i ' to the better of the two leakage barriers in series when L performing Type B or C tests. i i 5

. . (11) Test connections must be administrative 1y controlled to ensure their leak tightness or otherwise be subject to Type C testing. 'One way to ensure their leak tightness is to cap, with a good seal, the test connection after its use. Proper administrative controls should ensure valve closure and cap reinstallation within the local leak rate testing procedure, and with a checklist prior to unit restart. (12) Whenever a valve is replaced, repaired, or repacked during an outage for which Type A, B, and/or C surveillance testing was scheduled, local leak rate testing for the as-found as well as the as-left condition must be performed on that penetration. In the case of a replaced valve, the as-found test can be waived if no other containment isolation valve of similar design exists at the site. No violations or deviations were identified in this area. 4. Containment Integrated Leak Rate Test Witnessing (Unit 2) a. Instrumentation The inspector reviewed the calibration data and determined all the instruments used in the CILRT had been properly calibrated and that the correct weighting factors had been placed in the computer program as required. The following instrumentation was used throughout the test. _ Type Quantity RTDs 24 Dewcells 12 Pressure Gauges 2 Flowmeter 1 During the integrated leak rate test dewcell number 12 was deleted from the dan scan due to erratic (step changes) behavior. The test data was reinitialized using the other 11 dewcells and the weighting factors were reassigned. No other sensors or data sets were rejected during the test. b. Temperature Survey The inspectors reviewed the temperature survey performed by the licensee prior to containment pressurization. The survey was performed with all containment fans off. Both the survey, the CILRT, and the verification test were performed with the fans off. The results of the temperature survey were satisfactory for 6 _ _ _ _ _ ._ _ ._

I . . l l l

the containment condition under which the Type "A" test was performed. The survey confirmed that the temperature readings of the RTDs were representative of each containment subvolume. c. Witness of Test The inspectors witnessed the. reduced pressure CILRT on October 1, .1986, and noted that test prerequisites were met and that the appropriate revision to the test procedure was followed by test personnel. Valve lineups for the following systems were verified to ensure that no fluid could enter the containment atmosphere and that adequate venting and draining was provided: System Penetration (s) Component Cooling to and from 1P1A 15 and 17 Component Cooling to and from IP1B 16 and 18 Service Air Supply to Containment 33C Hot Leg Sample 28A Pressurizer Steam Space Sample 28C Reactor Makeup Water to Containment 30C Nitrogen to Safety Injection Accumulators 14C Instrument Air Supply 33A and 33B Nitrogen Supply Line to Pressurizer Relief Tank 14A Demineralized Water Supply to Containment 12A No violations or deviations were identified. 5. Test Results Evaluation a. Reduced Pressure CILRT Data Evaluation Upon satisfactorily completion of the required stabilization period. An'eight hour reduced pressure CILRT was performed at 45.2 PSIA during October 1, 1986, with data collected and reduced by the licensee every 15 minutes. The inspectors independently monitored and evaluated leak rate and instrument performance. There was agreement between the inspectors' and licensee's results as indicated by the following summary (units are in weight percent per day). Measurement Licensee Inspectors Leakage rate measured 0.026 0.026 during ILRT (Ltm) Ltm at upper 95% 0.102 0.102 Confidence level Appendix J acceptance criteria at 95% UCL <0.75 Lt or <0.201 wt.%/ day. 7 -

_ - . b. Supplemental Test Data Evaluation After the satisfactory completion of the reduced pressure eight hour CILRT, a known leakage (based on the inspectors' independent readings and calculations) of 5.68 SCFM, equivalent to 0.268 weight percent per day (wt.%/ day) was induced. Data was collected and analyzed by the licensee every 15 minutes. The inspectors independently monitored and evaluated leak rate data to verify the licensee's results. After five hours, the supplemental test was terminated with satisfactory . results as indicated by the following summary (units are in weight ' percent per day). Measurement Licensee Inspectors Measured leakage rate 0.312 0.312 during supplemental, Lc ! Induced leakage rate, Lo 0.268 0.268 Lc - (Lo + Ltm) 0.018 0.018 Appendix J acceptance criteria: -0.067 <[Lc-(Lo + Ltm)] <+0.067. - As indicated above, the licensee's test verification resiilts were stable and within the acceptance criteria. c. CILRT Valve Lineup Penalties Due to penetration configurations which deviated from the penetration lineup requirement for the CILRT, the results of local leak rate tests for each penetration must be added to Ltm at the 95 percent UCL. The following penalties must be added using the minimum pathway leakage for the following penetrations or possible sources of in-leakage: Local Leak Rate Based . ' On Latest Test (Units Penetration / Equipment are in SCCM) Service Air 495 Post Accident Containment Sampling Connection 0 Letdown 101 Seal Injection A 6 Seal Injection B 1 N Bottles and Accumulators 13,563 2 Containment Pressure Connection 0 Aux Charging 28 Charging 2 Total = 14,196 SCCM = .0237 wt.%/ day. No violations or deviations were identified. i 8 . - . - . . . . - _ _ - _ _ . _ . . . _ - - --. - - - . _.

. . . d. As-Found Condition of CILRT Results The as-found condition is the condition of the containment at the beginning of the outage prior to any repairs or adjustments to the containment boundary. Since the licensee performed the CILRT prior to repairs of the containment isolation valves and penetrations, the only adjustment was due to valve lineup penalties that deviated from the ideal. The as-found Type A test result can then be obtained by adding the adjustments to the overall Type A test result. The licensee is limited to the Appendix J limit of <0.75 Lt or <0.201 wt.%/ day leakage. The following is a summary of the as-found containment leak rate (units are in weight percent per day): Measurement CILRT Valve Lineup Penalties 0.024 As-found Type A test results 0.102 Total As-found 0.126 The licensee passed this CILRT in the as-found condition. 6. Local Leak Rate Test Review The inspector reviewed local leak rate test Procedure No. 0I-58, Revision 7, " Leak Testing of Containment Isolation Valves Units 1 and 2 General Instructions and Information," for testing method, acceptance criteria and penetrations to be tested. The inspector also reviewed and verified the containment local leak rate test program to determine whether the sum of LLRT results met the acceptance criteria (<0.6 La or <231,000 SCCM). In addition, the inspector verified that penetrations and containment isolation valves were tested at the required frequency and that measuring and that equipment was calibrated at the required intervals. The following set of local leak rate tests results were reviewed: Unit Refueling Outage Date When Performed 1 10 December 1982 2 9 April 1983 1 11 August 1983 2 10 October 1984 1 12 September 1984 2 11 November 1985 1 13 June 1986 During the review of the local leak rate test (LLRT) results, the inspector observed that measuring and test equipment identification numbers were not documented on LLRT results. The licensee currently uses three leak rate indicators which have different ranges but overlap at the lower and higher readings. The serial number and the ra;ge of the leak rate indicators are as follows: (1) No. TIS-1008A, from 0 to 2 standard l l 9 I ,-, n , , . , ,-. . - - - - . - - . - - - . . , _ , .--. - , , . . - ,-

.: I ^ liters per minute (SLM), (2) No. TIS-1012 has three ranges, from 0.02 to 0.2 SLM, 0.2 to 2 SLM, and 0-20 SLM and (3) No. TIS-10088, from.0 to . - 400 SLM. -The inspector reviewed records to determine whether out of cal.ibration test equipment was being reported to the leak rate testing department and whether the LLRT results were being adjusted to account for the as-found calibration errors. Although no problems were found in this area, the inspector was concerned that' erroneous LLRT corrections could. occur since the range and test equipment were never documented. On September 30, 1986, the licensee issued an internal memo instructing all personnel performing local leak rate tests to document the' test equipment used and the range. This item.is open pending review of future LLRT results. (266/86021-01; 301/86018-01). 7. Review of Previous CILRT Results a. The inspectors' reviewed the results of previous CILRTs as presented by the licensee in their reports to the NRC. The reports reviewed and the conclusions reached by the inspectors were discussed with the licensee and are as follows: ' (1) Unit No. 1 October 1981 CILRT The calculated leakage rate at the 95% UCL was 0.068 wt.%/ day. According to the report nine penetrations were not in the ideal test configuration, therefore requiring a penalty to be added to the CILRT results. It also indicates that repairs and adjustments'were made prior to the Type A test. .The values given for those nine penetrations before repairs was 149,058 scc / min or 0.758 wt.%/ day and after repairs was 4,064 scc / min' or 0.027 wt.%/ day. Based on the results'given in the report the as-found containment leakage rate was 0.799 wt.%/ day and the as left containment leakage rate was 0.095 wt.%/ day. The acceptance criteria = 0.75 Lt = 0.212 wt.%/ day. The Type A test was a failure in the as-found condition. (2) Unit No. 2 April 1982 CILRT The calculated leakage rate at the 95% UCL was 0.072 wt.%/ day. According to the report eleven penetrations were not in the ideal test configuration, therefore requiring a penalty to be added to the CILRT results. It also' indicates that repairs and adjustments were made prior to the Type A test. The values given for those eleven penetrations before repairs was 126,462 sec/ min or 0.147 wt.%/ day'and after repairs was 1,471 scc / min or 0.002 wt.%/ day. Based on the results given in the report the as found containment leakage rate was 0.217 wt.%/ day and that as left containment leakage rate was 0.074 wt.%/ day. The acceptance criteria = 0.75 Lt = 0.201 wt.%/ day. The Type A test was a failure in the as found condition; however, since the test just concluded (October 1986) was successful in the as-found condition the results of the 1982 CILRT will have no effect on future test frequency. 10

_ ._ _ .. _ _ .. . 1 4- . , L -{ ~ (3) Unit No.~1' April 1984 CILRT. . The calculated leakage rate, Ltm, was 0.186~wt.%/ day with a ~ 95% UCL of 0.202 wt.%/ day, adjusted for.the PORV N bottles 2 leakage. The superimposed leakage rate, Lo, during the supplemental _ test was 0.147 wt.%/ day. The measured leakage rate, Lc, during the supplemental test, adjusted for the PORV N bottles leakage, was 0.234 wt.%/ day. 10 CFR 50, Appendix J, 2requires.that a Type A text be verified by a supplemental test of sufficient duration to establish accurately.the change in leakage between the Type A test and the supplemental test, and that for the results to be acceptable the differenta between the two tests can not exceed 0.25 Lt. In this case, the ~ difference between the Type A test and the supplemental test .was: Ltm - (Lc - Lo) = 0.186-(0.234 - 0.147) = 0.099 wt.%/ day. Since 0.25 Lt = 0.053 wt.%/ day, the results of the supplemental test were not acceptable. Appendix J requires that if the results of the supplemental N test are not within 0.25 Lt, the cause must be determined, corrective action taken, and a successful test performed. The m ^' report-shows that the data was misinterpreted by the licensee ~; which resulted in a failure to realize that the supplemental test had failed. As a result, no cause of failure was

determined, no corrective action was taken, and a successful ' " supplemental text was never performed. This is a violation -(266/86021-02) of 10 CFR 50, Appendix J. Since the supplemental test failed to verify the accur'acy of the Type A test, the inspectors find the entire 1984 CILRT- invalid. A review of the CILRTs performed during the present ten year service period showed that three tests will have been performed once the licensee conducts the CILRT scheduled for April 1987; therefore meeting Appendix J requirements. A- review of Technical Specifications requirements for containment integrity showed no coupling of the testing frequency with the definition of containment integrity. As a result, the voiding i of the April 1984 CILRT did not place Unit 1 in violation of containment integrity, i b. During the recent interview of December 11, 1986, the licensee i expressed disagreement with the Region III position regarding the April 1984 Unit 1 test. In addition, the licensee stated that the results presented for the penalties taken on the 1981 (Unit 1) and 1982 (Unit 2) tests had been calculated using the maximum leakage pathway method. The inspector stated that the licensee should recalculate the penalties using the minimum leakage pathway method and correct the reports submitted. This matter is open pending review of the licensee's local leak rate , l test data (266/86021-03; 301/86018-02). . ,

11 i l . . -,- - . . - . . - - . . , . . - . . , - - . - - - . . - - . , - - - - - , , . . - . . . . . . - . . - . - - . _ , _ . - -

_ - .. 8. Open Ite71 Open itsis<are matters which have been discussed with the licensee, which will be reviewed by the inspector and which involve some action on the paat of the NRC or licensee or both. Open items disclosed during the inspection are discussed in Paragraphs 6 and 7.b. 9. Exit Interview The inspectors met with licensee representatives denoted in Paragraph 1 during the inspection on October 2, 1986 and again by telephone at the conclusion of the inspection on December 11, 1986. The inspectors summarized the scope and findings of the inspection. The licensee acknowledged the information and did not indicate that any of the- information disclosed during the inspection could be considered proprietary in nature. - 12 . _ _ _ _ . - - _ _ , , - _ _ _ _ _ - _ . - - . _ - . - . _ . , _ . -. . . . - . . _ }}