ML20210E310: Difference between revisions

From kanterella
Jump to navigation Jump to search
StriderTol Bot change
StriderTol Bot change
 
(One intermediate revision by the same user not shown)
Line 19: Line 19:
=Text=
=Text=
{{#Wiki_filter:,
{{#Wiki_filter:,
  '
'
                                                        UNITED STATES
[gn Err
        [gn Err          o                   NUCLEAR REGULATORY COMMISSION
UNITED STATES
                      "
o
      y'                   n                              REGloN 11
NUCLEAR REGULATORY COMMISSION
    .y                   j                       101 MARIETTA STREET, N.W.
"
      *                 '*                         ATLANT A. GEORGI A 30323
y'
        '+9 . . . . . ,o
REGloN 11
    Report Nos.:             50-327/86-43 and 50-328/86-43
n
    Licensee: Tennessee Valley Authority
.y
                        6N38 A Lookout Place
j
                        1101 Market Street
101 MARIETTA STREET, N.W.
                        Chattanooga, TN 37401
*
    Docket Nos.: 50-327 and 50-328                                   License Nos.: DPR-77 and DPR-79
'*
    Facility Name:             Sequoyah Units 1 and 2
ATLANT A. GEORGI A 30323
    Inspection Conducted: July 28, 1986 - August 1, 1986
'+9 . . . . . ,o
    Inspectors:                                                   -
Report Nos.:
                        M. W. Braren, InspectpliE TKm Leader                         ~ Date' Signed
50-327/86-43 and 50-328/86-43
                                    kYl                                                 N
Licensee: Tennessee Valley Authority
                                                                                      'Date Signed
6N38 A Lookout Place
                        R. E. Carroll, Jr. , Projecf/ffgfiieer
1101 Market Street
                        G. PaulW                                                          S
Chattanooga, TN 37401
                                                                                                      '
Docket Nos.: 50-327 and 50-328
                                    k, L. , ;#iM'/       $_V (Browns Ferry)
License Nos.: DPR-77 and DPR-79
                                                    I g ec
Facility Name:
                                                                            -
Sequoyah Units 1 and 2
                                                                                        Date Signed
Inspection Conducted: July 28, 1986 - August 1, 1986
                            Y        ma
Inspectors:
                        J. Mathi W KeacL~r inspg#Cor 7
~ Date' Signed
                                                      l                              $
-
                                                                                        Tate Signed
M. W. Braren, InspectpliE TKm Leader
                                          __    /                                      ,,/
kYl
    Approved by:                                                                        y 24
N
                          B. Debs, Section Chief                                        D4te Signed
R. E. Carroll, Jr. , Projecf/ffgfiieer
j                        Division of Reactor Projects
'Date Signed
G. Paul k, L. , ;#iM'/ $_
-
Date Signed
W
S
'
I g ec V (Browns Ferry)
Y
ma
l
l
                                                        SUMMARY
$
    Scope:         This special, announced inspection was conducted in the area of
J. Mathi W KeacL~r inspg#Cor 7
    Modification Testing (MT) with a concentration on testing associated with
Tate Signed
    Environmentally Qualified (EQ) equipment modifications. This inspection involved
Approved by:
__
/
,,/
y 24
B. Debs, Section Chief
D4te Signed
j
Division of Reactor Projects
l
SUMMARY
Scope:
This special, announced inspection was conducted in the area of
Modification Testing (MT) with a concentration on testing associated with
Environmentally Qualified (EQ) equipment modifications. This inspection involved
a review of major or complicated Post Modification Tests (PMT), as well as a
!
review of Post Modification Functional Tests (PMFT). Additionally, a followup of
associated Inspector Identified Items, discussed in paragraph 9 of Inspection
Report 327, 328/86-20, was performed.
!
Results:
In the areas inspected, two violations were identified.
The first
l
violation, discussed in paragraph 6, involved multiple examples of
failure to
!
!
    a review of major or complicated Post Modification Tests (PMT), as well as a
properly implement the requirements of Administrative Instruction (AI)-19,
    review of Post Modification Functional Tests (PMFT). Additionally, a followup of
Part IV, " Plant Modifications After Licensing" and Surveillance Instruction
    associated Inspector Identified Items, discussed in paragraph 9 of Inspection
(51)-166.6, " Post Maintenance Testing of Category A and B Valves." The second
    Report 327, 328/86-20, was performed.
violation, also discussed in paragraph 6, involved a failure to properly change
!  Results:          In the areas inspected, two violations were identified.              The first
plant approved procedures.
l  violation, discussed in paragraph 6, involved multiple examples of                      failure to
8609220243 860912
properly implement the requirements of Administrative Instruction (AI)-19,
PDR
    Part IV, " Plant Modifications After Licensing" and Surveillance Instruction
ADOCK 05000327
    (51)-166.6, " Post Maintenance Testing of Category A and B Valves." The second
    violation, also discussed in paragraph 6, involved a failure to properly change
    plant approved procedures.
                      8609220243 860912
i
i
                      PDR      ADOCK 05000327
i
i                      G                     PDR
G
PDR


      .
]
                                                                                      ]
.
.
                                        REPORT DETAILS
.
  1.   Licensee Employee Contacted
REPORT DETAILS
    *P. R. Wallace, Plant Manager
1.
        L. M. Nobles, Operations and Engineering Superintendent
Licensee Employee Contacted
    *B. M. Patterson, Maintenance Superintendeot
*P. R. Wallace, Plant Manager
    *N. E. Andrews, Site Quality Manager
L. M. Nobles, Operations and Engineering Superintendent
    *D. C. Craven, Quality Assurance Manager
*B. M. Patterson, Maintenance Superintendeot
    *G.   B. Kirk, Compliance Licensing Supervisor
*N. E. Andrews, Site Quality Manager
    *R. W. Olson, Modifications Branch Manager
*D. C. Craven, Quality Assurance Manager
    *M.   R. .Sedlacik, Electrical Section Manager, Modifications Branch
*G. B. Kirk, Compliance Licensing Supervisor
    *R.   M. Mooney, Systems Engineering Supervisor
*R. W. Olson, Modifications Branch Manager
    *J.   A. McPherson, Mechanical Test Supervisor
*M. R. .Sedlacik, Electrical Section Manager, Modifications Branch
    *R.   W. Fortenberry, Technical Support Supervisor
*R. M. Mooney, Systems Engineering Supervisor
    *R.   V. Pierce, Mechanical Maintenance Supervisor
*J. A. McPherson, Mechanical Test Supervisor
    *H. D. Elkins Jr., Instrument Maintenance Supervisor
*R. W. Fortenberry, Technical Support Supervisor
    *M. A. Skarzinski, Electrical Maintenance Supervisor
*R. V. Pierce, Mechanical Maintenance Supervisor
    *R. H. Smith, Project Management
*H. D. Elkins Jr., Instrument Maintenance Supervisor
    *J. H. Sullivan, Regulatory Engineering Supervisor
*M. A. Skarzinski, Electrical Maintenance Supervisor
    *P. H. Buckholz, Sequoyah Site Representative
*R. H. Smith, Project Management
        S. D. Gilley, Modification Engineer
*J. H. Sullivan, Regulatory Engineering Supervisor
        E. L. Legg, Modification Engineer
*P. H. Buckholz, Sequoyah Site Representative
        J. Edwards, Instrument Maintenance
S. D. Gilley, Modification Engineer
        T. L. Rutledge, Modification Engineer
E. L. Legg, Modification Engineer
        D._R. Branham, Modification Engineer
J. Edwards, Instrument Maintenance
        Other licensee employees contacted included technicians, operators, shift
T. L. Rutledge, Modification Engineer
        engineers and maintenance personnel.
D._R. Branham, Modification Engineer
    * Attended exit interview
Other licensee employees contacted included technicians, operators, shift
  2.   Exit Interview
engineers and maintenance personnel.
        The inspection scope and findings were summarized on August 1,1986, with
* Attended exit interview
        those persons indicated by an asterisk in paragraph one above.         The
2.
        following new items were discussed:
Exit Interview
        a.   Violation for failure to properly implement the requirements of AI-19,
The inspection scope and findings were summarized on August 1,1986, with
              Part IV and SI-166.6 in the area of functional testing.
those persons indicated by an asterisk in paragraph one above.
        b.   Violation for failure to properly change plant approved procedures.
The
              This item was initially categorized as an unresolved item then upgraded
following new items were discussed:
              after additional discussion with NRC personnel.
a.
        The licensee acknowledged the inspection findings. The licensee did not
Violation for failure to properly implement the requirements of AI-19,
        identify as proprietary any material provided to the inspectors during the
Part IV and SI-166.6 in the area of functional testing.
        inspection. At no time during the inspection period did the inspectors
b.
        provide written material to the licensee.
Violation for failure to properly change plant approved procedures.
This item was initially categorized as an unresolved item then upgraded
after additional discussion with NRC personnel.
The licensee acknowledged the inspection findings.
The licensee did not
identify as proprietary any material provided to the inspectors during the
inspection. At no time during the inspection period did the inspectors
provide written material to the licensee.


  _
_
        .
.
    .
.
                                                2
2
      3. Followup On Inspector Identified Items
3.
        a.   (Closed) IFI 327, 328/86-20-03; Review of modifications to Limitorque
Followup On Inspector Identified Items
              Valves to determine effect, if any, of improper wiring. The issue was
a.
              . originally addressed in paragraph nine of inspection report 327,
(Closed) IFI 327, 328/86-20-03; Review of modifications to Limitorque
              328/86-20 and dealt with the rewiring of approximately 214 Limitorque
Valves to determine effect, if any, of improper wiring. The issue was
              Operators to establish EQ qualifications as well as simplifying and
. originally addressed in paragraph nine of inspection report 327,
                                            .
328/86-20 and dealt with the rewiring of approximately 214 Limitorque
              correcting limit and/or torque switch discrepancies. The inspector was
Operators to establish EQ qualifications as well as simplifying and
              concerned with the possibility-that the improper wiring of limit / torque
.
              switches could have had an effect on valve operation.
correcting limit and/or torque switch discrepancies. The inspector was
              During the review of Work Plan (WP) 11866 (unit 1) and WP 11853
concerned with the possibility-that the improper wiring of limit / torque
                                    .
switches could have had an effect on valve operation.
              (unit 2), which rewired the limitorque valves, the inspector's concern
During the review of Work Plan (WP) 11866 (unit 1) and WP 11853
              was re-addressed.     It was determined that some of the previous
(unit 2), which rewired the limitorque valves, the inspector's concern
              torque / limit switch combinations did, under certain circumstances, have
.
              the potential of preventing the fulfillment of valve function.
was re-addressed.
              However, the inspector determined that these valves are part of the
It was determined that some of the previous
              ASME Section XI Article IWV valve test program and are tested for
torque / limit switch combinations did, under certain circumstances, have
              operability on a routine basis per that program.
the potential of preventing the fulfillment of valve function.
        b.   (Closed) IFI 327, 328/86-20-11; Use of terminology of " perform the
However, the inspector determined that these valves are part of the
              applicable portions of a Plant Operations Review Committee (PORC)
ASME Section XI Article IWV valve test program and are tested for
              approved procedure". This item is being combined with a related item
operability on a routine basis per that program.
              associated with changes to approved procedures. Both items will be       .
b.
              resolved as part of that issue which is identified as Violation 327,     I
(Closed) IFI 327, 328/86-20-11; Use of terminology of " perform the
              328/86-43-02 and discussed in detail in Paragraph 6 of this report.
applicable portions of a Plant Operations Review Committee (PORC)
      4. Unresolved Items
approved procedure". This item is being combined with a related item
        No Unresolved Items were identified during this inspection.
associated with changes to approved procedures.
      5. Design, Design Changes, and Modifications (37700)
Both items will be
        Although the major objective of this inspection was to determine the
.
        adequacy of Modification Testing, the inspectors did review several of the
resolved as part of that issue which is identified as Violation 327,
        modification Work Plans (WPs) for technical adequacy, proper review and
I
        approval, adequacy of safety evaluation as well as drawing and procedure
328/86-43-02 and discussed in detail in Paragraph 6 of this report.
        updates. Work Plans reviewed as well as inspection findings are as follow:
4.
l       a.   Containment Pressure Transmitter Modifications
Unresolved Items
i             Engineering Change Notice (ECN) 6554 and WP 11912 replaces the existing
No Unresolved Items were identified during this inspection.
              containment pressure transmitters 1 & 2-PDT-30-42 and 1 & 2-PDT-30-43
5.
              with qualified Foxboro transmitters per NUREG 0588. These transmitters
Design, Design Changes, and Modifications (37700)
              provide input to containment isolation and containment spray logic.
Although the major objective of this inspection was to determine the
              The replacement transmitters are functionally and electrically
adequacy of Modification Testing, the inspectors did review several of the
              equivalent. All functional and operability tests were performed with
modification Work Plans (WPs) for technical adequacy, proper review and
              revised   Surveillance   Instructions and Instrument Maintenance
approval, adequacy of safety evaluation as well as drawing and procedure
                Instructions (IMI).   An error in documentation was noted on IMI-135
updates. Work Plans reviewed as well as inspection findings are as follow:
              (Foxboro Instrument N-E130M Assembly Instruction) Appendix C data sheet
l
              page 1 of 4, Rev. 5 for 2-PDT-30-42 instrument. The work plan
a.
Containment Pressure Transmitter Modifications
i
Engineering Change Notice (ECN) 6554 and WP 11912 replaces the existing
containment pressure transmitters 1 & 2-PDT-30-42 and 1 & 2-PDT-30-43
with qualified Foxboro transmitters per NUREG 0588. These transmitters
provide input to containment isolation and containment spray logic.
The replacement transmitters are functionally and electrically
equivalent. All functional and operability tests were performed with
revised
Surveillance
Instructions
and
Instrument
Maintenance
Instructions (IMI).
An error in documentation was noted on IMI-135
(Foxboro Instrument N-E130M Assembly Instruction) Appendix C data sheet
page 1 of
4,
Rev. 5 for 2-PDT-30-42 instrument.
The work plan


  .
.
.
                                        3
.
      documentation indicated that lubricant (P/N N0114AA) was used whereas
3
      the correct lubricant should have been P/N X0114AA. A review of power
documentation indicated that lubricant (P/N N0114AA) was used whereas
      store procurement records indicated that P/N X0114AA was used for the
the correct lubricant should have been P/N X0114AA. A review of power
      assembly installation. The cognizant engineer was made aware of this
store procurement records indicated that P/N X0114AA was used for the
      documentation error. The inspector further reviewed all greases,
assembly installation. The cognizant engineer was made aware of this
      sealants, and lubricants used in Work Plan 11912 for traceability and
documentation error.
      proper usage. No deficiencies were noted other than this documentation
The inspector further reviewed all greases,
      error.
sealants, and lubricants used in Work Plan 11912 for traceability and
      The inspector reviewed Work Plan 11912 closecut package for adequacy
proper usage. No deficiencies were noted other than this documentation
      with regulatory requirements and commitments.         The work ' plan
error.
      subsections reviewed included a sampling of the work plan control
The inspector reviewed Work Plan 11912 closecut package for adequacy
      section, the work plan specification section,       the modification
with regulatory requirements and commitments.
      authorization section, the data inspection sheet section, the material
The work ' plan
      traceability section, and the vendor information section.           No
subsections reviewed included a sampling of the work plan control
      deficiencies were noted.
section, the work plan specification section,
    b. Reactor Coolant System Transmitters Removal to Outside the Crane Wall
the modification
      ECN L6439   and WP 11750 moves existing reactor coolant system
authorization section, the data inspection sheet section, the material
      transmitters 1 & 2 LT-68-320,1 & 2 PT-68-522 and 1 & 2 PT-68-523 to
traceability section, and the vendor information section.
      outside the polar crane wall. The work plan was reviewed to determine
No
        if regulatory requirements were being met.     The work plan status
deficiencies were noted.
      currently was under the implementation and closecut phases. Some
b.
      portions of the work plan documentation was not yet complete. Work
Reactor Coolant System Transmitters Removal to Outside the Crane Wall
        instructions and in process signoffs were adequate as completed. The
ECN L6439
      Accountability of Modification Material forms, required for level I and
and WP 11750 moves existing reactor coolant system
        II materials (AI-19, Part IV, Attachment 16), were missing from the work
transmitters 1 & 2 LT-68-320,1 & 2 PT-68-522 and 1 & 2 PT-68-523 to
      package. - This traceability form is required when material ordered for
outside the polar crane wall. The work plan was reviewed to determine
      one ECN is used instead for another ECN. Material ordered for ECN
if regulatory requirements were being met.
      6533, 6550 was used on this work package, ECN 6439. The cognizant
The work plan status
      engineer noted that the required forms will be included when the work
currently was under the implementation and closecut phases.
      plan is closed out. No other deficiencies were noted during the sample
Some
        review.
portions of the work plan documentation was not yet complete.
    c. Instrument Setpoint Changes . Due to Environmental Consideration in
Work
        Various Systems
instructions and in process signoffs were adequate as completed. The
        ECN L6551 and WP 11916 revises setpoints for various - safety-related
Accountability of Modification Material forms, required for level I and
        instruments to allow for instrument inaccuracies due to harsh
II materials (AI-19, Part IV, Attachment 16), were missing from the work
        environments resulting from a high energy line break. The work plan
package. - This traceability form is required when material ordered for
        documentation was reviewed for regulatory adherence and completeness
one ECN is used instead for another ECN.
      All instruments in the work plan are 10 CFR Part 50.49 devices. .The
Material ordered for ECN
        setpoints were     changed   using existing plant procedures.     No
6533, 6550 was used on this work package, ECN 6439. The cognizant
        deficiencies were noted.
engineer noted that the required forms will be included when the work
    d. Upper Head Injection Water Tank Level Switch Replacement
plan is closed out. No other deficiencies were noted during the sample
        ECN L6359 and WP 11751 replaces the four Barton Model 288A level
review.
        switches on the upper head injection water tank with more reliable
c.
        switches. The switches function to close the UHI isolation valves on
Instrument Setpoint Changes . Due to Environmental Consideration in
Various Systems
ECN L6551 and WP 11916 revises setpoints for various - safety-related
instruments to allow for instrument inaccuracies due to harsh
environments resulting from a high energy line break. The work plan
documentation was reviewed for regulatory adherence and completeness
All instruments in the work plan are 10 CFR Part 50.49 devices. .The
setpoints were
changed
using
existing plant procedures.
No
deficiencies were noted.
d.
Upper Head Injection Water Tank Level Switch Replacement
ECN L6359 and WP 11751 replaces the four Barton Model 288A level
switches on the upper head injection water tank with more reliable
switches. The switches function to close the UHI isolation valves on


    .
.
.
                                            4
.
            low level in the tank.       The closure of these valves preven.ts
4
            introduction of nitrogen gas into the RCS following the injection of
low level in the tank.
            borated water into the RCS. Under the ECN, the Barton level switches
The closure of these valves preven.ts
            were replaced with functionally equivalent switches.
introduction of nitrogen gas into the RCS following the injection of
            After the. initial completion of work on this work plan it was noted
borated water into the RCS. Under the ECN, the Barton level switches
            that a design error existed in the connection wiring drawings. A field
were replaced with functionally equivalent switches.
            change request (FCR4335) was initiated to rework the design errors and
After the. initial completion of work on this work plan it was noted
            this rework has not been completed to date; therefore, this work plan
that a design error existed in the connection wiring drawings. A field
            is still in the implementation work phase. The work plan, procedural
change request (FCR4335) was initiated to rework the design errors and
            step 15, related to plant housekeeping after maintenance was not signed
this rework has not been completed to date; therefore, this work plan
            off as complete although the initial work was completed ~in
is still in the implementation work phase. The work plan, procedural
            September 1985. The signoff for the foreman to verify cleanliness
step 15, related to plant housekeeping after maintenance was not signed
            should occur after each work phase to assure adequate work controls and
off as complete although the
            plant housekeeping. No other comments can be currently made about this
initial work was completed ~in
            work plan since it is still in process. The cognizant engineer was
September 1985.
            informed of all inspector concerns.
The signoff for the foreman to verify cleanliness
  6. Modification Testing (72701)
should occur after each work phase to assure adequate work controls and
      The inspectors selected for review several WPs in the areas of Mechanical
plant housekeeping. No other comments can be currently made about this
      Modification, Electrical Modification and Instrument Modification. The WPs
work plan since it is still in process. The cognizant engineer was
      selected were those initiated between August 1985 and present, with an
informed of all inspector concerns.
      attempt to concentrate on modifications in the area of EQ upgrade. The WPs
6.
      selected, including those discussed in paragraph five, included the
Modification Testing (72701)
      following:
The inspectors selected for review several WPs in the areas of Mechanical
      -
Modification, Electrical Modification and Instrument Modification. The WPs
            11750 (Relocate level transmitter 1 & 2-LT-68-320 & 1 & 2-PT-68-522 &
selected were those initiated between August 1985 and present, with an
                    523), Units 1 & 2
attempt to concentrate on modifications in the area of EQ upgrade. The WPs
      -
selected, including those discussed in paragraph five, included the
            11751 (Replace Barton level switch on UHI tank), Unit 1
following:
      -
-
            11762 (PMT 52), Unit 1
11750 (Relocate level transmitter 1 & 2-LT-68-320 & 1 & 2-PT-68-522 &
      -
523), Units 1 & 2
            11773 (Replace bolted bonnet valves), Unit 1
-
      -
11751 (Replace Barton level switch on UHI tank), Unit 1
            11834 (Install flange on various component cooling lines), Unit 2
11762 (PMT 52), Unit 1
      -
-
            11853 (Replace wiring on limitorque operators), Unit 2
11773 (Replace bolted bonnet valves), Unit 1
      -
-
            11866 (Replace wiring on limitorque operators), Unit 1
-
      -
11834 (Install flange on various component cooling lines), Unit 2
            11890 (PMT 74 Auto Shut Trip), Unit 2
11853 (Replace wiring on limitorque operators), Unit 2
      -
-
            11893 (Relocate PT-68-322 & 323 & LT-68-320), Unit 2
-
        -
11866 (Replace wiring on limitorque operators), Unit 1
            11897 (Replace solenoid vivs), Units 1 & 2
11890 (PMT 74 Auto Shut Trip), Unit 2
        -
-
            11906 (Replace motors on FCV-2-074-001 & 002), Unit 2
-
11893 (Relocate PT-68-322 & 323 & LT-68-320), Unit 2
11897 (Replace solenoid vivs), Units 1 & 2
-
-
11906 (Replace motors on FCV-2-074-001 & 002), Unit 2


  .
.
.
                                            5
.
  -
5
          11912 (Replace 1, 2-PDT-30-42 & 43), Units 1 & 2
11912 (Replace 1, 2-PDT-30-42 & 43), Units 1 & 2
  -
-
          11916 (Change setpoints on various safety-related WST), Unit 2
-
    -
11916 (Change setpoints on various safety-related WST), Unit 2
          11928 (Replace NAMCO limit switches sys 30, 63, 77, 81 & 68), Units
-
                    1&2
11928 (Replace NAMCO limit switches sys 30, 63, 77, 81 & 68), Units
    -
1&2
          12040 (Replace Rework & Reroute PP-7118 power feed for DG 2BB),
12040 (Replace Rework & Reroute PP-7118 power feed for DG 2BB),
                    Unit 2
-
    --
Unit 2
          12074 (Replace Nozzles on Steam generators), Unit 2
--
    The review of the above work plans concentrated on the MT aspects of the
12074 (Replace Nozzles on Steam generators), Unit 2
    Modification Packages. A brief description of the Sequoyah MT program, as
The review of the above work plans concentrated on the MT aspects of the
    previously discussed in Inspection Report 327, 328/86-20, is provided to
Modification Packages. A brief description of the Sequoyah MT program, as
    clarify the licensee's terminology and program description. AI-19, Part IV,
previously discussed in Inspection Report 327, 328/86-20, is provided to
    Revision 18, is the controling document and specifies the MT process. This
clarify the licensee's terminology and program description. AI-19, Part IV,
    instruction requires a PiiT if the modification was major and the Division
Revision 18, is the controling document and specifies the MT process.
    of Nuclear Engineering (DNE) required it through issuance of a test scoping
This
    document. However, the majority of testing associated with modifications
instruction requires a PiiT if the modification was major and the Division
    falls into the category of post modification functional test (PMFT). When a
of Nuclear Engineering (DNE) required it through issuance of a test scoping
    PMFT is required, AI-19, Part IV requires this test be specified in the WP.
document. However, the majority of testing associated with modifications
    The WP that requires a PMFT must list all checks or tests necessary to be
falls into the category of post modification functional test (PMFT). When a
    performed before returning the equipment to service. This functional test
PMFT is required, AI-19, Part IV requires this test be specified in the WP.
    is required to be comprehensive enough to ensure that the new components
The WP that requires a PMFT must list all checks or tests necessary to be
    perform their intended function and that the work did not inadvertently
performed before returning the equipment to service.
    degrade an operating system or component.
This functional test
    Specifics of the Work Plans reviewed and the inspectors' findings are
is required to be comprehensive enough to ensure that the new components
    provided as follows:
perform their intended function and that the work did not inadvertently
    a.   Main Steam and Feedwater Root Valves Replacement
degrade an operating system or component.
            ECN 6183 and WP 11773 replaced Hancock 5500 valves with Voght 300 in
Specifics of the Work Plans reviewed and the inspectors' findings are
            portions of Main Steam and Main Auxiliary Feedwater System where design
provided as follows:
            temperature and pressure caused leakage. This work (replacement) was
a.
            exempt from ASME Section XI, hydrostatic testing since all piping,
Main Steam and Feedwater Root Valves Replacement
            valves and fittings were one-inch or smaller. As a matter of prudence,
ECN 6183 and WP 11773 replaced Hancock 5500 valves with Voght 300 in
            the cognizant engineer indicated that the affected valves and piping
portions of Main Steam and Main Auxiliary Feedwater System where design
          would be inspected for leaks. Inspection will be either at hydrostatic
temperature and pressure caused leakage.
            or operating conditions.   No deficiencies were identified.
This work (replacement) was
    b.     Installation of Flanges
exempt from ASME Section XI, hydrostatic testing since all piping,
            ECN 6499 and WP 11834 install flanges in the component cooling water
valves and fittings were one-inch or smaller. As a matter of prudence,
            inlet, outlet and relief valve lines to' the vent . condenser heat
the cognizant engineer indicated that the affected valves and piping
            exchanger associated with the Boric Acid Evaporator, Package "B".
would be inspected for leaks. Inspection will be either at hydrostatic
            Functional testing consisted of a hydrostatic test per SI-265,
or operating conditions.
            " Hydrostatic Testing Following Repairs and Modifications". The
No deficiencies were identified.
            purpose of the Hydro was to test the newly installed flanges and
b.
            welds. Test pressure was 165 psig.         In addition to a visible
Installation of Flanges
            examination of the welds, a liquid penetrant examination was performed
ECN 6499 and WP 11834 install flanges in the component cooling water
            by the licensee.   No deficiencies were identified.
inlet, outlet and relief valve lines to' the vent . condenser heat
exchanger associated with the Boric Acid Evaporator, Package
"B".
Functional testing consisted of a hydrostatic test per SI-265,
" Hydrostatic Testing Following Repairs and Modifications".
The
purpose of the Hydro was to test the newly installed flanges and
welds.
Test pressure was 165 psig.
In addition to a visible
examination of the welds, a liquid penetrant examination was performed
by the licensee.
No deficiencies were identified.


                                                                                    ,
,
        .
.
    .
.
                                          6
6
        c. Pressurizer Level Transmitter Relocation
c.
          ECN 6439 and WP 11893 relocates level transmitters from inside the
Pressurizer Level Transmitter Relocation
          crane wall to outside the crane wall in the incore instrument room.
ECN 6439 and WP 11893 relocates level transmitters from inside the
          The location was changed to the outside crane wall so maintenance can
crane wall to outside the crane wall in the incore instrument room.
          be performed in mode 1, 2 and 3.     This will also. reduce radiation
The location was changed to the outside crane wall so maintenance can
          exposure when working on the transmitters in modes 4-6.       Functional
be performed in mode 1, 2 and 3.
          testing consisted of calibration of. level transmitters and Non
This will also. reduce radiation
          Destructive Examination (NDE) of the welds.         No problems were
exposure when working on the transmitters in modes 4-6.
          identified with this modification.
Functional
  '
testing consisted of calibration of. level transmitters and Non
        d. Steam Generator J-Nozzles Replacement
Destructive Examination (NDE) of the welds.
          NCR 2215 and WP 12074 removes and replace original carbon steel
No problems were
          J-nozzles with new Inconel J-Nozzles. The subject work activities were
identified with this modification.
          performed under the cognizance of the onsite Combustion Engineering -
'
          (CE) Task Manager. QC visually examined "J" Nozzle Welds repairs per
d.
          OP-9.1, Rev. 5. A final inspection of cleanliness was performed by QC.
Steam Generator J-Nozzles Replacement
          No post modification testing nor functional testing were required for
NCR 2215 and WP 12074 removes and replace original carbon steel
          this modification. No deficiencies were identified.
J-nozzles with new Inconel J-Nozzles. The subject work activities were
        e. Limit Switch Replacements
performed under the cognizance of the onsite Combustion Engineering -
          ECN 6556 and WP 11928 replaced existing limit switches on various air
(CE) Task Manager. QC visually examined "J" Nozzle Welds repairs per
          operated valves in systems 30, 63, 77, 81, and 68 with environmentally
OP-9.1, Rev. 5.
          qualified NAMCO brand limit switches to meet 10 CFR Part 50.49
A final inspection of cleanliness was performed by QC.
          requirements. Specified functional tests consisted of cycling the
No post modification testing nor functional testing were required for
          valves to ensure proper limit switch adjustment / valve position
this modification. No deficiencies were identified.
          indication and stroke timing per SI-166.6. No problems were identified
e.
          with this modification.
Limit Switch Replacements
        f. Limitorque Valve Modifications
ECN 6556 and WP 11928 replaced existing limit switches on various air
          ECN L6544 and WPs 11866 (Unit 1) and 11853 (Unit 2) replaced all wiring
operated valves in systems 30, 63, 77, 81, and 68 with environmentally
          within the limit switch compartment of approximately 214 limitorque
qualified NAMCO brand limit switches to meet 10 CFR Part 50.49
          valve   operators with     environmentally qualified wiring.     This
requirements.
          Modification involved valves contained in systems 1, 3, 26, 62, 63, 67,
Specified functional tests consisted of cycling the
          68, 70 and 74. Appropriate drawings were changed as part of this wire
valves to ensure proper limit switch adjustment / valve position
          replacement effort, such that previously jumpered out limit / torque
indication and stroke timing per SI-166.6. No problems were identified
          switches were eliminated 'from control circuits altogether in order to
with this modification.
          simplify the circuits and their rewiring. Additionally, in the case of
f.
            16 valves, wiring changes were made to eliminate a limit switch that
Limitorque Valve Modifications
          was effectively making an existing torque swite:h in their respective
ECN L6544 and WPs 11866 (Unit 1) and 11853 (Unit 2) replaced all wiring
          control circuit non-functional.
within the limit switch compartment of approximately 214 limitorque
          The functional tests specified in the work plans consisted of a hand
valve
          cycling of the valve actuators with a check on limit switches, closing
operators with
          and opening contractors. The valves were ther cycled open and closed
environmentally qualified wiring.
          electrically. Excluding the 16 valves that were modified to include an
This
          existing torque switch as a functional part of their control circuit,
Modification involved valves contained in systems 1, 3, 26, 62, 63, 67,
            the majority of these limitorque valves are containment isolation
68, 70 and 74. Appropriate drawings were changed as part of this wire
      a
replacement effort, such that previously jumpered out limit / torque
switches were eliminated 'from control circuits altogether in order to
simplify the circuits and their rewiring. Additionally, in the case of
16 valves, wiring changes were made to eliminate a limit switch that
was effectively making an existing torque swite:h in their respective
control circuit non-functional.
The functional tests specified in the work plans consisted of a hand
cycling of the valve actuators with a check on limit switches, closing
and opening contractors.
The valves were ther cycled open and closed
electrically. Excluding the 16 valves that were modified to include an
existing torque switch as a functional part of their control circuit,
the majority of these limitorque valves are containment isolation
a
m.
m.


  .
.
.
                                        7
.
      valves and are therefore subject to the surveillance requirements of TS
7
      3.6.3. Accordingly, TS Surveillance 4.6.3.1 requires that containment
valves and are therefore subject to the surveillance requirements of TS
      isolation valves be cycled and timed to demonstrate them operable prior
3.6.3.
      to returning them to service after maintenance, repair or replacement
Accordingly, TS Surveillance 4.6.3.1 requires that containment
      work is performed on the valve or its associated actuator, control or
isolation valves be cycled and timed to demonstrate them operable prior
      power circuit.     The stroke timing test associated with these
to returning them to service after maintenance, repair or replacement
      containment isolation valves i s SI-166.6. As for the 16 excluded
work is performed on the valve or its associated actuator, control or
      valves, section 6.8 of Technical Instruction (TI) -69, " Summary of
power circuit.
      Pre-and Post-Maintenance Valve Tests For ASME Section XI and 10 CFR 50
The stroke timing test associated with these
      Appendix J," requires that a stroke timing test be performed per
containment isolation valves i s SI-166.6.
      SI-166.6 whenever maintenance of this nature is performed on a valve
As for the 16 excluded
      control system. Consequently, the stroke timing test of each valve per
valves, section 6.8 of Technical Instruction (TI) -69, " Summary of
      SI-166.6 would be required to be performed in order to prove valve
Pre-and Post-Maintenance Valve Tests For ASME Section XI and 10 CFR 50
      operability; however, SI-166.6 was not specified in either work plan as
Appendix
      a test to be performed. Section 4.1.1.13.d (2) of Administrative
J,"
      Instruction (AI)-19, Part IV, requires that any checks or tests
requires that a stroke timing test be performed per
      necessary -to return equipment back to service be specified in the WP.
SI-166.6 whenever maintenance of this nature is performed on a valve
      The omission of SI-166.6 from the WPs is considered a violation of
control system. Consequently, the stroke timing test of each valve per
      AI-19, Part-IV (327, 328/86-43-01). It should be noted that ongoing
SI-166.6 would be required to be performed in order to prove valve
      MOVATS Testing of these valves, although not specified in the subject
operability; however, SI-166.6 was not specified in either work plan as
      work plans, will include a stroke test per SI-166.6.
a test to be performed.
    g. Residual Heat Removal (RHR) Loop Isolation Valves
Section 4.1.1.13.d (2) of Administrative
      ECN 6540 and WP 11906 replaced the existing motors on valves 2-FCV-74-1
Instruction (AI)-19, Part IV, requires that any checks or tests
      and 2-FCV-74-2 with environmentally qualified motors.
necessary -to return equipment back to service be specified in the WP.
      These valves are the RHR suction isolation valves off of reactor
The omission of SI-166.6 from the WPs is considered a violation of
      coolant loop 4 and are considered necessary to mitigate an RHR line
AI-19, Part-IV (327, 328/86-43-01).
      break.   Specified functional tests included megger, grease, and
It should be noted that ongoing
      rotational checks of the motors, and the performance of a stroke timing
MOVATS Testing of these valves, although not specified in the subject
      test of the valves per SI-166.6. TS Surveilla"ce 4.4.6.2.2.c requires
work plans, will include a stroke test per SI-166.6.
      that these valves be demonstrated operable by verifying leakage to be
g.
      within its limits prior to returning the valve (s) to service following
Residual Heat Removal (RHR) Loop Isolation Valves
      maintenance, repair or replacement work on the valve (s). Additionally,
ECN 6540 and WP 11906 replaced the existing motors on valves 2-FCV-74-1
      TI-69 requires a Post-Maintenance Leak Test be performed on a motor
and 2-FCV-74-2 with environmentally qualified motors.
      operated valve when motors are not replaced with identical motors. A
These valves are the RHR suction isolation valves off of reactor
      Leak Rate Test would be indicated in this case since the existing
coolant loop 4 and are considered necessary to mitigate an RHR line
      motors were rated at 2.6 HP, whereas the replacement motors were rated
break.
      at 4~0 HP. The Leak Test associated with these valves is SI-166.18,
Specified functional tests included megger, grease, and
            .
rotational checks of the motors, and the performance of a stroke timing
      "RHR Return Valve Leak Rate Test". The omission of SI-166.18 from the
test of the valves per SI-166.6. TS Surveilla"ce 4.4.6.2.2.c requires
      WP as a specified test to be performed prior to returning the valves to
that these valves be demonstrated operable by verifying leakage to be
        service is not in accordance with AI-19, Part IV. This is considered
within its limits prior to returning the valve (s) to service following
      another example of Violation 327,328/86-43-01 identified in paragraph f
maintenance, repair or replacement work on the valve (s). Additionally,
      above. It is recognized that due to the duration of this outage,
TI-69 requires a Post-Maintenance Leak Test be performed on a motor
        SI-166.18 would have also been required to be performed by TS
operated valve when motors are not replaced with identical motors. A
        4.4.6.2.2.c prior to entering mode 2.     This would be verified in
Leak Rate Test would be indicated in this case since the existing
      General Operating Instruction (GOI)-1, " Unit Heat Up From Cold
motors were rated at 2.6 HP, whereas the replacement motors were rated
        Shutdown to Hot Standby."
at 4~0 HP.
                                      -         -     . - - _ _ _ .   . . _ _ . _ _ _ . . -_
The Leak Test associated with these valves is SI-166.18,
.
"RHR Return Valve Leak Rate Test". The omission of SI-166.18 from the
WP as a specified test to be performed prior to returning the valves to
service is not in accordance with AI-19, Part IV. This is considered
another example of Violation 327,328/86-43-01 identified in paragraph f
above.
It is recognized that due to the duration of this outage,
SI-166.18 would have also been required to be performed by TS
4.4.6.2.2.c prior to entering mode 2.
This would be verified in
General Operating Instruction (GOI)-1, " Unit Heat Up From Cold
Shutdown to Hot Standby."
-
-
. - - _ _ _ .
. . _ _
.
. .
-


  m
m
      *
*
    .
.
                                          8
8
        h. Replace Solenoid Valves With New EQ Valves
h.
Replace Solenoid Valves With New EQ Valves
4
4
          ECN 6552 and WP 11897 replaced existing solenoid control valves with
ECN 6552 and WP 11897 replaced existing solenoid control valves with
          new EQ valves required to meet the requirements of NUREG 0552. The WP
new EQ valves required to meet the requirements of NUREG 0552. The WP
          reviewed replaced 12 valves; three in system 43, six in system 62, one
reviewed replaced 12 valves; three in system 43, six in system 62, one
          in system 63, and two in system 87. The new valves were Automatic
in system 63, and two in system 87. The new valves were Automatic
          Switch Co (ASCO) model #206-381 and model'#8316-54E. Per the vendor
Switch Co (ASCO) model #206-381 and model'#8316-54E.
          installation and maintenance instruction manual, the model #206-381
Per the vendor
          valves were required to be mounted with the solenoid vertical and
installation and maintenance instruction manual, the model #206-381
,          upright.
valves were required to be mounted with the solenoid vertical and
          The inspectors review of the above WP verified that inspection records ,
upright.
          were included. These records indicated that the solenoid on valves     1
,
          2-FSV-43-(202, 207 and 208), model #206-381, were oriented vertical .
The inspectors review of the above WP verified that inspection records
          However, when the inspector reviewed the installation and inspection
,
          step of the WP, Step 8.2a of Vertical was defined as, " Vertical i 45 .
were included.
          The inspector requested TVA provide justification for the 45
These records indicated that the solenoid on valves
          allowance. The modification engineer eventually produced a letter
1
          dated April 29, 1985, where an ASCO sales manager indicated that the
2-FSV-43-(202, 207 and 208), model #206-381, were oriented vertical .
          model 206 series valves could function with a solenoid orientation up
However, when the inspector reviewed the installation and inspection
          to 45     from vertical . However, the letter went on to state that
step of the WP, Step 8.2a of Vertical was defined as, " Vertical i 45 .
          seismic qualification for the 206 series was performed in the vertical
The inspector requested TVA provide justification for the 45
          position only and the effects of mounting in the other orientation
allowance.
          would have to be evaluated. The inspector requested the seismic test
The modification engineer eventually produced a letter
          data for other vertical orientation and received (from TVA) Seismic
dated April 29, 1985, where an ASCO sales manager indicated that the
          Simulation Test Report #17746-1. This report documented the Wyle
model 206 series valves could function with a solenoid orientation up
          Laboratories test performed June 9 and 10, 1986, for TVA under Purchase
to 45
          Order TV-56071A. The test concluded that for the seismic event the
from vertical .
          valves continued to function and maintain their structural integrity.
However, the letter went on to state that
          The inspector was satisfied with the information provided by TVA.
seismic qualification for the 206 series was performed in the vertical
          However, since TVA had installed the valves in April 1986, several
position only and the effects of mounting in the other orientation
          months before qualification testing, the modifications supervisor was
would have to be evaluated. The inspector requested the seismic test
          cautioned about the use of equipment in a manner not recommended or
data for other vertical orientation and received (from TVA) Seismic
          qualified by the manufacturer without prior testing or qualification by
Simulation Test Report #17746-1.
!         TVA. Additionally, if the installation was conditioned to seismic
This report documented the Wyle
l         qualification af ter installation it sFould have been specified in the
Laboratories test performed June 9 and 10, 1986, for TVA under Purchase
          WP. The functional testing review for this WP indicated that testing
Order TV-56071A. The test concluded that for the seismic event the
          was performed, however, cross referencing of the testing performed back
valves continued to function and maintain their structural integrity.
            to the WP was not always documented. Specifically, WP 11897 was not
The inspector was satisfied with the information provided by TVA.
            referenced on a SI-166.6 test package or master list reference for
However, since TVA had installed the valves in April 1986, several
          eight of the twelve valves. The inspector did, however, locate a valve
months before qualification testing, the modifications supervisor was
            functional tet t performed on the same date indicated in the WP but no
cautioned about the use of equipment in a manner not recommended or
            reference back to the WP could be produced by the licensee. SI-166.6
qualified by the manufacturer without prior testing or qualification by
            specifically required a test data package or master list notation to
!
            tie the specific test to the work plan. This failure to follow the
TVA.
            requirements of SI-166.6 is considered another example of Violation
Additionally, if the installation was conditioned to seismic
            327, 328/86-43-01 identified in paragraph f. above.
l
qualification af ter installation it sFould have been specified in the
WP. The functional testing review for this WP indicated that testing
was performed, however, cross referencing of the testing performed back
to the WP was not always documented.
Specifically, WP 11897 was not
referenced on a SI-166.6 test package or master list reference for
eight of the twelve valves. The inspector did, however, locate a valve
functional tet t performed on the same date indicated in the WP but no
reference back to the WP could be produced by the licensee.
SI-166.6
specifically required a test data package or master list notation to
tie the specific test to the work plan.
This failure to follow the
requirements of SI-166.6 is considered another example of Violation
327, 328/86-43-01 identified in paragraph f. above.


                                                                                      1
1
  .
.
.
                                        9
.
    1. Replacement of Cable PP711B in Cable. Tray AS-B1, Emergency Supply
9
      Breaker Feeder From 6.9KV Shutdown Board 2B-B
1.
      ECN 6627 and WP 12040 replaced a section of cable identified as PP711B.
Replacement of Cable PP711B in Cable. Tray AS-B1, Emergency Supply
      This work plan specified functional testing per SI-7 which was
Breaker Feeder From 6.9KV Shutdown Board 2B-B
      accompitshed on June 17, 1986. No problems were identified with this
ECN 6627 and WP 12040 replaced a section of cable identified as PP711B.
      modification.
This work plan specified functional testing per SI-7 which was
    J. PMT-74 Automatic Shunt Trip Modification Test (Unit 2)
accompitshed on June 17, 1986. No problems were identified with this
      ECN 6233 and WP 11890 specified the testing associated with the
modification.
      Automatic Shunt Trip Modification on Unit 2. This procedure had
J.
      several changes written prior to the completion of testing. Change
PMT-74 Automatic Shunt Trip Modification Test (Unit 2)
      #86-488 modified the expected voltage values at a specific test point.
ECN 6233 and WP 11890 specified the testing associated with the
      This' change was processed using a change form (Appendix G of AI-4) and
Automatic Shunt Trip Modification on Unit
      handled as an expeditious change. To understand the temporary change
2.
      process as'used by TVA, the following is provided:
This procedure had
      -
several changes written prior to the completion of testing.
            TS 6.8.3 allows temporary changes to plant committee approved
Change
            procedures under certain restrictions.
#86-488 modified the expected voltage values at a specific test point.
      -
This' change was processed using a change form (Appendix G of AI-4) and
            ANSI 18.7-1976, to which TVA is committed, also makes allowance
handled as an expeditious change.
            (paragraph 5.2.2) for the licensee to make temporary changes to a
To understand the temporary change
            procedure providing certain conditions are met.     This ANSI also
process as'used by TVA, the following is provided:
            requires this procedure change program to be described in writing
TS 6.8.3 allows temporary changes to plant committee approved
            by the licensee.
-
      -
procedures under certain restrictions.
            AI-4, " Plant Instructions   -
ANSI 18.7-1976, to which TVA is committed, also makes allowance
                                            Document Control", is the plant
-
            procedure TVA used to describe this Procedure Change Program.
(paragraph 5.2.2) for the licensee to make temporary changes to a
            Section 13 of this procedure discusses the actual change process.
procedure providing certain conditions are met.
            The method of changing a Plant Operation Review Committee (PORC)
This ANSI also
            approved procedure in an expeditious manner is described in
requires this procedure change program to be described in writing
            paragraph 13.1. AI-4 only allows expeditious changes under the
by the licensee.
            following two conditions:
Document Control", is the plant
            (1) To make changes which will remain in effect for only a limited
-
                  number of instruction performances (e.g., an SI needs to be
AI-4, " Plant Instructions
                  performed differently this one time because the plant is in an
-
                  abnormal configuration).
procedure TVA used to describe this Procedure Change Program.
            (2) To make urgently needed revisions when there is not time to go
Section 13 of this procedure discusses the actual change process.
                  through the original type of review / approval cycle (e.g., an NRC
The method of changing a Plant Operation Review Committee (PORC)
                  inspection identifies a serious deficiency in an instruction'which
approved procedure in an expeditious manner is described in
                  must be corrected immediately). In this case, the plant
paragraph 13.1.
                  instruction change form (Appendix G of AI-4) authorizes an
AI-4 only allows expeditious changes under the
                  expeditious change practice until a permanent instruction change
following two conditions:
                  can be issued.
(1) To make changes which will remain in effect for only a limited
number of instruction performances (e.g., an SI needs to be
performed differently this one time because the plant is in an
abnormal configuration).
(2) To make urgently needed revisions when there is not time to go
through the original type of review / approval cycle (e.g., an NRC
inspection identifies a serious deficiency in an instruction'which
must be corrected immediately).
In this case, the plant
instruction change form (Appendix G of AI-4) authorizes an
expeditious change practice until a permanent instruction change
can be issued.


                                                                            ,
,
  .
.
.
.
                                10
10
    -
As part of the Post Modification and Post Maintenance Testing
        As part of the Post Modification and Post Maintenance Testing
-
        program, plant engineers routinely specify in the WP or on the
program, plant engineers routinely specify in the WP or on the
        maintenance form to " accomplish the applicable portions" of
maintenance form to " accomplish the applicable portions" of
        approved procedure.   This method appears to circumvent the
approved procedure.
        procedure change process as described in TS 6.8.3 and AI-4.
This method appears to circumvent the
        Additionally, if the user omits certain steps or picks and chooses
procedure change process as described in TS 6.8.3 and AI-4.
        steps of the approved procedure he has in fact changed the intent
Additionally, if the user omits certain steps or picks and chooses
        of the original procedure. In this case, TS 6.8.3 requires that a
steps of the approved procedure he has in fact changed the intent
        change with the same level of review and approval be executed
of the original procedure. In this case, TS 6.8.3 requires that a
        prior to use.
change with the same level of review and approval be executed
    The specific example of changing a committee approved procedure (ie.,
prior to use.
    changes to WP 11890) in an-expeditious manner as well as the improper
The specific example of changing a committee approved procedure (ie.,
    changing of committee approved procedures (i.e., " accomplish the
changes to WP 11890) in an-expeditious manner as well as the improper
    applicable portions") is considered a violation of TS 6.8.3     (327,
changing of committee approved procedures
    328/86-43-02).
(i.e.,
" accomplish the
applicable portions") is considered a violation of TS 6.8.3
(327,
328/86-43-02).
}}
}}

Latest revision as of 15:04, 23 May 2025

Insp Repts 50-327/86-43 & 50-328/86-43 on 860728-0801. Violations Noted:Failure to Properly Implement Requirements of Administrative Instruction & Change Plant Approved Procedures
ML20210E310
Person / Time
Site: Sequoyah  
Issue date: 08/26/1986
From: Branch M, Carroll R, Debs B, Mathis J, Paulk G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20210E303 List:
References
50-327-86-43, 50-328-86-43, NUDOCS 8609220243
Download: ML20210E310 (11)


See also: IR 05000327/1986043

Text

,

'

[gn Err

UNITED STATES

o

NUCLEAR REGULATORY COMMISSION

"

y'

REGloN 11

n

.y

j

101 MARIETTA STREET, N.W.

'*

ATLANT A. GEORGI A 30323

'+9 . . . . . ,o

Report Nos.:

50-327/86-43 and 50-328/86-43

Licensee: Tennessee Valley Authority

6N38 A Lookout Place

1101 Market Street

Chattanooga, TN 37401

Docket Nos.: 50-327 and 50-328

License Nos.: DPR-77 and DPR-79

Facility Name:

Sequoyah Units 1 and 2

Inspection Conducted: July 28, 1986 - August 1, 1986

Inspectors:

~ Date' Signed

-

M. W. Braren, InspectpliE TKm Leader

kYl

N

R. E. Carroll, Jr. , Projecf/ffgfiieer

'Date Signed

G. Paul k, L. , ;#iM'/ $_

-

Date Signed

W

S

'

I g ec V (Browns Ferry)

Y

ma

l

$

J. Mathi W KeacL~r inspg#Cor 7

Tate Signed

Approved by:

__

/

,,/

y 24

B. Debs, Section Chief

D4te Signed

j

Division of Reactor Projects

l

SUMMARY

Scope:

This special, announced inspection was conducted in the area of

Modification Testing (MT) with a concentration on testing associated with

Environmentally Qualified (EQ) equipment modifications. This inspection involved

a review of major or complicated Post Modification Tests (PMT), as well as a

!

review of Post Modification Functional Tests (PMFT). Additionally, a followup of

associated Inspector Identified Items, discussed in paragraph 9 of Inspection

Report 327, 328/86-20, was performed.

!

Results:

In the areas inspected, two violations were identified.

The first

l

violation, discussed in paragraph 6, involved multiple examples of

failure to

!

properly implement the requirements of Administrative Instruction (AI)-19,

Part IV, " Plant Modifications After Licensing" and Surveillance Instruction

(51)-166.6, " Post Maintenance Testing of Category A and B Valves." The second

violation, also discussed in paragraph 6, involved a failure to properly change

plant approved procedures.

8609220243 860912

PDR

ADOCK 05000327

i

i

G

PDR

]

.

.

REPORT DETAILS

1.

Licensee Employee Contacted

  • P. R. Wallace, Plant Manager

L. M. Nobles, Operations and Engineering Superintendent

  • B. M. Patterson, Maintenance Superintendeot
  • N. E. Andrews, Site Quality Manager
  • D. C. Craven, Quality Assurance Manager
  • G. B. Kirk, Compliance Licensing Supervisor
  • R. W. Olson, Modifications Branch Manager
  • M. R. .Sedlacik, Electrical Section Manager, Modifications Branch
  • R. M. Mooney, Systems Engineering Supervisor
  • J. A. McPherson, Mechanical Test Supervisor
  • R. W. Fortenberry, Technical Support Supervisor
  • R. V. Pierce, Mechanical Maintenance Supervisor
  • H. D. Elkins Jr., Instrument Maintenance Supervisor
  • M. A. Skarzinski, Electrical Maintenance Supervisor
  • R. H. Smith, Project Management
  • J. H. Sullivan, Regulatory Engineering Supervisor
  • P. H. Buckholz, Sequoyah Site Representative

S. D. Gilley, Modification Engineer

E. L. Legg, Modification Engineer

J. Edwards, Instrument Maintenance

T. L. Rutledge, Modification Engineer

D._R. Branham, Modification Engineer

Other licensee employees contacted included technicians, operators, shift

engineers and maintenance personnel.

  • Attended exit interview

2.

Exit Interview

The inspection scope and findings were summarized on August 1,1986, with

those persons indicated by an asterisk in paragraph one above.

The

following new items were discussed:

a.

Violation for failure to properly implement the requirements of AI-19,

Part IV and SI-166.6 in the area of functional testing.

b.

Violation for failure to properly change plant approved procedures.

This item was initially categorized as an unresolved item then upgraded

after additional discussion with NRC personnel.

The licensee acknowledged the inspection findings.

The licensee did not

identify as proprietary any material provided to the inspectors during the

inspection. At no time during the inspection period did the inspectors

provide written material to the licensee.

_

.

.

2

3.

Followup On Inspector Identified Items

a.

(Closed) IFI 327, 328/86-20-03; Review of modifications to Limitorque

Valves to determine effect, if any, of improper wiring. The issue was

. originally addressed in paragraph nine of inspection report 327,

328/86-20 and dealt with the rewiring of approximately 214 Limitorque

Operators to establish EQ qualifications as well as simplifying and

.

correcting limit and/or torque switch discrepancies. The inspector was

concerned with the possibility-that the improper wiring of limit / torque

switches could have had an effect on valve operation.

During the review of Work Plan (WP) 11866 (unit 1) and WP 11853

(unit 2), which rewired the limitorque valves, the inspector's concern

.

was re-addressed.

It was determined that some of the previous

torque / limit switch combinations did, under certain circumstances, have

the potential of preventing the fulfillment of valve function.

However, the inspector determined that these valves are part of the

ASME Section XI Article IWV valve test program and are tested for

operability on a routine basis per that program.

b.

(Closed) IFI 327, 328/86-20-11; Use of terminology of " perform the

applicable portions of a Plant Operations Review Committee (PORC)

approved procedure". This item is being combined with a related item

associated with changes to approved procedures.

Both items will be

.

resolved as part of that issue which is identified as Violation 327,

I

328/86-43-02 and discussed in detail in Paragraph 6 of this report.

4.

Unresolved Items

No Unresolved Items were identified during this inspection.

5.

Design, Design Changes, and Modifications (37700)

Although the major objective of this inspection was to determine the

adequacy of Modification Testing, the inspectors did review several of the

modification Work Plans (WPs) for technical adequacy, proper review and

approval, adequacy of safety evaluation as well as drawing and procedure

updates. Work Plans reviewed as well as inspection findings are as follow:

l

a.

Containment Pressure Transmitter Modifications

i

Engineering Change Notice (ECN) 6554 and WP 11912 replaces the existing

containment pressure transmitters 1 & 2-PDT-30-42 and 1 & 2-PDT-30-43

with qualified Foxboro transmitters per NUREG 0588. These transmitters

provide input to containment isolation and containment spray logic.

The replacement transmitters are functionally and electrically

equivalent. All functional and operability tests were performed with

revised

Surveillance

Instructions

and

Instrument

Maintenance

Instructions (IMI).

An error in documentation was noted on IMI-135

(Foxboro Instrument N-E130M Assembly Instruction) Appendix C data sheet

page 1 of

4,

Rev. 5 for 2-PDT-30-42 instrument.

The work plan

.

.

3

documentation indicated that lubricant (P/N N0114AA) was used whereas

the correct lubricant should have been P/N X0114AA. A review of power

store procurement records indicated that P/N X0114AA was used for the

assembly installation. The cognizant engineer was made aware of this

documentation error.

The inspector further reviewed all greases,

sealants, and lubricants used in Work Plan 11912 for traceability and

proper usage. No deficiencies were noted other than this documentation

error.

The inspector reviewed Work Plan 11912 closecut package for adequacy

with regulatory requirements and commitments.

The work ' plan

subsections reviewed included a sampling of the work plan control

section, the work plan specification section,

the modification

authorization section, the data inspection sheet section, the material

traceability section, and the vendor information section.

No

deficiencies were noted.

b.

Reactor Coolant System Transmitters Removal to Outside the Crane Wall

ECN L6439

and WP 11750 moves existing reactor coolant system

transmitters 1 & 2 LT-68-320,1 & 2 PT-68-522 and 1 & 2 PT-68-523 to

outside the polar crane wall. The work plan was reviewed to determine

if regulatory requirements were being met.

The work plan status

currently was under the implementation and closecut phases.

Some

portions of the work plan documentation was not yet complete.

Work

instructions and in process signoffs were adequate as completed. The

Accountability of Modification Material forms, required for level I and

II materials (AI-19, Part IV, Attachment 16), were missing from the work

package. - This traceability form is required when material ordered for

one ECN is used instead for another ECN.

Material ordered for ECN

6533, 6550 was used on this work package, ECN 6439. The cognizant

engineer noted that the required forms will be included when the work

plan is closed out. No other deficiencies were noted during the sample

review.

c.

Instrument Setpoint Changes . Due to Environmental Consideration in

Various Systems

ECN L6551 and WP 11916 revises setpoints for various - safety-related

instruments to allow for instrument inaccuracies due to harsh

environments resulting from a high energy line break. The work plan

documentation was reviewed for regulatory adherence and completeness

All instruments in the work plan are 10 CFR Part 50.49 devices. .The

setpoints were

changed

using

existing plant procedures.

No

deficiencies were noted.

d.

Upper Head Injection Water Tank Level Switch Replacement

ECN L6359 and WP 11751 replaces the four Barton Model 288A level

switches on the upper head injection water tank with more reliable

switches. The switches function to close the UHI isolation valves on

.

.

4

low level in the tank.

The closure of these valves preven.ts

introduction of nitrogen gas into the RCS following the injection of

borated water into the RCS. Under the ECN, the Barton level switches

were replaced with functionally equivalent switches.

After the. initial completion of work on this work plan it was noted

that a design error existed in the connection wiring drawings. A field

change request (FCR4335) was initiated to rework the design errors and

this rework has not been completed to date; therefore, this work plan

is still in the implementation work phase. The work plan, procedural

step 15, related to plant housekeeping after maintenance was not signed

off as complete although the

initial work was completed ~in

September 1985.

The signoff for the foreman to verify cleanliness

should occur after each work phase to assure adequate work controls and

plant housekeeping. No other comments can be currently made about this

work plan since it is still in process. The cognizant engineer was

informed of all inspector concerns.

6.

Modification Testing (72701)

The inspectors selected for review several WPs in the areas of Mechanical

Modification, Electrical Modification and Instrument Modification. The WPs

selected were those initiated between August 1985 and present, with an

attempt to concentrate on modifications in the area of EQ upgrade. The WPs

selected, including those discussed in paragraph five, included the

following:

-

11750 (Relocate level transmitter 1 & 2-LT-68-320 & 1 & 2-PT-68-522 &

523), Units 1 & 2

-

11751 (Replace Barton level switch on UHI tank), Unit 1

11762 (PMT 52), Unit 1

-

11773 (Replace bolted bonnet valves), Unit 1

-

-

11834 (Install flange on various component cooling lines), Unit 2

11853 (Replace wiring on limitorque operators), Unit 2

-

-

11866 (Replace wiring on limitorque operators), Unit 1

11890 (PMT 74 Auto Shut Trip), Unit 2

-

-

11893 (Relocate PT-68-322 & 323 & LT-68-320), Unit 2

11897 (Replace solenoid vivs), Units 1 & 2

-

-

11906 (Replace motors on FCV-2-074-001 & 002), Unit 2

.

.

5

11912 (Replace 1, 2-PDT-30-42 & 43), Units 1 & 2

-

-

11916 (Change setpoints on various safety-related WST), Unit 2

-

11928 (Replace NAMCO limit switches sys 30, 63, 77, 81 & 68), Units

1&2

12040 (Replace Rework & Reroute PP-7118 power feed for DG 2BB),

-

Unit 2

--

12074 (Replace Nozzles on Steam generators), Unit 2

The review of the above work plans concentrated on the MT aspects of the

Modification Packages. A brief description of the Sequoyah MT program, as

previously discussed in Inspection Report 327, 328/86-20, is provided to

clarify the licensee's terminology and program description. AI-19, Part IV,

Revision 18, is the controling document and specifies the MT process.

This

instruction requires a PiiT if the modification was major and the Division

of Nuclear Engineering (DNE) required it through issuance of a test scoping

document. However, the majority of testing associated with modifications

falls into the category of post modification functional test (PMFT). When a

PMFT is required, AI-19, Part IV requires this test be specified in the WP.

The WP that requires a PMFT must list all checks or tests necessary to be

performed before returning the equipment to service.

This functional test

is required to be comprehensive enough to ensure that the new components

perform their intended function and that the work did not inadvertently

degrade an operating system or component.

Specifics of the Work Plans reviewed and the inspectors' findings are

provided as follows:

a.

Main Steam and Feedwater Root Valves Replacement

ECN 6183 and WP 11773 replaced Hancock 5500 valves with Voght 300 in

portions of Main Steam and Main Auxiliary Feedwater System where design

temperature and pressure caused leakage.

This work (replacement) was

exempt from ASME Section XI, hydrostatic testing since all piping,

valves and fittings were one-inch or smaller. As a matter of prudence,

the cognizant engineer indicated that the affected valves and piping

would be inspected for leaks. Inspection will be either at hydrostatic

or operating conditions.

No deficiencies were identified.

b.

Installation of Flanges

ECN 6499 and WP 11834 install flanges in the component cooling water

inlet, outlet and relief valve lines to' the vent . condenser heat

exchanger associated with the Boric Acid Evaporator, Package

"B".

Functional testing consisted of a hydrostatic test per SI-265,

" Hydrostatic Testing Following Repairs and Modifications".

The

purpose of the Hydro was to test the newly installed flanges and

welds.

Test pressure was 165 psig.

In addition to a visible

examination of the welds, a liquid penetrant examination was performed

by the licensee.

No deficiencies were identified.

,

.

.

6

c.

Pressurizer Level Transmitter Relocation

ECN 6439 and WP 11893 relocates level transmitters from inside the

crane wall to outside the crane wall in the incore instrument room.

The location was changed to the outside crane wall so maintenance can

be performed in mode 1, 2 and 3.

This will also. reduce radiation

exposure when working on the transmitters in modes 4-6.

Functional

testing consisted of calibration of. level transmitters and Non

Destructive Examination (NDE) of the welds.

No problems were

identified with this modification.

'

d.

Steam Generator J-Nozzles Replacement

NCR 2215 and WP 12074 removes and replace original carbon steel

J-nozzles with new Inconel J-Nozzles. The subject work activities were

performed under the cognizance of the onsite Combustion Engineering -

(CE) Task Manager. QC visually examined "J" Nozzle Welds repairs per

OP-9.1, Rev. 5.

A final inspection of cleanliness was performed by QC.

No post modification testing nor functional testing were required for

this modification. No deficiencies were identified.

e.

Limit Switch Replacements

ECN 6556 and WP 11928 replaced existing limit switches on various air

operated valves in systems 30, 63, 77, 81, and 68 with environmentally

qualified NAMCO brand limit switches to meet 10 CFR Part 50.49

requirements.

Specified functional tests consisted of cycling the

valves to ensure proper limit switch adjustment / valve position

indication and stroke timing per SI-166.6. No problems were identified

with this modification.

f.

Limitorque Valve Modifications

ECN L6544 and WPs 11866 (Unit 1) and 11853 (Unit 2) replaced all wiring

within the limit switch compartment of approximately 214 limitorque

valve

operators with

environmentally qualified wiring.

This

Modification involved valves contained in systems 1, 3, 26, 62, 63, 67,

68, 70 and 74. Appropriate drawings were changed as part of this wire

replacement effort, such that previously jumpered out limit / torque

switches were eliminated 'from control circuits altogether in order to

simplify the circuits and their rewiring. Additionally, in the case of

16 valves, wiring changes were made to eliminate a limit switch that

was effectively making an existing torque swite:h in their respective

control circuit non-functional.

The functional tests specified in the work plans consisted of a hand

cycling of the valve actuators with a check on limit switches, closing

and opening contractors.

The valves were ther cycled open and closed

electrically. Excluding the 16 valves that were modified to include an

existing torque switch as a functional part of their control circuit,

the majority of these limitorque valves are containment isolation

a

m.

.

.

7

valves and are therefore subject to the surveillance requirements of TS 3.6.3.

Accordingly, TS Surveillance 4.6.3.1 requires that containment

isolation valves be cycled and timed to demonstrate them operable prior

to returning them to service after maintenance, repair or replacement

work is performed on the valve or its associated actuator, control or

power circuit.

The stroke timing test associated with these

containment isolation valves i s SI-166.6.

As for the 16 excluded

valves, section 6.8 of Technical Instruction (TI) -69, " Summary of

Pre-and Post-Maintenance Valve Tests For ASME Section XI and 10 CFR 50

Appendix

J,"

requires that a stroke timing test be performed per

SI-166.6 whenever maintenance of this nature is performed on a valve

control system. Consequently, the stroke timing test of each valve per

SI-166.6 would be required to be performed in order to prove valve

operability; however, SI-166.6 was not specified in either work plan as

a test to be performed.

Section 4.1.1.13.d (2) of Administrative

Instruction (AI)-19, Part IV, requires that any checks or tests

necessary -to return equipment back to service be specified in the WP.

The omission of SI-166.6 from the WPs is considered a violation of

AI-19, Part-IV (327, 328/86-43-01).

It should be noted that ongoing

MOVATS Testing of these valves, although not specified in the subject

work plans, will include a stroke test per SI-166.6.

g.

Residual Heat Removal (RHR) Loop Isolation Valves

ECN 6540 and WP 11906 replaced the existing motors on valves 2-FCV-74-1

and 2-FCV-74-2 with environmentally qualified motors.

These valves are the RHR suction isolation valves off of reactor

coolant loop 4 and are considered necessary to mitigate an RHR line

break.

Specified functional tests included megger, grease, and

rotational checks of the motors, and the performance of a stroke timing

test of the valves per SI-166.6. TS Surveilla"ce 4.4.6.2.2.c requires

that these valves be demonstrated operable by verifying leakage to be

within its limits prior to returning the valve (s) to service following

maintenance, repair or replacement work on the valve (s). Additionally,

TI-69 requires a Post-Maintenance Leak Test be performed on a motor

operated valve when motors are not replaced with identical motors. A

Leak Rate Test would be indicated in this case since the existing

motors were rated at 2.6 HP, whereas the replacement motors were rated

at 4~0 HP.

The Leak Test associated with these valves is SI-166.18,

.

"RHR Return Valve Leak Rate Test". The omission of SI-166.18 from the

WP as a specified test to be performed prior to returning the valves to

service is not in accordance with AI-19, Part IV. This is considered

another example of Violation 327,328/86-43-01 identified in paragraph f

above.

It is recognized that due to the duration of this outage,

SI-166.18 would have also been required to be performed by TS 4.4.6.2.2.c prior to entering mode 2.

This would be verified in

General Operating Instruction (GOI)-1, " Unit Heat Up From Cold

Shutdown to Hot Standby."

-

-

. - - _ _ _ .

. . _ _

.

. .

-

m

.

8

h.

Replace Solenoid Valves With New EQ Valves

4

ECN 6552 and WP 11897 replaced existing solenoid control valves with

new EQ valves required to meet the requirements of NUREG 0552. The WP

reviewed replaced 12 valves; three in system 43, six in system 62, one

in system 63, and two in system 87. The new valves were Automatic

Switch Co (ASCO) model #206-381 and model'#8316-54E.

Per the vendor

installation and maintenance instruction manual, the model #206-381

valves were required to be mounted with the solenoid vertical and

upright.

,

The inspectors review of the above WP verified that inspection records

,

were included.

These records indicated that the solenoid on valves

1

2-FSV-43-(202, 207 and 208), model #206-381, were oriented vertical .

However, when the inspector reviewed the installation and inspection

step of the WP, Step 8.2a of Vertical was defined as, " Vertical i 45 .

The inspector requested TVA provide justification for the 45

allowance.

The modification engineer eventually produced a letter

dated April 29, 1985, where an ASCO sales manager indicated that the

model 206 series valves could function with a solenoid orientation up

to 45

from vertical .

However, the letter went on to state that

seismic qualification for the 206 series was performed in the vertical

position only and the effects of mounting in the other orientation

would have to be evaluated. The inspector requested the seismic test

data for other vertical orientation and received (from TVA) Seismic

Simulation Test Report #17746-1.

This report documented the Wyle

Laboratories test performed June 9 and 10, 1986, for TVA under Purchase

Order TV-56071A. The test concluded that for the seismic event the

valves continued to function and maintain their structural integrity.

The inspector was satisfied with the information provided by TVA.

However, since TVA had installed the valves in April 1986, several

months before qualification testing, the modifications supervisor was

cautioned about the use of equipment in a manner not recommended or

qualified by the manufacturer without prior testing or qualification by

!

TVA.

Additionally, if the installation was conditioned to seismic

l

qualification af ter installation it sFould have been specified in the

WP. The functional testing review for this WP indicated that testing

was performed, however, cross referencing of the testing performed back

to the WP was not always documented.

Specifically, WP 11897 was not

referenced on a SI-166.6 test package or master list reference for

eight of the twelve valves. The inspector did, however, locate a valve

functional tet t performed on the same date indicated in the WP but no

reference back to the WP could be produced by the licensee.

SI-166.6

specifically required a test data package or master list notation to

tie the specific test to the work plan.

This failure to follow the

requirements of SI-166.6 is considered another example of Violation

327, 328/86-43-01 identified in paragraph f. above.

1

.

.

9

1.

Replacement of Cable PP711B in Cable. Tray AS-B1, Emergency Supply

Breaker Feeder From 6.9KV Shutdown Board 2B-B

ECN 6627 and WP 12040 replaced a section of cable identified as PP711B.

This work plan specified functional testing per SI-7 which was

accompitshed on June 17, 1986. No problems were identified with this

modification.

J.

PMT-74 Automatic Shunt Trip Modification Test (Unit 2)

ECN 6233 and WP 11890 specified the testing associated with the

Automatic Shunt Trip Modification on Unit

2.

This procedure had

several changes written prior to the completion of testing.

Change

  1. 86-488 modified the expected voltage values at a specific test point.

This' change was processed using a change form (Appendix G of AI-4) and

handled as an expeditious change.

To understand the temporary change

process as'used by TVA, the following is provided:

TS 6.8.3 allows temporary changes to plant committee approved

-

procedures under certain restrictions.

ANSI 18.7-1976, to which TVA is committed, also makes allowance

-

(paragraph 5.2.2) for the licensee to make temporary changes to a

procedure providing certain conditions are met.

This ANSI also

requires this procedure change program to be described in writing

by the licensee.

Document Control", is the plant

-

AI-4, " Plant Instructions

-

procedure TVA used to describe this Procedure Change Program.

Section 13 of this procedure discusses the actual change process.

The method of changing a Plant Operation Review Committee (PORC)

approved procedure in an expeditious manner is described in

paragraph 13.1.

AI-4 only allows expeditious changes under the

following two conditions:

(1) To make changes which will remain in effect for only a limited

number of instruction performances (e.g., an SI needs to be

performed differently this one time because the plant is in an

abnormal configuration).

(2) To make urgently needed revisions when there is not time to go

through the original type of review / approval cycle (e.g., an NRC

inspection identifies a serious deficiency in an instruction'which

must be corrected immediately).

In this case, the plant

instruction change form (Appendix G of AI-4) authorizes an

expeditious change practice until a permanent instruction change

can be issued.

,

.

.

10

As part of the Post Modification and Post Maintenance Testing

-

program, plant engineers routinely specify in the WP or on the

maintenance form to " accomplish the applicable portions" of

approved procedure.

This method appears to circumvent the

procedure change process as described in TS 6.8.3 and AI-4.

Additionally, if the user omits certain steps or picks and chooses

steps of the approved procedure he has in fact changed the intent

of the original procedure. In this case, TS 6.8.3 requires that a

change with the same level of review and approval be executed

prior to use.

The specific example of changing a committee approved procedure (ie.,

changes to WP 11890) in an-expeditious manner as well as the improper

changing of committee approved procedures

(i.e.,

" accomplish the

applicable portions") is considered a violation of TS 6.8.3

(327,

328/86-43-02).