ENS 51106: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 16: | Line 16: | ||
| event date = 05/31/2015 16:00 EDT | | event date = 05/31/2015 16:00 EDT | ||
| last update date = 06/02/2015 | | last update date = 06/02/2015 | ||
| title = Technical Specification Required Shutdown Due | | title = Technical Specification Required Shutdown Due to Failure of an Emergency Diesel Generator | ||
| event text = At 1600 [EDT] on May 31, 2015, [DC Cook] operations commenced a shutdown of DC Cook Unit 1 to comply with LCO 3.8.1 Condition G, when the 14 day limit to complete Condition B Required Action could not be met. | | event text = At 1600 [EDT] on May 31, 2015, [DC Cook] operations commenced a shutdown of DC Cook Unit 1 to comply with LCO 3.8.1 Condition G, when the 14 day limit to complete Condition B Required Action could not be met. | ||
At 0010 [EDT] on May 18, 2015, Unit 1 AB Emergency Diesel Generator was removed from service for planned maintenance. LCO 3.8.1 Condition B was entered which allows 14 days to restore diesel to operable. | At 0010 [EDT] on May 18, 2015, Unit 1 AB Emergency Diesel Generator was removed from service for planned maintenance. LCO 3.8.1 Condition B was entered which allows 14 days to restore diesel to operable. |
Latest revision as of 21:47, 1 March 2018
Where | |
---|---|
Cook ![]() Michigan (NRC Region 3) | |
Reporting | |
10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown | |
LER: | 05000315/LER-2015-001 |
Time - Person (Reporting Time:+-3.47 h-0.145 days <br />-0.0207 weeks <br />-0.00475 months <br />) | |
Opened: | Richard Harris 16:32 May 31, 2015 |
NRC Officer: | Mark Abramovitz |
Last Updated: | Jun 2, 2015 |
51106 - NRC Website
| |