ENS 51432: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
| Line 16: | Line 16: | ||
| event date = 09/29/2015 10:30 EDT | | event date = 09/29/2015 10:30 EDT | ||
| last update date = 09/29/2015 | | last update date = 09/29/2015 | ||
| title = Both Trains | | title = Both Trains of the Standby Gas Treatment System Declared Inoperable | ||
| event text = On 9/29/15 at 1020 EDT, the 'B' train of Standby Gas Treatment System was declared inoperable for planned testing. On 9/29/15 at 1030 EDT, during performance of a surveillance on Unit 1 Reactor Pressure Vessel water level instrumentation, one channel was found to not meet acceptance criteria. The failed level channel is part of the initiation logic for the 'A' train of Standby Gas Treatment. This resulted in a loss of safety function for the Standby Gas Treatment System. On 9/29/15 at 1145 EDT, the 'B' train of Standby Gas Treatment was restored to operable by restoring from the planned testing. | | event text = On 9/29/15 at 1020 EDT, the 'B' train of Standby Gas Treatment System was declared inoperable for planned testing. On 9/29/15 at 1030 EDT, during performance of a surveillance on Unit 1 Reactor Pressure Vessel water level instrumentation, one channel was found to not meet acceptance criteria. The failed level channel is part of the initiation logic for the 'A' train of Standby Gas Treatment. This resulted in a loss of safety function for the Standby Gas Treatment System. On 9/29/15 at 1145 EDT, the 'B' train of Standby Gas Treatment was restored to operable by restoring from the planned testing. | ||
This event is being reported under 10 CFR 50.72(b)(3)(v)(c) and per the guidance of NUREG 1022 Rev 3 section 3.2.7 as a loss of a Safety Function. | This event is being reported under 10 CFR 50.72(b)(3)(v)(c) and per the guidance of NUREG 1022 Rev 3 section 3.2.7 as a loss of a Safety Function. | ||
Latest revision as of 20:46, 1 March 2018
| Where | |
|---|---|
| Susquehanna Pennsylvania (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material | |
| LER: | 05000387/LER-2015-006 Regarding Loss of Safety Function Due to Inoperability of Both Trains of the Standby Gas Treatment System and a Loss of Safety Function of the Control Room Emergency Outside Air Supply System Due to Air Flow |
| Time - Person (Reporting Time:+0.43 h0.0179 days <br />0.00256 weeks <br />5.89014e-4 months <br />) | |
| Opened: | Carl Young 14:56 Sep 29, 2015 |
| NRC Officer: | Charles Teal |
| Last Updated: | Sep 29, 2015 |
| 51432 - NRC Website
| |