ENS 47147: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 08/11/2011 16:31 EDT
| event date = 08/11/2011 16:31 EDT
| last update date = 08/11/2011
| last update date = 08/11/2011
| title = Loss Of Intake Cooling Water For 20 Minutes
| title = Loss of Intake Cooling Water for 20 Minutes
| event text = At 1631 hours on Thursday, August 11, 2011, Turkey Point Unit 3 lost the function of the Intake Cooling Water (ICW) System for approximately 20 minutes.  This is reportable in accordance with 10 CFR 50.72(b)(3)(v)(B) and (D).  Loss of function occurred when manual valve 3-50-406, ICW/Component Cooling Water (CCW) Heat Exchanger Outlet Valve, failed closed.  Valve 3-50-406 is located in the common discharge line preventing flow through both ICW headers to the CCW heat exchangers.  Operations Department personnel opened the bypass valves associated with the failed valve and restored ICW flow to the CCW heat exchangers at approximately 1651 hours.   
| event text = At 1631 hours on Thursday, August 11, 2011, Turkey Point Unit 3 lost the function of the Intake Cooling Water (ICW) System for approximately 20 minutes.  This is reportable in accordance with 10 CFR 50.72(b)(3)(v)(B) and (D).  Loss of function occurred when manual valve 3-50-406, ICW/Component Cooling Water (CCW) Heat Exchanger Outlet Valve, failed closed.  Valve 3-50-406 is located in the common discharge line preventing flow through both ICW headers to the CCW heat exchangers.  Operations Department personnel opened the bypass valves associated with the failed valve and restored ICW flow to the CCW heat exchangers at approximately 1651 hours.   
Presently, Unit 3 is in Mode 1 at 100% power with all systems stable.
Presently, Unit 3 is in Mode 1 at 100% power with all systems stable.

Latest revision as of 22:06, 1 March 2018

ENS 47147 +/-
Where
Turkey Point NextEra Energy icon.png
Florida (NRC Region 2)
Reporting
10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident
LER: 05000250/LER-2011-002
Time - Person (Reporting Time:+0.6 h0.025 days <br />0.00357 weeks <br />8.2188e-4 months <br />)
Opened: Nicholas Desantis
21:07 Aug 11, 2011
NRC Officer: Mark Abramovitz
Last Updated: Aug 11, 2011
47147 - NRC Website
Loading map...